Data Sheet: Electrical Data: Connection Details

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 2000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X4X20X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X4X20X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E
Version of external connection L1,L2,L3,N,PE CT circuit color YELLOW E

Auxiliary power circuit color RED, BLACK


Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 4200 Language English
Plant depth mm 600 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 1 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA01/00BFA02 SH. No.: 1 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 2000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X4X20X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X4X20X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E
Version of external connection L1,L2,L3,N,PE CT circuit color YELLOW E

Auxiliary power circuit color RED, BLACK


Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 4200 Language English
Plant depth mm 600 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 2 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA03/00BFA04 SH. No.: 2 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply CABLE BOTTOM
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 630 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X2X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X2X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 3800 Language English
Plant depth mm 500 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 3 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA01/00BMA02 SH. No.: 3 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 3200 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 220 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X6X50X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X6X50X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 5600 Language English
Plant depth mm 600 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 4 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA11/00BFA12 SH. No.: 4 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 3200 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X6X50X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X6X50X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 5200 Language English
Plant depth mm 600 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 5 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA13/00BFA14 SH. No.: 5 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply CABLE BOTTOM
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 400 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X2X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X2X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 3800 Language English
Plant depth mm 500 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 6 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA11/00BMA12 SH. No.: 6 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 6300 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X6X50X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X6X50X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 10800 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 7 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA21/00BFA22 SH. No.: 7 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 6300 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X6X50X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X6X50X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 9600 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 8 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA23/00BFA24 SH. No.: 8 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply CABLE BOTTOM
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 630 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X2X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X2X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 3800 Language English
Plant depth mm 500 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 9 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA21/00BMA22 SH. No.: 9 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 10 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 01BFA41/01BFA42 SH. No.: 10 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 11 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 02BFA41/02BFA42 SH. No.: 11 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 125 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 6600 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 12 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA51/00BFA52 SH. No.: 12 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 5000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X40X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X40X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 13 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA41/00BFA42 SH. No.: 13 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 14 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 03BFA41/03BFA42 SH. No.: 14 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 15 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 04BFA41/04BFA42 SH. No.: 15 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 7400 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 16 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA53/00BFA54 SH. No.: 16 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 5000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X40X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X40X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 6200 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 17 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BFA43/00BFA44 SH. No.: 17 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 2000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X4X20X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X4X20X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 14200 Language English
Plant depth mm 600 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 18 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA41/00BMA42 SH. No.: 18 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 8600 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 19 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA31/00BMA32 SH. No.: 19 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 8200 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 20 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 10BFA61/10BFA62 SH. No.: 20 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply BUSDUCT TOP
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 4000 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 2X4X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 2X4X30X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X40X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 65 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2200 Color Black text in white background


Plant width mm 8200 Language English
Plant depth mm 800 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 21 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 10BFA63/10BFA64 SH. No.: 21 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

A
DATA SHEET A

ELECTRICAL DATA: CONNECTION DETAILS:


Rated Operating voltage V AC 400 Connection for supply CABLE BOTTOM
Rated frequency Hz 60 Connection for outgoing CABLE BOTTOM
B B

Rated current A 400 Connection in plant FRONT


System Configuration TNS, 3 PHASE, 4 WIRES
Rated control voltage V DC 110 (External voltage source) SERVICE LOCATION:
Rated voltage for heaters V AC 230 Installation Area INDOOR

C
Rated insulation voltage V 1000 Ambient temperature °C 40 C

Altitude m <1000

BUSBAR DETAILS: WIRING:


Main busbar cross section mm 1X2X30X10 Wires type PVC 600-1000 V, Cu

D Neutral Busbar mm 1X4X20X10 Control circuit cross section mm² 1.0 D

Ground Busbar mm 1X2X20X5 CT/VT circuit cross section mm² 4.0

Short time current (Icw) for 1sec kA 50 Auxiliary power circuit cross section mm² 2.5

Busbar Insulation HEAT-SHRINK AC circuit color RED, WHITE

Color code Red, Yellow, Blue,Black,Green/Yellow DC circuit color GRAY


E CT circuit color YELLOW E

Version of external connection L1,L2,L3,N,PE


Auxiliary power circuit color RED, BLACK
Labeling Bi-Directional Ferrule
ENCLOSURE DETAILS:
Type of Switchgear Sivacon S8 / Single front IDENTIFICATION LABEL:
F Installation Free Stand Material Gravoply F

Plant height mm 2000 Color Black text in white background


Plant width mm 3800 Language English
Plant depth mm 500 Fixation Rivets
Base height mm NA
G Notes: G
Internal separation Form 4b
Degree of protection IP 41
Canopy YES
Ventilation YES
Gland plate YES
H H
Color of enclosure parts RAL 7035
Color of Canopy RAL 7035
Door locks Door lock 3mm double bit
Transport unit YES

I I

REPLACEMENT OF TECHNOLOGIES AN ENDED LIFETIMEASSETS OF APP. BY: MUFID


CLIENT: Saudi Services for Electro Mechanic Works Co PROJECT:
AL JUBAIL DESALINATIONPLANT, PHASE 2 - SWCC
VER BY: NEGM
P.O. No.: JBDS-2/330/23 DTD 21-03-2023 PRODUCT: Switch Boards
J CHK BY: ABUZER J
OFFER No.: SQ-00008874-YZ PRODUCT TYPE: FG-PS-LV-SWGR-IEC

Mohamed.Negm
REC PID: 111573 ITEM ID:
DWG No.: 230147
00A 10/04/2023 ISSUED FOR APPROVAL Abuzer TITLE: TECHNICAL SPECIFICATION ITEM No.: 22 T +966 13 8121266

Last editor:
F +966 13 8121295
REV DATE MODIFICATION/REMARKS PRE. BY NMR No.: 601 FORM NO.: - TAG No.: 00BMA61/00BMA62 SH. No.: 22 OF 22
Abuzer

E-mail-info@rawabielectric.com
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
The drawing and the information contained herein are the sole property of Rawabi Electric. The contents there of must not be imported by a third party not be used for any unauthorized purpose without the written permission of Rawabi Electric.

You might also like