WP01049A24EN0117 - 0519-Optimize Biogas Production With Accurate, Real-Time Monitoring - v001
WP01049A24EN0117 - 0519-Optimize Biogas Production With Accurate, Real-Time Monitoring - v001
Real-Time Monitoring
Prosonic
Flow B 200
Condensate Particle
Digester trap filter
Prosonic
Flow B 200
Prosonic
Flow B 200 Cerabar M Cerabar M Gas motor
PMP51 PMP51
Filter
Prosonic S M
FMU90
Gas tank
Gas control path
Prosonic S
FDU90
Boiler
Prosonic
Gas Flow B 200 Cerabar M Cerabar M
compressor PMP51 PMP51
Filter
What conditions must be quality of the biogas. If the bacterial temperature, tank level, proper
maintained to keep anaerobic health declines without indication mixing, pH, and actual biogas flow/
digesters operating properly? and with no corrective action, the percent methane content.
process loses efficiency, and the
The process begins with a consistent volume of waste that can be treated Which methods are typically used
supply of organic matter. Also, an is reduced dramatically. While other to analyze and record these
oxygen-free environment, constant parameters like temperature and pH parameters?
temperature (95°F), proper mixing, are important to the overall health of
and a relatively neutral pH (6.6-7.6) the digester, they can be slow to Typically, in process plants we see
all play an important role in this react. A significant loss of biogas two types of control, i.e.,
application. production and methane programmable logic controller (PLC)
concentration in the biogas is or distributed control system (DCS).
What problems occur when an a rather fast indicator. These supervisory control and data
anaerobic digester gets “out of acquisition (SCADA) systems monitor
sorts?” Which are the most important and control all the signals generated
parameters to monitor to ensure from various field devices, such as
There is an old adage in process optimum biogas production? instrumentation, pumps, motors,
control which says, “what cannot be and drives. A human machine
measured cannot be controlled.” A consistent supply of organic matter. interface (HMI) displays all the
Most plants want to know the Other basic parameters are an parameters and acts as a window to
quantity but more importantly the oxygenfree environment, constant the process for the plant operators.
What are common challenges for What type of instrumentation can Is there a risk of explosion when
using instrumentation to monitor accurately provide realtime using instrumentation to measure
anaerobic digester performance? monitoring of biogas flow, biogas?
temperature, and methane content
A major challenge is finding accurate for anaerobic digestion systems? Biogas contains methane (CH4),
and repeatable instrumentation that which is a highly combustible gas.
performs over time and measures Ultrasonic “transit time” technology Thus, the overall anaerobic system
the percent methane (CH4) content with an integral temperature sensor design, including the
of the biogas. uses sound velocity to calculate the instrumentation, is required to meet
methane fraction of the biogas. In the proper hazardous area
Are thermal mass or thermal addition, pressure can be assumed as classifications. In addition, the
dispersion flowmeters a good constant or, if variable, the transit digester vessel is considered a
solution for measuring biogas flow time flowmeter can take an external confined space (oxygen-free), so
from anaerobic digesters? input from a pressure transmitter. extreme caution and following OSHA
This calculation uses a proven regulations is critical when
No. Historically, customers will use relationship between sound velocity, performing maintenance in and
either a thermal dispersion (thermal temperature, and a methane/carbon around the vessel.
mass) type flowmeter or an orifice dioxide gas mixture. All trace gas
plate/differential pressure to monitor components are ignored except water
flow. Biogas presents many severe vapor, which is compensated for as
application challenges, such as low well.
flow, varying temperatures, and wet/
dirty gas. Also, how do you calibrate
the unit accurately for mixed and
changing gas compositions (CH4 +
CO2 + trace gases)? However, once
the gas has been dried and cleaned,
thermal mass technology can be
used effectively.