water outlet, the static pressure at that outlet is calculated as being equal to 0.433 psi pressure for each foot
of difference in elevation between the outlet and the water level in the tank. In this case, the minimum static
pressure at the outlet should be determined as that corresponding to the Iev~1 of the lowest water level at
which the tank is intended to operate.
This circuit is called the Basic Design Circuit (BOC) for sizing the main water lines and risers.
In most systems, the BDC will be found to be the run of cold water supply piping extending from the source
of supply to the domestic hot water vessel pIns the run of hot water supply piping extending to the highest and
most remote hot water outlet on the system. However, in systems supplied directly from the public main and
having flushometcr-valve water closets at the topmost floor, the BDC may be found to be the run of cold
water supply piping extending from the public main to the highest and most remote flushometer valve on the
system.
5/8" 20gpm
3/4" 30gpm
1" 50gpm
1-1/2" 100gpm
2" 160gpm
3" 300gpm
Also, the standard establishes the maximum pressure loss corresponding to these maximum capacities as
follows:
15 psi for the 5/8", 3/4" and 111 meter sizes
20 psi for the 1_ll2 tt , 2 11• 3". 4 11 and 6" sizes.