DFM 1616
DFM 1616
Product Description
The DFM-1616 Field Module provides additional I/O (16
universal inputs and 16 universal outputs) to Delta’s DSC-
1616E or ASM-24E BACnet Controllers. It communicates on
Delta’s LINKnet network.
Important Information
The DFM-1616 works only with the DSC-1616E and ASM-24E (firmware V3.33 R1 or later).
Package Contents
Product: DFM-1616 (Rev. 2.0a)
DFM-1616 (Rev.2.0a) Installation Guide
Related Documents
Delta Controls Wiring Guidelines
ORCAview Operator Guide
ORCAview Technical Reference Manual
Release Notes for related Firmware
Cautions or Warnings
This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap)
should be used when installing this product so that damage to the product does not occur.
Danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent
type recommended by the manufacturer. Dispose of used batteries according to the
manufacturer’s instructions. Replace the battery with type CR2032.
Equipment damage or loss of data may occur if these procedures are not followed as specified.
Installations requiring CE conformance: All wiring for CE rated products must use an extra low
voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating
transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% duty
cycle.
Mounting
The DFM-1616 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This
controller should be mounted in an appropriate location within packaged equipment or another enclosure that
meets code requirements.
Page 2 of 10
Document Edition 2.4
Board Layout
Page 3 of 10
Delta Controls
Controller Configuration
Controller Addressing
The DIP Switch is a binary switch. Each individual DIP switch represents a
unique value, which forms the controller address when added together.
To set the address, simply move the switches that add up to the controllers
desired address to the ON position.
Note: Each controller on the same LINKnet segment must have a unique DIP
switch address. LINKnet controllers can only be addressed between 1 and 12.
Page 4 of 10
Document Edition 2.4
Wiring General
All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2
transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product
and output loads.
Power
This product is designed to use a 24VAC Class 2 power supply. A single transformer may be used to power
multiple controllers and/or auxiliary field devices (actuators, etc.) provided the following conditions are met:
All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified devices
will damage both the transformer and connected equipment.
The transformer is properly sized, including line losses for the total VA requirements.
Polarity is observed between controllers (with respect to 24~ and Gnd).
Each controller is grounded as shown in the diagram below. This is important to protect equipment and
ensure a common ground reference for RS-485 communications.
The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits).
Make sure to ground the controller using the ground lug that is available on the
controller. The controller uses the ground lug to establish a common reference for
communications. If the controller is not grounded then communication problems
may occur.
Page 5 of 10
Delta Controls
Network Communication
The controller communicates on Delta Controls LINKnet network at 76,800 bps. Refer to Appendix E in the
V3.33 ORCAview Technical Reference Manual for further details on configuring the LINKnet network.
This functionality allows critical equipment (boiler/chiller pumps) to remain operational so that undesired results
will not occur. For example, if a boiler is being controlled through the DFM-1616 set the default value for the
boiler pumps in the output object to ON. If communication is lost, the boiler pumps will continue to run.
Page 6 of 10
Document Edition 2.4
Input Configuration
The input must be configured to accept the signal used by
the input device. Place the jumper for each input in the
correct location on the Input Type Selector Block. The
diagram to the right shows the factory default selection of
10 KΩ.
Output Configuration
Each HOA switch is HAND, OFF, AUTO from right to left.
HAND
AUTO
OFF
The HAND position allows a user to manually force the
output on, the OFF position allows a user to manually force
an output off, and the AUTO position allows the output to
be controlled automatically by the controller.
Indicators
LED Function Description
Power Controller Power This yellow LED turns on to indicate that the controller has power
Indicator applied.
Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate.
Network LINKnet (RS485) The green LED flashes to indicate when the controller is
(NET1) Communication transmitting out the port, and the red LED flashes to indicate when
Status Indicators the controller is receiving data through the port. If communication
is good, both LEDs will flash at a high rate.
Inputs Input Status A corresponding red LED varies in intensity and is brightly lit when
(IP1 – IP16) Indicators the associated input is receiving a low voltage input signal (i.e. a
closed contact, 0 VDC, 0mA or a high temperature reading or low
resistance).
Outputs Output Status A tri-color LED is used. Under automatic control, the
(OP1 – OP16) Indicators corresponding output LED is green and is on or off to match the
status of an associated binary output. The LED will also vary in
intensity relative to the output signal for an analog output. With
HOA switches, the output LED is red in the OFF position and
yellow in the HAND position.
Page 7 of 10
Delta Controls
Product Specifications
Page 8 of 10
Document Edition 2.4
CE - DECLARATION OF CONFORMITY
according to ISO/IEC Guide 22 and EN 45014
Supplementary Information
The product(s) herewith comply with the requirements of the EMC Directive 89/336/EEC. The
product(s) were tested in a typical configuration.
Lee Dickson
Quality Assurance Manager
Page 9 of 10
Delta Controls
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his
own expense.
ICES-003 This Class A digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulations
Cet appareil numérique de la Classe A Respecte toutes les exigences du Règlement sur le matérial
brouiller du Canada.
Page 10 of 10