Professional Documents
Culture Documents
Upc 2021
Upc 2021
TABLE 422.1
MINIMUM PLUMBING FACILITIES1
Fach building shall be provided with sanitary facilities, including provisions for persons with disabilities as prescribed by the Department Having Jurisdic -
tion. Table 422.1 applies to new buildings, additions to a building , and changes of occupancy or type in an existing building resulting in increased occupant
load .
BATHTUBS DRINKING
URINALS OR FOUNTAINS
TYPE OF WATER CLOSETS ( FIXTURES LAVATORIES SHOWERS FACILITIES
^
OTHER
OCCUPANCY 2 ( FIXTURES PER PERSON )3 PER (FIXTURES PER PERSON )5 ( FIXTURES ( FIXTURES I
PERSON )4 PER PER
PERSON) PERSON)
-
A l Assembly occupancy Female
Female
(fixed or permanent seat- 1: 1-25 Male Male
Male 1: 1-100
ing )- theaters, concert
1 : 1 - 100
2: 26 - 50 -
1; 1 200 -
1; 1 200
2 : 101 -200
1; 1-250
halls, and auditoriums 3: 51 -100 2 : 201 -300 2 : 201 -400 2 : 251-500
2: 101 - 200
4: 101 - 200 3 : 301 -400 3: 401 -600 -
4 : 201 300
3: 501-750
3: 201 -400 5 : 301 -500 1 service
6: 201 - 300 -
4 : 401 600 4 : 601 -750
6 : 501 -750 sink or
8 : 301 -400
laundry tray
Over 600 , Over 750 ,
Over 400, add 1 fixture for Over 750, add 1 fixture for
add 1 fixture add 1 fixture
each additional 500 males each additional 250 males
for each for each
and 1 fixture for each and I fixture for each
additional additional
additional 125 females. additional 200 females.
300 males. 500 persons.
A-2 Assembly occu- Female
pancy- restaurants, pubs , Male 1: 1-25 Male
Male Female
lounges, niehtclubs and 1: 1 -50 2 : 26 - 50 1: 1 -200 1: 1-250
1: 1-150 1; 1- 150
banquet halls 2: 51-150 3: 51-100 2 : 201 -300 2 : 251-500
2 : 151-200 2 : 151 -200
3: 151 - 300 4: 101 - 200 3 : 301 -400 3 : 501-750
3: 201 -400 4: 201-400 1 service
4: 301 -400 6: 201 - 300 4 : 401 -600
8 : 301-400 sink or
laundry tray
Over 600, Over 750 ,
Over 400, add 1 fixture for Over 400, add 1 fixture for
add 1 fixture add 1 fixture
each additional 250 males each additional 250 males
for each for each
and 1 fixture for each 125 and 1 fixture for each
additional additional
females. additional 200 females
300 males. 500 persons.
A-3 Assembly occupancy Female
Female
( typical without fixed or 1 : 1 -25 Male Male
Male 1: 1-100
permanent seating ) - 2: 26 - 50 1: 1-100 1: 1-200 1: 1-250
arcades, places of wor -
1 : 1 - 100
3: 51 -100 2 : 101 -200 2 : 201 -400 -
2 : 101 200
2 : 251-500
2: 101 - 200 4: 201 -300
ship , museums, libraries , 4: 101 -200 3 : 201 -400 3: 401-600 3 : 501-750
3: 201 -400 5 : 301 -500 1 service
lecture halls, gymnasiums 6: 201 - 300 4 : 40 i -600 4 : 60 i -750
( without spectator seat-
6 : 501 -750 sink or
8 : 301 -400
ing ) , indoor pools ( with - laundry tray
Over 600 , Over 750 ,
out spectator seating ) Over 400, add 1 fixture for Over 750, add 1 fixture for
add 1 fixture add 1 fixture
each additional 500 males each additional 250 males
for each for each
and 1 fixture for each and I fixture for each
additional additional
additional 125 females. additional 200 females.
300 males. 500 persons.
A-4 Assembly occupancy Female
( indoor activities or sport- Female
1: 1-25 Male
ing events with spectator Male Male 1: 1-100
2 : 26 - 50 1: 1-100 1: 1-250
seating )- swimming pools, :
1 1 - 100 1: 1-200 2 : 101 -200
2 : 101 -200 2 : 251-500
skating nnks, arenas, and 2: 101 - 200 3: 51 -100 -
2 : 201 400 -
4 : 201 300
3 : 201 -400
3: 201 -400 4: 101 - 200
3 : 501-750
gymnasiums 3: 401-750 5 : 301 -500 1 service
6: 201 - 300 4 : 401 -600 6 : 501 -750 sink or laun-
8 : 301 -400 dry trav
tr '
f
TABLE 422.1
MINIMUM PLUMBING FACILITIES1 ( continued)
BATHTUBS DRINKING
URINALS OR FOUNTAINS
TYPE OF WATER CLOSETS ( FIXTURES LAVATORIES SHOWERS FACILITIES
^
OTHER
I OCCUPANCY5 ( FIXTURES PER PERSON )3 PER (FIXTURES PER PERSON )5 ( FIXTURES ( FIXTURES
PERSON )4 PER PER
PERSON) PERSON)
A-5 Assembly occupancy Female
( outdoor activities or Female
1: 1-25 Male
sporting events)- amuse- Male Male 1: 1-100
2: 26 - 50 1: 1-100 1: 1-250
ment parks, grandstands 1 : 1 - 100 1; 1-200 2 : 101 -200
2: 101 - 200
3: 51 -100 -
2 : 101 200
2 : 201-400 4 : 201 -300
2 : 251-500
and stadiums 4: 101 - 200 3 : 201 -400 3 : 501-750
3: 201 -400 3: 401-750 5 : 301 -500
6: 201 - 300 4 : 401 -600 1 service
6 : 501 -750
8 : 301-400 sink or
Over 600 , Over 750 , laundry tray
Over 750, add 1 fixture for add 1 fixture
Over 400, add 1 fixture for add 1 fixture
each additional 250 males for each
each additional 500 males for each
and I fixture for each additional
and 1 fixture for each additional
additional 200 females.
additional 125 females. 300 males. 500 persons.
TABLE 422.1
MINIMUM PLUMBING FACILITIES1 ( continued)
BATHTUBS DRINKING
URINALS OR FOUNTAINS
TYPE OF WATER CLOSETS ( FIXTURES LAVATORIES SHOWERS FACILITIES
^
OTHER
OCCUPANCY 2 ( FIXTURES PER PERSON)3 PER (FIXTURES PER PERSON)5 ( FIXTURES ( FIXTURES I
PERSON)4 PER PER
PERSON) PERSON)
1-2 Institu- Hospitals
tional occu- and nursing 1 per room 1 per room 1 per room
1 service
pancy-medi homes -indi-
1 per 150 sink or
cal, psychi- viduai
atric, surgi- rooms and 1 per 20 laundry tray
1 per 8 patients 1 per 10 patients
cal or ward room patients
nursing Hospital
homes Waiting or
1 per room 1 per room 1 per room
Visitor
Rooms
Male Female
1: 1 - 15 1: 1-15
2: 16 -35 3: 16 - 35
Employee 3: 36 - 55 4: 36 -55
Male Female
Use 1 per 40 1 per 40
Over 55 , add 1 fixture for
each additional 40 per -
sons.
1-3 Institu- 1 per cell
Prisons 1 per cell 1 per cell 1 per 20
tional occu- block/floor
pancy Correctional
(houses 1 service
facilities or
more than 5 1 per 8 1 per 10 1 per 8 1 per floor sink or laun-
juvenile
people) dry tray
center
Male Female
1: 1 - 15 1: 1- 15
2: 16 - 35 3: 16 - 35
Employee 3: 36 - 55 4: 36 - 55
Male Female
1 per 150
Use 1 per 40 l per 40
Over 55 , add 1 fixture for
each additional 40 per -
sons.
1-4 Institutional occu- Male Female
pancy ( any age that 1: 1 - 15 1: 1 - 15
receives care for less than 2: 16 - 35 3: 16 - 35 1 service
3: 36 - 55
Male Female
24 hours) 4: 36 - 55 1 per 150 sink or
1 per 40 1 per 40
Over 55 , add 1 fixture for laundry tray
each additional 40 per -
sons.
M Mercantile occupancy Female
Male Female
(the sale of merchandise 1: 1 - 100 Male Male 1: 1-250 1 service
1: 1 - 100 1: 1-200
and accessible to the pub- 2: 101 - 200 0: 1 - 200 1; 1-200 2 : 251- 500 sink or
2: 101 - 200 2 : 201-300
lie) 4: 201 - 300 1 : 201-400 2 : 201-400 3 : 501-750 laundry tray
3 : 201 - 400 3 : 301-400
6: 301 -400
Over 400, Over 750,
Over 400, add 1 fixture for Over 400, add I fixture for
add 1 fixture add 1 fixture
each additional 500 males each additional 500 males
for each for each
and 1 fixture for each 200 and 1 fixture for each 400
additional additional
females. females.
500 males. 500 persons.
R- l Residential occu-
1 service
pancy ( minimal stay )- 1 per sleep -
hotels, motels, bed and 1 per sleeping room 1 per sleeping room sink or
ing room
laundry tray
breakfast homes
TABLE 422.1
MINIMUM PLUMBING FACILITIES1 ( continued)
BATHTUBS DRINKING
URINALS OR FOUNTAINS/
TYPE OF WATER CLOSETS ( FIXTURES LAVATORIES SHOWERS FACILITIES
OTHER
I OCCUPANCY 2 ( FIXTURES PER PERSON)3 PER
PERSON)4
(FIXTURES PER PERSON)5 (FIXTURES
PER
( FIXTURES
PER
PERSON) PERSON)
1 kitchen sink
per apartment.
1 laundry trav
or 1 automatic
clothes washer
Apartment 1 pei' connection per
1 per apartment 1 per apartment
house /unit apartment unit or 1 laun-
dry tray or 1
automatic
clothes washer
connection tor
each 12 units
-
R 3 Residential occu- Male Female Male Female
pancy (long-term or per - 1 per 10 1 per 8 I per 12 1 per 12
manent in nature) for
Add 1 fixture for each Add 1 fixture for each 1 service sink
more than 5 hut does not 1 per 8 1 per 150
additional 25 males and 1 additional 20 males and 1 or laundry tray
exceed 16 occupants)
fixture for each additional fixture for each additional
20 females. 15 females.
R-3 Residential occu-
pancy ( one and two fam- 1 kitchen
ily dwellings) sink and 1
1 per one automatic
1 per one and two family 1 per one and two family and two clothes washer
dwelling dwelling family connection per
dwelling one and two
family
dwelling
TABLE 422.1
MINIMUM PLUMBING FACILITIES1 ( continued)
BATHTUBS DRINKING
URINALS OR FOUNTAINS/
TYPE OF WATER CLOSETS ( FIXTURES LAVATORIES SHOWERS FACILITIES
OTHER
OCCUPANCY 2 ( FIXTURES PER PERSON)3 PER (FIXTURES PER PERSON)5 (FIXTURES ( FIXTURES I
PERSON)4 PER PER
PERSON) PERSON)
S- 1, S-2 Storage occu - Male Female Male Female
1; 1-250
pancy-storage of goods , 1: 1 - 100 1: 1 - 100 1: 1-200 1: 1-20G
2 : 251-500
warehouse , aircraft 2: 101 - 200 2: 101 - 200 2 : 201-400 2 : 201-400
3: 501-750
hanger, food products, 3 : 201 - 400 3: 201 -400 3: 401-750 3: 401-750
appliances Over 750, 1 service sink
Over 400, add 1 fixture for add 1 fix - or laundry tray
Over 750, add 1 fixture for
each additional 500 males ture for
each additional 500 per -
and 1 fixture for each each addi -
sons.
additional 150 females. tional 500
persons.
Notes :
L
The figures shown arc based upon one fixture being the minimum required for the number of persons indicated or any fraction thereof.
1
A restaurant is defined as a business that sells food to be consumed on the premises.
a. The number of occupants for a drive -in restaurant shall be considered as equal to the number of parking stalls .
b. Hand-washing facilities shall be available in the kitchen for employees.
3
The total number of required water closets for females shall be not less than the total number of required water closer and urinals for males.
4
For each urinal added in excess of the minimum required one water closet shall be permitted to be deducted. The number of water closets shall not be reduced
,