GENERAL NOTES

1. ALL ELECTRONICS WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRONICS CODE.
2. ALL ELECTRONIC WORKS AND INSTALLATION SHALL BE PERFORMED UNDER THE STRICT SUPERVISION OF A
DULY LICENSED PROFESSIONAL ELECTRONICS ENGINEER ( PECE ).
3. ALL MATERIALS TO BE USED AND EQUIPMENT (CCTV & DVR) MUST BE OF HIGH QUALITY AND CONFORMS TO
INDUSTRY STANDARD.
4. INSTALLING PARTY SHOULD CONSULT THE OWNER AND OTHER TRADES WORKING IN THE SITE TO PROPERLY
SCHEDULE TO AVERT CONFLICT WORKING SCHEDULES.
5. THE PLANS AS DRAWN ARE BASED UPON THE ARCHITECTURAL PLAN AND DETAILS, THE PLANS IS
DIAGRAMMATICAL. DO NOT SCALE SHOW ALL FITTINGS. THE LOCATION OF CCTV AND OTHER EQUIPMENT IS
APPROXIMATE.
6. SHOULD THE CABLING OF CCTV BE INSTALLED IN A CONDUIT, CCTV CABLING MUST BE SEPARATED AND NOT
JOINED IN WITH POWER CABLING.
7. MOUNTING OF THE CCTV SHOULD BE IN A MANNER THAT IT IS NOT OBSTRUCTED AND MOUNTING HEIGHT
SHOULD NOT BE LOW AND TOO HIGH TO MAXIMIZE THE FIELD OF VIEW BUT NOT DEGRADE THE IMAGE QUALITY.

5880

4930 950
4930 950

750

750
1530

1800
1300

1300
5430

1730
4290

4290
8500

8770
5440

3710
750

750
1030

1030
1500

1500
900

900
UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR SECOND FLOOR


1 CCTV & SPEAKER LAYOUT 2 CCTV & SPEAKER LAYOUT
AUX1 SCALE 1:75 MTS AUX1 SCALE 1:75 MTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN AUX1
GENERAL NOTES
1. ALL ELECTRICAL WORKS HEREIN SHALL COMPLY WITH THE PROVISION
OF THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE,
THE RULES AND REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITY
CONCERNED, AND THE RULES AND REGULATIONS OF THE THE UTILITY
COMPANY CONCERNED SUCH AS COOPERATIVE, TELECOMM CO., ETC.
2. SERVICE POWER SUPPLY SHALL BE 230V, SINGLE (1) PHASE, 4-WIRES
60HZ SYSTEM.
3. WIRING METHOD SHALL BE DONE IN EMT AND IMC, AS INDICATED IN THE
DRAWING. MAIN: 100 AT/100AF, 230 V,60HZ 1Ø,2P BOLT-ON TYPE
DEMAND FACTOR (D.F.) = 80% USE: 2 - 30.0mm2 THHN + 1 - 8.0mm2 THW in 32mmØ RSC
4. MINIMUM BRANCH CIRCUIT WIRE SHALL BE 3.5 MM THHN COPPER WIRE I f = [ (123.7 A) X 80% D.F ] = 98.928 A
FOR LIGHTING AND POWER SYSTEM AND RACEWAYS SHALL BE 15MM DIA. PROVIDE GROUNDING TERMINAL
EMT. TRADE SIZE CONDUIT, WIRES SHALL BE INSULATED FOR 600V.
TELECOMM CABLE SHALL BE UTP # 22 AWG 8/C
5. ALL BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE
INDIVIDUAL BRANCH CIRCUIT, HOMERUNS SHALL NOT BE COMBINED IN THE
SAME RACEWAY.
6. ALL JUNCTION, PULL, OUTLET AND SWITCH BOXES SHALL BE PRIMER
PAINTED AND WITH COVER PLATE.
7. WHENEVER NECESSARY PULL BOX OF PROPER SIZES AND DIMENSIONS
SHALL BE PROVIDED ALTHOUGH NOT INDICATED IN THE DRAWING.
8. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED FOR THE
INTENDED LOCATION AND PURPOSE.
9. FOR EACH SPARE BRANCH CIRCUIT IN PANEL BOARDS, PROVIDE 20MM
DIA. EMT CONDUIT TERMINATING IN DEEP TYPE SQUARE BOX WITH COVER
BELOW CEILING SLAB. MAIN: 80AT/100AF, 230 V,60HZ 1Ø,2P BOLT-ON TYPE
10. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER DIRECT AND DEMAND FACTOR (D.F.) = 80% USE: 2 - 30.0mm2 THHN + 1 - 8.0mm2 THW in 32mmØ RSC
I f = [ (88.16A) X 80% D.F ] = 70.528 A
IMMEDIATE SUPERVISION OF DULY QUALIFIED LICENSED ELECTRICAL PROVIDE GROUNDING TERMINAL
ENGINEER OR MASTER ELECTRICIAN.

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN EE1
5880

4930 950
4930 950

750

750
1800
1530

1300

1300
5430
2

1730
2
4290

4290
8770
8500

5440

3710
750

750
1030

1030
1500

1500
900

900
UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR SECOND FLOOR


1 LIGHTINGS LAYOUT PLAN 2 LIGHTINGS LAYOUT PLAN
EE2 SCALE 1:75 MTS EE2 SCALE 1:75 MTS

5880

4930 950
4930 950
750

750
1800
1530

1300
3

1300
5430

6
4

1730
4290

4290
8770
8500

5440

3710
4
750

750

5
1030

1030
1500

1500
900

900
UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR SECOND FLOOR


3 POWER LAYOUT PLAN 4 POWER LAYOUT PLAN
EE2 SCALE 1:75 MTS EE2 SCALE 1:75 MTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN EE2
GENERAL NOTES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
2. EXECUTE THIS PLAN IN ACCORDANCE TO THE EXISTING GUIDELINES REGULATION OF
THE LATEST NATIONAL FIRE PROTECTION ASSOCIATION, THE FIRE CODE OF THE
PHILIPPINES, THE NATIONAL BUILDING CODE AND IN PLACE RESIDENCES TENANT
GUIDELINES.
3. THE CONTRACTOR SHALL COORDINATE WITH OTHER RELATED TRADE PRIOR TO THE
INSTALLATION.
4. THE CONTRACTOR SHALL VERIFY THE ACTUAL DIMENSION AND LOCATION OF
PROPOSED PIPES, ANY DEVIATION OR RELOCATION SHALL BE WITH PRIOR APPROVAL
OF BUILDING OWNER/ ADMINISTRATOR.
5. ALL THE B.I. PIPES FOR BRANCH LINES W/ ADEQUATE HANGERS SHALL BE
HYDROSTATICALLY TESTED AT 150 PSI FOR A DURATION OF TWO HOURS AND SHOULD
BE WITNESSED & CERTIFIED BY THE ENGINEER AND BUILDING OWNER'S
REPRESENTATIVE.
6. PIPE MATERIALS AND SPRINKLER HEAD SPECIFICATION SHALL CONFORM TO THE
SPECIFIED BRAND AND REQUIREMENTS.
7. ALL SPRINKLER HEADS SHALL BE RATED AT 165 DEGREE F.
8. ALL SPRINKLER HEAD ELEVATION SHALL BE MINIMUM OF 2300 MM FROM FINISH FLOOR
LEVEL.
9. ALL SPRINKLER WORKS SHALL BE DONE ONLY BY A CONTRACTOR WITH TECHNICAL
EXPERTISE IN SPRINKLER SYSTEM INSTALLATION.

5880

4930 950
4930 950

750
750

1800
1530

1300
1300
5430

1730
4290
4290

8770
8500

5440

3710
750
750

1030
1030

1500
1500

900
900

UPRIGHT SPRINKLER UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR GROUND FLOOR SECOND FLOOR


1 SPRINKLER DETAIL 2 FIRE PROTECTION 3 FIRE PROTECTION
FP1 SCALE NTS FP1 SCALE 1:75 MTS FP1 SCALE 1:75 MTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN FP1
GENERAL NOTES
AIRCONDITIONING EQUIPMENT SCHEDULE
1. ALL MECHANICAL WORKS HEREIN INCLUDED SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST
REQUIREMENT OF THE PHILIPPINES NATIONAL BUILDING CODE AND THE REGULATION OF QUEZON CITY. COOLING FAN DATA WEIGHT DIMENSION ELECTRICAL SUPPLY
AREA
UNIT QTY. CAPACITY UNIT SHIPPING R E M A R K S
2. WORMANSHIP: THE WORK THROUGHOUT SHALL BE EXECUTED IN THE BEST AND MOST THOROUGH MANNER SERVED
(HP/TR) AIR FLOW CFM UNIT SHIPPING
(W/H/D) (W/H/D)
VOLTS PHASE HERTZ
TO KNOWN TO TRADE AND TO THE SATISFACTION OF THE ARCHITECT AND ENGINEER.
FCU - 01 1 AS SHOWN 6 HP 988 38 N/A 235/1590/690 N/A 230 SINGLE 60
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING ALL GOVERNMENT / LOCAL CONSTRUCTION AND
FCU - 02 1 AS SHOWN 6 HP 988 50 N/A 1850/600/350 N/A 230 SINGLE 60
OPERATION PERMITS AND PAY ALL THE REQUIRED FEES AND REQUIRED TO PROVIDE THE AS-BUILT PLANS.
4.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL THE FOUNDATIONS / SUPPORTS ALL MECHANICAL FCU - 03 1 AS SHOWN 3 TR 988 38 N/A 235/1590/690 N/A 230 SINGLE 60

EQUIPMENT.
5.DURING THE PROCESS OF THE WORKS SECURE THE CONSTRUCTION MEMBERS AND TOOL INSTALLATION PLACE.
THE TOOLS MUST BE USED ACCORDING TO THE TYPE OF APPLICATION.ALWAYS CARRY OUT WORK WITH DEDICATED
TOOLS.
6. ALL WORKS CARRIED OUT IN THE INSTALLATION OF THE AIR CONDITIONING EQUIPMENT SHALL CONFORM
THE MANUFACTURERS INSTALLATION GUIDELINES.

5880

4930 950
4930 950

750
750

1800
1530

1300
1300

5430

3 CEILING SUSPENDED DETAIL


M-1 SCALE NTS

1730
4290
4290

8770
8500

5440

3710
750
750

1030
1030

1500
1500

900
900

UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR SECOND FLOOR


1 AIRCONDITIONING LAYOUT 2 AIRCONDITIONING LAYOUT
M-1 SCALE 1:75 MTS M-1 SCALE 1:75 MTS
4 ACCU MOUNTING DETAIL
M-1 SCALE NTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN ME1
5880 5880
GENERAL NOTES 4930 950 4930 950

RISER
1. ALL PLUMBING WORKS HEREIN INCLUDED HEREIN SHALL BE EXECUTED IN ACCORDING TO THE

750

750
PROVISIONS OF THE NATIONAL PLUMBING CODE, THE NATIONAL BUILDING CODE AND THE RULES AND

1530

1530
REGULATIONS OF THE LOCAL GOVERNMENT AUTHORITY.

1300

1300
2. COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND SPECIFICATION THE ENGINEER
SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCY FOUND HEREIN.
3. ALL PIPES SHALL BE INSTALLED AS INDICATED ON PLANS. ANY RELOCATIONS REQUIRED FOR PROPER
EXECUTION OF OTHER TRADE SHALL BE WITH PRIOR APPROVAL WITH THE ARCHITECT OR ENGINEER.
4.PROPOSED SANITARY UTILITIES SHALL CONFORM TO THE ACTUAL LOCATION DEPTH AND INVERT

4290

4290
ELEVATION OF ALL EXISTING PIPES AND STRUCTURES AS VERIFIED BY THE CONTRACTOR

8500

8500
5440

5440
5.ALL SLOPE FOR HORIZONTAL DRAINAGE SHALL MAINTAIN 1 % UNLESS OTHERWISE SPECIFIED.
6. SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS.

750

750
7. THE CONTRACTOR SHALL VERIFY ALL EXISTING UTILITIES ON SITE. COORDINATE TAPPING POINT FOR
SEWAGE DISPOSAL, DRAINAGE TAPPING POINT AND WATER LINE SERVICE CONNECTING POINT. UNLESS

1030

1030
OTHERWISE SPECIFIED.

1500

1500
900

900
8.ALL PIPES SIZES ARE IN MILLIMETERS AND ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE
SPECIFIED. UP UP

900 2340 900 2100 940 900 2340 900 2100 940

LEGENDS & ABBREVIATION

GROUND FLOOR GROUND FLOOR


SP/WP SOIL PIPE/WASTE PIPE 1 SANITARY LAYOUT PLAN 2 WATER LINE LAYOUT PLAN
P1 SCALE 1:75 MTS P1 SCALE 1:75 MTS

WM WATER METER

VTR VENT THRU ROOF 4930 950 4930 950


TO MAIN WATER LINE

FD FLOOR DRAIN

750

750
1800

1800
1300

1300
LAV LAVATORY 5430 5430

WC WATER CLOSET

1730

1730
CO CLEAN OUT
4290

4290
8770

8770
B BIDET

3710

3710
HB HOSE BIB
750

750
FL FLUSH
1030

1030
F FAUCET

1500

1500
900

900
GT GATE VALVE
900 2340 900 2100 940 2120 900 2000 940 900 2340 900 2100 940 2120 900 2000 940

13140 13140

SECOND FLOOR SECOND FLOOR


3 SANITARY LAYOUT PLAN 4 WATER LINE LAYOUT PLAN
P1 SCALE 1:75 MTS P1 SCALE 1:75 MTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN P1
SD SD SD
ZONE 1
B
MPS

FACP
GROUND FLOOR
1 SINGLE LINE DIAGRAM
FDAS1 SCALE NTS

SD SD SD SD SD
ZONE 1
B
MPS

FACP
SECOND FLOOR
2 SINGLE LINE DIAGRAM
FDAS1 SCALE NTS

5880

4930 950
4930 950

750
750

1800
1530

1300
1300
5430
B
MPS

1730
B
MPS

4290
4290

8770
8500

5440

3710
750
750

1030
1030

1500
1500

900
900
UP

900 2340 900 2100 940 2120 900 2000 940


900 2340 900 2100 940
13140

GROUND FLOOR SECOND FLOOR


3 SMOKE DETECTOR LAYOUT 4 SMOKE DETECTOR LAYOUT
FDAS1 SCALE 1:75 MTS FDAS1 SCALE 1:75 MTS

SUNSET DRYGOODS & LOUNGE


ALFONSO REI N DEL ROSARIO AS SHOWN FDAS1