HT Cable Hot Spot & Discharge

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Location AIPO/PCE/J00060 P/E Ampang No.

2
Equipment 11/0.4kV Transformer 1 Manufacturer MTM 8/12/2015
Model Rating 1000kVA/53A 1:27:09 PM
Compartment 11kV R Ph. Cable Panel No. Humidity: 0.52
Panel

IR IMAGE VISUAL IMAGE

Spo2
43.5°C

40
Spo1

35

33.8°C

PARAMETER VALUE PARAMETER VALUE


Spot Temp. 1 (Spo1) 43.5°C Serial No. 10364
Spot Temp. 2 (Spo2) 37.3°C Heater (A)
Average Temp. - CB Position
Ambient Temp. 31.0°C Busbar Position
Delta T (∆T) 6.2°C Cable Type XLPE 70
Load (A)
Severity INTERMEDIATE

ULTRASOUND SPECTRUM
Decibel (dB) 25dB
Sound Characteristic Tracking
Severity CRITICAL

TEV (Background) dB
TEV Reading Pulse/ Category Severity
Cycle
Front
Back

Analysis:
Electrical discharge activity sound indicative of tracking profile was detected on the cable. The discharge is
accompanied by a hot spot on the same area possibly caused by discharge damage on the cable insulation.

Recommendations:
1. Cut off damaged cable section. Smooth rough and sharp edges.
GENERAL VIEW