R4EMLED-01
4W MAINTAINED LED EXIT BOX, C/w
4pcs legend stickers
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or
use of this product, consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification
For the latest technical information please visit our web site www.ledgrouprobus.com or www.ledgrouprobus.com.au
Specifications Installation:
Model No. R4EMLED-01 1. Ensure mains supply is switched off before commencing installation.
Operating mode maintained and 2. Remove the PC tray from the body of fitting.
non-maintained 3. Remove the cover of terminal from the PC tray by removing the screw.
Supply Voltage: 220-240V~50/60Hz 4. Knock out the intended cable entry hole suitable for your installation (Fit
Power Consumption: 4W cable gland if weatherproofing necessary).
Lumen Output: 50lm 5. Mark appropriate fixing points on wall or ceiling; check that fixings will
Colour Temperature: 6500K not impinge on concealed cables or pipes before drilling holes.
Beam Angle: 120o 6. Fix the PC tray to ceiling/wall using suitable screws.
Battery 3.6V 2Ah Ni-MH cells 7. Connect wires from unswitched supply to terminals on gear tray, Brown
Operating Temp Range: 5oC ~ 40oC to PL, Blue to N and green/yellow to Earth. There is a link between
IP Rating: IP20 switched live (SL) and permanent live (PL) terminals (maintained).
Safety Classification: Class I, Must be earthed LEDs controlled by switch, connect switched live wire to
Dimensions(mm): (L)347X(W)80X(H)218 terminal SL and permanent live to PL.
Weight: 1.0kg Note: if “SL” terminal not connected, fitting works as non-maintained.
Warranty: 2 year 8. Write installation date on battery and connect battery.
Installation: Ceiling or Wall mounting 9. Insert the legends into the ivory diffuser.
10. Attach the body of fitting into the PC tray.
Suitable for mounting on a normally flammable surface 11. Switch on supply: the green LED should come on indicating correct
Green LED indicator indicates battery charging mode battery charge has started. In the non-maintained unit, the LEDs only
Complies with AS/NZ2293.3. lights if the mains supply fails; In the maintained unit, the LEDs will
light(if switched live on), when the mains supply fails, battery will
operate LEDs in emergency mode.
ISO 9001:2008
After installation, allow 24 hours to ensure full battery charge and then interrupt the supply; the maximum
duration time is 3 hours check that LEDs are still lighting. (NZ: 16 hour charge time, maximum duration time 2
hours)
Installer
Installation Type
1st Year 2st Year 3st Year 4st Year 5st Year
Month Test
Signed Date Signed Date Signed Date Signed Date Signed Date
1 Short
2 Short
3 Short
4 Short
5 Short
6 Short
7 Short
8 Short
9 Short
10 Short
11 Short
Short
12
3Hr.
80mm
218mm
Figure 3 Figure 4
255mm
42mm
Non-maintained maintained
L N SL PL N
From
battery
Brown
Brown
Red +
Blue
Blue
Y/G
Y/G
Black -
Figure 5 Figure 6
PL
SL