INSTRUCTION MANUAL

R4EMLED-01
4W MAINTAINED LED EXIT BOX, C/w
4pcs legend stickers

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or
use of this product, consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification
For the latest technical information please visit our web site www.ledgrouprobus.com or www.ledgrouprobus.com.au

Specifications Installation:
Model No. R4EMLED-01 1. Ensure mains supply is switched off before commencing installation.
Operating mode maintained and 2. Remove the PC tray from the body of fitting.
non-maintained 3. Remove the cover of terminal from the PC tray by removing the screw.
Supply Voltage: 220-240V~50/60Hz 4. Knock out the intended cable entry hole suitable for your installation (Fit
Power Consumption: 4W cable gland if weatherproofing necessary).
Lumen Output: 50lm 5. Mark appropriate fixing points on wall or ceiling; check that fixings will
Colour Temperature: 6500K not impinge on concealed cables or pipes before drilling holes.
Beam Angle: 120o 6. Fix the PC tray to ceiling/wall using suitable screws.
Battery 3.6V 2Ah Ni-MH cells 7. Connect wires from unswitched supply to terminals on gear tray, Brown
Operating Temp Range: 5oC ~ 40oC to PL, Blue to N and green/yellow to Earth. There is a link between
IP Rating: IP20 switched live (SL) and permanent live (PL) terminals (maintained).
Safety Classification: Class I, Must be earthed LEDs controlled by switch, connect switched live wire to
Dimensions(mm): (L)347X(W)80X(H)218 terminal SL and permanent live to PL.
Weight: 1.0kg Note: if “SL” terminal not connected, fitting works as non-maintained.
Warranty: 2 year 8. Write installation date on battery and connect battery.
Installation: Ceiling or Wall mounting 9. Insert the legends into the ivory diffuser.
10. Attach the body of fitting into the PC tray.
Suitable for mounting on a normally flammable surface 11. Switch on supply: the green LED should come on indicating correct
Green LED indicator indicates battery charging mode battery charge has started. In the non-maintained unit, the LEDs only
Complies with AS/NZ2293.3. lights if the mains supply fails; In the maintained unit, the LEDs will
light(if switched live on), when the mains supply fails, battery will
operate LEDs in emergency mode.

ISO 9001:2008

Q UAL IT Y ASSU RE D CO MPANY

Information for the Product user:


1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE marked with
crossed out wheelie bin symbol).
2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre for waste electrical
equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.
3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is important that it is
separated from normal household waste and recycled in the WEEE chain
4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household waste, but should be
disposed of according to local WEEE regulations

The Installation must be carried out by an electrician


LED Group LED Group ROBUS Australia
Western Retail Park Tel: +353 1 7099000 9/210 Queensport Road North Tel: +61 73893 1488
Nangor Road Fax: +353 1 7099060 Murarrie Fax: +61 73112 1927
Dublin 12 Email: info@ledgrouprobus.ie QLD 4172 Email: purchases@ledgrouprobus.com.au
Ireland Website: www.ledgrouprobus.ie Australia Website: www.ledgrouprobus.com.au
Issue 1 110615 1
Testing The emergency lighting must be inspected and tested regularly in accordance with local codes of practice:
note: for safety reasons tests should be carried out during daylight hours.

The minimum recommended test schedule is as follows:

After installation, allow 24 hours to ensure full battery charge and then interrupt the supply; the maximum
duration time is 3 hours check that LEDs are still lighting. (NZ: 16 hour charge time, maximum duration time 2
hours)

1. Daily check that charge indicator LED is working


2. Monthly, interrupt mains for a short period and check LEDs light
3. Annual 12 month check, full duration test. Interrupt mains supply, LEDs will light and stay on for the
complete duration of the test: batteries must be replaced when they can no longer power the LEDs for 3
hours (NZ: 2 hours).
4. Complete record sheet on installation and retain in maintenance file.
5. Update file with ongoing test records for inspection by fire officer or other duly authorised person

Installation and Maintenance Record:

Installer

Installation Type

Installation test duration & Date

1st Year 2st Year 3st Year 4st Year 5st Year
Month Test
Signed Date Signed Date Signed Date Signed Date Signed Date
1 Short
2 Short
3 Short

4 Short

5 Short
6 Short
7 Short
8 Short
9 Short
10 Short
11 Short
Short
12
3Hr.

The Installation must be carried out by an electrician

LED Group LED Group Robus [ New Zealand Office ]


Western Retail Park Tel: +353 1 7099000 4 Henderson Place, Penrose
Nangor Road Fax: +353 1 7099060 Po Box 13642 www.ideal.co.nz
Dublin 12 Email: info@ledgrouprobus.ie Onehunga, Auckland www.rexellighting.co.nz
Ireland Website: www.ledgrouprobus.ie New Zealand www.ledgrouprobus.com.au 2
Installation diagram
Figure 1 Figure 2
347mm

80mm

218mm

Figure 3 Figure 4
255mm

42mm

Non-maintained maintained

L N SL PL N
From
battery
Brown

Brown

Red +
Blue

Blue
Y/G

Y/G

Black -

Figure 5 Figure 6

PL
SL

The Installation must be carried out by an electrician


LED Group LED Group ROBUS Australia
Western Retail Park Tel: +353 1 7099000 9/210 Queensport Road North Tel: +61 73893 1488
Nangor Road Fax: +353 1 7099060 Murarrie Fax: +61 73112 1927
Dublin 12 Email: info@ledgrouprobus.ie QLD 4172 Email: purchases@ledgrouprobus.com.au
Ireland Website: www.ledgrouprobus.ie Australia Website: www.ledgrouprobus.com.au 3