GE KV2C USER GUIDE

Caution Code Display


Caution Display Probable Cause Remedy

CA 000 001 Low battery. Battery failed Replace battery.


test.
CA 000 010 Meter unprogrammed. Using Program the meter.
default values.
CA 000 040 Loss of program. Program the meter.
Programming interrupted.
Using previous values.
CA 000 400 Low potential on indicated Check circuit voltages.
phase.
CA 004 000 Demand overload warning Check for service overload
has exceeded programmed conditions.
threshold. Check programming
threshold value.
CA 040 000 Leading kVArh warning. a. Disable the warning.
b. b. Check system
operating parameters
if leading kVArh is
unexpected.
CA 400 000 Received kWh warning. a. Check meter socket
and CT wiring.
a. CT polarity is b. Disable caution.
incorrect. Check system
b. Energy is flowing operating parameters
from load to line. if reverse energy flow
c. c. Meter’s is unexpected.
internal wiring c. c. Check that
defective sensor connector is
properly seated.