Specification FRLS Cables
Specification FRLS Cables
This specification covers the minimum requirements and guidelines for Fire
Retardant Low Smoke (FRLS) Cables (Copper/ Aluminium) upto 1.1 KV
Voltage Grade.
In closed and crowded places such as subways; road and railway tunnels;
cinema halls, hospitals, schools, office complexes and public premises in
general, the speed of spread of fire is a critical factor. Besides this, the
opacity and toxicity of the fumes are very important factors as these may
lead to intoxication and suffocation, besides causing panic among the
victims due to reduced visibility. FRLS cables are generally used in such
areas where safety of persons and/ or protection of equipment are of
paramount importance.
5.0 Inspection:
Inspection shall be carried out in conformity with the ordered
Specifications; IS 7098-1, IS 1554-1, IS 3975-1999, IS5831-1984, IS
8130-1984, IS 10810-1984, ASTM D2863, ASTM D2843, IEC60331,
IEC 60332 and other relevant standards
Visual Inspection:
Manufacturer’s Name; Voltage Grade of cable; No. of cores; Size of cable;
Length of cable; Type of armouring; Material of Conductor; Year of
Manufacture
Routine Tests:
Conductor resistance test; High voltage test.
Type Tests:
All Type tests listed in Relevant Conformance Standard shall be reviewed
and confirmed by authorized ONGC inspecting authority to be in order
and the certificates thereof have been submitted.
Acceptance Tests:
All Acceptance tests listed in Relevant Conformance Standard shall be
performed on cable samples drawn by authorized ONGC inspecting
authority and shall be witnessed by him.
Documentation:
1. Test reports for the cable.
2. Warranty/ Guarantee certificate.
3. Certificate that the item has been designed, manufactured and tested to
meet the specified requirement.
4. Calibration reports/ status reports of instruments used in testing.
5. Proof of ISO 9001-2008 Certification.