Table 13.6.

1
SIZE OF VERTICAL CONDUCTORS AND LEADERS
Nominal Flow Allowable Projected Roof Area
Diameter Capacity at Various Rates of Rainfall per Honr (Sq. Ft.)
(inches) (GPM) I" 2" 3" 4" 5" 6"
2" 23 2,180 r,090 727 545 436 363
3" 67 6,426 3,213 2,142 1,607 1,285 1,071
4" 144 13,840 6,920 4,613 3,460 2,768 2,307
5" 261 25,094 12,547 8,365 6,273 5,019 4,182
6" 424 40,805 20,402 13,602 10,201 8,161 6,801
8" 913 87,878 43,939 29,293 21,970 17,576 14,646
10" 1655 159,334 79,667 53,11 I 39,834 31,867 26,556
12" 2692 259,095 129,548 86,365 64,774 51,819 43,183
15" 4880 . 469,771 234,886 156,590 117,443 93,954 78,295
7" 8" 9" lO" ]]11 12"
2" 23 311 272 242 218 198 182
3" 67 918 803 714 643 584 536
4" 144 1,977 1,730 1,538 1,384 1,258 1,153
5" 261 3,585 3,137 2,788 2,509 2,281 2,091
6" 424 5,829 5,101 4,534 4,080 3,710 3,400
8" 913 12,554 10,985 9,764 8,788 7,989 7,323
JO" 1655 22,762 19,917 17,704 15,933 14,485 13,277
]2" 2692 37,014 32,387 28,788 25,910 23,554 21,591
15" 4880 67,110 58,721 52,197 46,977 42,706 39,146

NOTES:
l. Flow capacities are based on stacks flowing 7/24 full.
2. Interpolation between rainfall rates is permitted.

13.9 CONTROLLED FLOW STORM WATER SYSTEM·

13.9.1 Application
In lieu of sizing the storm drainage system on the basis of actual maximum projected roof areas as previously
described in this Chapter, the roof drainage system, or part thereof may be sized on equivalent or adjusted
maximum projected roof areas that result from controlled flow and storage of storm water on the roof pro-
vided flow control devices are used and subject to the approval ofthe Authority Having Jurisdiction.

13.9,2 Design
A controlled flow storm water system shall be designed, installed, inspected and certified as an engineered
special design plumbing system as outlined in Appendix E ofthis Code.

2006 Notional Standard Pl"mbing Code-lIlusrraled 321