Foundation F9

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Page 1 of 158

Isolated Footing Design (IS 456-2000)


Footing No. Group ID Foundation Geometry
- - Length Width Thickness
805 F9 3.25m 3.25m 0.60m
815 F9 3.25m 3.25m 0.60m
841 F9 3.25m 3.25m 0.60m
842 F9 3.25m 3.25m 0.60m
843 F9 3.25m 3.25m 0.60m
844 F9 3.25m 3.25m 0.60m
845 F9 3.25m 3.25m 0.60m
846 F9 3.25m 3.25m 0.60m
847 F9 3.25m 3.25m 0.60m
848 F9 3.25m 3.25m 0.60m
853 F9 3.25m 3.25m 0.60m
857 F9 3.25m 3.25m 0.60m
858 F9 3.25m 3.25m 0.60m
859 F9 3.25m 3.25m 0.60m
860 F9 3.25m 3.25m 0.60m
861 F9 3.25m 3.25m 0.60m
862 F9 3.25m 3.25m 0.60m
869 F9 3.25m 3.25m 0.60m
874 F9 3.25m 3.25m 0.60m
878 F9 3.25m 3.25m 0.60m
879 F9 3.25m 3.25m 0.60m
880 F9 3.25m 3.25m 0.60m
881 F9 3.25m 3.25m 0.60m
882 F9 3.25m 3.25m 0.60m
883 F9 3.25m 3.25m 0.60m
884 F9 3.25m 3.25m 0.60m
885 F9 3.25m 3.25m 0.60m

Footing No. Footing Reinforcement Pedestal Reinforcement


- Bottom Reinforcement(Mz) Bottom Reinforcement(Mx) Top Reinforcement(Mz) Top Reinforcement(Mx) Main Steel Trans Steel
805 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
815 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
841 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
842 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
843 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
844 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
845 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
846 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
847 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
848 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
853 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
857 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
858 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
859 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
860 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
861 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
862 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
869 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
874 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
878 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
879 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
880 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
881 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
882 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
883 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 2 of 158

884 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm
885 Ø12 @ 150 mm c/c Ø12 @ 150 mm c/c Ø10 @ 175 mm c/c Ø10 @ 175 mm c/c 10 – Ø25 Ø8 @ 175
mm

Isolated Footing 815

2.5 m 3.1 m

2m

Elevation 0.6 m

X 1.625m

1.4 m
3.25m

0.75 m
1.625m

3.25m

Plan

Input Values

Footing Geomtery

Calculate Dimension with user


Design Type : specified minimums as
starting value
Minimum Footing Length - X(Fl) : 3000.00 mm
Minimum Footing Width - Z (Fw) : 3000.00 mm
Minimum Footing Thickness(Ft) : 600.00 mm
Eccentricity along X (Oxd) : 0.00 mm
Eccentricity along Z (Ozd) : 0.00 mm

Column Dimensions

Column Shape : Rectangular


Column Length - X (Pl) : 0.55 m
Column Width - Z (Pw) : 0.35 m

Pedestal

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 3 of 158

Include Pedestal : Yes


Pedestal Shape : Rectangular
Pedestal Height (Ph) : 2.50 m
Pedestal Length - X (Pl) : 1.40 m
Pedestal Width - Z (Pw) : 0.75 m

Design Parameters

Concrete and Rebar Properties

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 4 of 158

Unit Weight of Concrete : 23.60 kN/m3


Strength of Concrete : 25.00 N/mm2
Yield Strength of Steel : 500.00 N/mm2
Minimum Bar Size : Ø10
Maximum Bar Size : Ø12
Pedestal Minimum Bar Size : Ø6
Pedestal Maximum Bar Size : Ø32
Minimum Bar Spacing : 150.00 mm
Maximum Bar Spacing : 300.00 mm
Pedestal Clear Cover (P, CL) : 50.00 mm
Footing Clear Cover (F, CL) : 70.00 mm

Soil Properties

Soil Type : Cohesive Soil


Unit Weight : 17.60 kN/m3
Soil Bearing Capacity : 220.00 kPa

Multiplying factor for soil bearing


: 2.00
capacity for ultimate loads

Soil Bearing Capacity Type : Gross Bearing Capacity


Soil Surcharge : 0.00 kN/m2
Height of Soil above Footing : 2000.00 mm
Type of Depth : Fixed Top
Cohesion : 0.00 kN/m2

Minimum Percentage of Slab area in


: 0.00
Contact for Service Loads

Minimum Percentage of Slab area in


: 0.00
Contact for Ultimate Loads

Sliding and Overturning

Coefficient of Friction : 0.50


Factor of Safety Against Sliding : 1.50
Factor of Safety Against Overturning : 1.50

Global Settings

Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)

Design Calculations

Load Combinations

Load Combination/s- Service Stress Level


Load Soil Self
Load Combination
Load Combination Title Combination Bearing Weight
Number
Factor (a) Factor (b) Factor (c)
a - Value specified in the Load Safety Factor table
b - Value specified in the Pile/Soil Bearing Capacity Factors table
c - Value specified in the Apply Self Weight and Dead Weight Factor table
1 EQX+ 1.00 1.00 1.00
2 EQX- 1.00 1.00 1.00
3 EQZ+ 1.00 1.00 1.00
4 EQZ- 1.00 1.00 1.00
5 DL 1.00 1.00 1.00
6 LL 1.00 1.00 1.00
7 W.L +0 I.P=0.2 1.00 1.00 1.00
9 W.L +90 I.P=0.2 1.00 1.00 1.00
10 101. 1.0 DL+1.0LL 1.00 1.00 1.00

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 5 of 158

Load Combination/s- Service Stress Level


Load Soil Self
Load Combination
Load Combination Title Combination Bearing Weight
Number
Factor (a) Factor (b) Factor (c)
a - Value specified in the Load Safety Factor table
b - Value specified in the Pile/Soil Bearing Capacity Factors table
c - Value specified in the Apply Self Weight and Dead Weight Factor table
11 102. 1.0 DL+0.8 LL + 0.8 EQX+ 1.00 1.00 1.00
12 103. 1.0 DL+0.8 LL + 0.8 EQX- 1.00 1.00 1.00
13 104. 1.0 DL+0.8 LL + 0.8 EQZ+ 1.00 1.00 1.00
14 105. 1.0 DL+0.8 LL + 0.8 EQZ- 1.00 1.00 1.00
15 106. 1.0 DL+0.8 LL + 0.8 WL+0 1.00 1.00 1.00
16 107. 1.0 DL+0.8 LL + 0.8 WL+90 1.00 1.00 1.00
17 108. 1.0 DL+1.0 EQX+ 1.00 1.00 1.00
18 109. 1.0 DL+1.0 EQX- 1.00 1.00 1.00
19 110. 1.0 DL+1.0 EQZ+ 1.00 1.00 1.00
20 111. 1.0 DL+1.0 EQZ- 1.00 1.00 1.00
21 112. 1.0 DL+1.0 WL+0 1.00 1.00 1.00
22 112. 1.0 DL+1.0 WL+90 1.00 1.00 1.00
Load Combination/s- Strength Level
Load Soil Self
Load Combination
Load Combination Title Combination Bearing Weight
Number
Factor (a) Factor (b) Factor (c)
a - Value specified in the Load Safety Factor table
b - Value specified in the Pile/Soil Bearing Capacity Factors table
c - Value specified in the Apply Self Weight and Dead Weight Factor table
1 EQX+ 1.00 1.00 1.00
2 EQX- 1.00 1.00 1.00
3 EQZ+ 1.00 1.00 1.00
4 EQZ- 1.00 1.00 1.00
5 DL 1.00 1.00 1.00
6 LL 1.00 1.00 1.00
7 W.L +0 I.P=0.2 1.00 1.00 1.00
9 W.L +90 I.P=0.2 1.00 1.00 1.00
10 101. 1.0 DL+1.0LL 1.00 1.00 1.00
11 102. 1.0 DL+0.8 LL + 0.8 EQX+ 1.00 1.00 1.00
12 103. 1.0 DL+0.8 LL + 0.8 EQX- 1.00 1.00 1.00
13 104. 1.0 DL+0.8 LL + 0.8 EQZ+ 1.00 1.00 1.00
14 105. 1.0 DL+0.8 LL + 0.8 EQZ- 1.00 1.00 1.00
15 106. 1.0 DL+0.8 LL + 0.8 WL+0 1.00 1.00 1.00
16 107. 1.0 DL+0.8 LL + 0.8 WL+90 1.00 1.00 1.00
17 108. 1.0 DL+1.0 EQX+ 1.00 1.00 1.00
18 109. 1.0 DL+1.0 EQX- 1.00 1.00 1.00
19 110. 1.0 DL+1.0 EQZ+ 1.00 1.00 1.00
20 111. 1.0 DL+1.0 EQZ- 1.00 1.00 1.00
21 112. 1.0 DL+1.0 WL+0 1.00 1.00 1.00
22 112. 1.0 DL+1.0 WL+90 1.00 1.00 1.00

Applied Loads on Top of Pedestal


Before consideration of self weight and load safety factor table

Moments are About the center of footing / pile cap (does not include moments caused by lateral loads)
For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical axis.

Applied Loads for Column - Service Stress Level


Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
1 0.17 -0.66 0.02 0.00 0.00
2 -0.17 0.66 -0.02 0.00 0.00
3 0.01 -1.32 2.46 0.00 0.00
4 -0.01 1.32 -2.46 0.00 0.00
5 6.65 -321.85 2.29 0.00 0.00
6 15.38 -662.04 4.92 0.00 0.00
7 0.29 -26.93 -19.29 0.00 0.00
9 -2.85 -41.45 9.91 0.00 0.00
10 22.03 -983.88 7.21 0.00 0.00
11 19.09 -852.00 6.24 0.00 0.00
12 18.82 -850.95 6.21 0.00 0.00
13 18.97 -852.53 8.19 0.00 0.00

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 6 of 158

Applied Loads for Column - Service Stress Level


Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
14 18.94 -850.42 4.25 0.00 0.00
15 19.18 -873.02 -9.21 0.00 0.00
16 16.68 -884.63 14.15 0.00 0.00
17 6.82 -322.51 2.31 0.00 0.00
18 6.48 -321.19 2.27 0.00 0.00
19 6.67 -323.16 4.75 0.00 0.00
20 6.64 -320.53 -0.17 0.00 0.00
21 6.94 -348.77 -17.00 0.00 0.00
22 3.80 -363.29 12.20 0.00 0.00

Applied Loads for Column - Strength Level


Fy
(kN)
Fx Fz Mx Mz
Load Case Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards
is positive
1 0.17 -0.66 0.02 0.00 0.00
2 -0.17 0.66 -0.02 0.00 0.00
3 0.01 -1.32 2.46 0.00 0.00
4 -0.01 1.32 -2.46 0.00 0.00
5 6.65 -321.85 2.29 0.00 0.00
6 15.38 -662.04 4.92 0.00 0.00
7 0.29 -26.93 -19.29 0.00 0.00
9 -2.85 -41.45 9.91 0.00 0.00
10 22.03 -983.88 7.21 0.00 0.00
11 19.09 -852.00 6.24 0.00 0.00
12 18.82 -850.95 6.21 0.00 0.00
13 18.97 -852.53 8.19 0.00 0.00
14 18.94 -850.42 4.25 0.00 0.00
15 19.18 -873.02 -9.21 0.00 0.00
16 16.68 -884.63 14.15 0.00 0.00
17 6.82 -322.51 2.31 0.00 0.00
18 6.48 -321.19 2.27 0.00 0.00
19 6.67 -323.16 4.75 0.00 0.00
20 6.64 -320.53 -0.17 0.00 0.00
21 6.94 -348.77 -17.00 0.00 0.00
22 3.80 -363.29 12.20 0.00 0.00

Footing Size

Initial Length (Lo) = 3.00 m


Initial Width (Wo) = 3.00 m

Area from initial length and width, Ao = = 9.00 m2

Min. area required from bearing pressure, Amin = = 7.33 m2

Note: Amin is an initial estimation.


P = Vertical load from column + selfweight of footing + weight of soil.
qmax = Respective Factored Bearing Capacity.

Final Footing Size

Length (L2) = 3.25 m Governing Load Case : #1

Width (W2) = 3.25 m Governing Load Case : #1

Depth (D2) = 0.60 m

Area (A2) = 10.56 m2

Depth is governed by Ultimate Load Case

(Service check is performed with footing thickness requirements from concrete check)

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 7 of 158

Final Pedestal Height = 2.50 m

Final Soil Height = 2.00 m

Weight of footing + pedestal = 235.41 kN


Weight of the soil above the footing (dry) = 394.24 kN
Uplift force due to buoyancy = 132.15 kN
Effect due to adhesion = 0.00 kN

Pressures at 4 Corners

Pressure at Pressure at Pressure at Area of


Pressure at
top right bottom right bottom left footing in
Load Case top left corner
corner corner corner uplift (Au)
(kN/m2)
(kN/m2) (kN/m2) (kN/m2) (m2)

10 119.0332 138.1483 144.4008 125.2858 0.00

10 119.0332 138.1483 144.4008 125.2858 0.00

10 119.0332 138.1483 144.4008 125.2858 0.00

10 119.0332 138.1483 144.4008 125.2858 0.00

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the
pressure will be redistributed to remaining corners.

Summary of adjusted Pressures at Four Corners

Pressure at Pressure at
Pressure at Pressure at
bottom right bottom left
Load Case top left corner top right corner
corner corner
(kN/m2) (kN/m2)
(kN/m2) (kN/m2)

10 119.0332 138.1483 144.4008 125.2858

10 119.0332 138.1483 144.4008 125.2858

10 119.0332 138.1483 144.4008 125.2858

10 119.0332 138.1483 144.4008 125.2858


Details of Out-of-Contact Area
(If Any)
Governing load case = N/A
Plan area of footing = 10.562 sq.m
Area not in contact with soil = = 0.00 sq.m
% of total area not in contact = 0.00%

Stability Check

OTM

Sliding Force 2.5 m 3.1 m


2m

Frictional Force 0.6 m

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 8 of 158

Factor of safety against


- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.

1 1464.83 N/A 1457.58 1.50 N/A 1653.84 1.50

2 1460.95 N/A 1453.72 1.50 N/A 1649.46 1.50

3 N/A 101.37 101.36 1.50 114.45 N/A 1.50

4 N/A 100.83 100.83 1.50 113.84 N/A 1.50

5 61.58 178.96 58.23 1.50 202.05 69.52 1.50

6 37.70 117.91 35.91 1.50 133.12 42.57 1.50

7 915.04 13.60 13.59 1.50 15.35 1033.11 1.50

9 94.62 27.19 26.13 1.50 30.70 106.83 1.50

10 33.62 102.78 31.95 1.50 116.04 37.96 1.50

11 35.34 108.19 33.60 1.50 122.15 39.90 1.50

12 35.83 108.58 34.02 1.50 122.59 40.45 1.50

13 35.59 82.41 32.67 1.50 93.04 40.18 1.50

14 35.58 158.41 34.71 1.50 178.85 40.17 1.50

15 35.72 74.44 32.20 1.50 84.05 40.33 1.50

16 41.44 48.84 31.60 1.50 55.14 46.79 1.50

17 60.09 177.78 56.93 1.50 200.72 67.85 1.50

18 63.14 180.15 59.59 1.50 203.39 71.29 1.50

19 61.54 86.39 50.12 1.50 97.54 69.48 1.50

20 61.62 2388.39 61.60 1.50 2696.57 69.57 1.50

21 60.98 24.90 23.05 1.50 28.11 68.84 1.50

22 113.12 35.28 33.68 1.50 39.83 127.71 1.50

Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding X Direction
Critical Load Case for Sliding along X-Direction : 10
Governing Disturbing Force : 22.03 kN
Governing Restoring Force : 740.69 kN
Minimum Sliding Ratio for the Critical Load Case : 33.62
Critical Load Case for Overturning About X-Direction : 7
Governing Overturning Moment : -59.78 kNm
Governing Resisting Moment : 917.73 kNm
Minimum Overturning Ratio for the Critical Load Case : 15.35

Critical Load Case And The Governing Factor Of Safety For Overturning and Sliding Z Direction
Critical Load Case for Sliding along Z-Direction : 7
Governing Disturbing Force : -19.29 kN
Governing Restoring Force : 262.21 kN
Minimum Sliding Ratio for the Critical Load Case : 13.60
Critical Load Case for Overturning About Z-Direction : 10
Governing Overturning Moment : -68.30 kNm
Governing Resisting Moment : : 2592.38 kNm
Minimum Overturning Ratio for the Critical Load Case : 37.96

Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant Direction : : 7
Governing Disturbing Force : 19.29 kN
Governing Restoring Force : 262.21 kN
Minimum Sliding Ratio for the Critical Load Case : 13.59

Compression Development Length Check


Development length calculation skipped as column reinforcement is not specified in input (Column Dimension Task Pane)

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 9 of 158

Top Reinforcement Design Requirement


Top Reinforcement needs to be provided because of resultant negative pressure coming from net pressure calculations
for bending.

Ultimate Pressures
The base pressures reported in this table do not include the effect of buoyancy. However, the area of footing in contact includes the effect of
buoyancy (if any).

Area of
Load Case / Pressure at Pressure at Pressure at Pressure at
footing in
Load top left top right bottom right bottom left
Contact with
Combination corner corner corner corner
soil (Au)
ID (kN/m2) (kN/m2) (kN/m2) (kN/m2)
(m2)

1 51.3727 51.5203 51.5350 51.3875 12.25

2 51.4273 51.2797 51.2650 51.4125 12.25

3 50.4337 50.4467 52.5815 52.5685 12.25

4 52.3663 52.3533 50.2185 50.2315 12.25

5 73.7939 79.5662 81.5524 75.7801 12.25

6 96.6393 109.9821 114.2484 100.9057 12.25

7 61.8404 62.0891 45.3561 45.1075 12.25

9 51.7197 49.2486 57.8469 60.3179 12.25

10 119.0332 138.1483 144.4008 125.2858 12.25

11 109.9635 126.5280 131.9391 115.3746 12.25

12 110.0072 126.3356 131.7232 115.3947 12.25

13 109.2123 125.6692 132.7763 116.3195 12.25

14 110.7584 127.1945 130.8860 114.4499 12.25

15 118.3377 134.9831 126.9960 110.3507 12.25

16 110.2411 124.7107 136.9886 122.5190 12.25

17 73.7666 79.6864 81.6874 75.7676 12.25

18 73.8212 79.4459 81.4174 75.7927 12.25

19 72.8276 78.6129 82.7339 76.9486 12.25

20 74.7602 80.5195 80.3709 74.6116 12.25

21 84.2344 90.2553 75.5085 69.4876 12.25

22 74.1136 77.4148 87.9993 84.6981 12.25

Minimum Required Contact Area for Ultimate Loads : 0.00 m2

Actual Area in Contact for all ultimate load cases exceeds the minimum required. Hence Safe

Gross Bearing Capacity for Ultimate Loads : 440.00 kN/m2

Maximum Corner Pressure from all ultimate load cases is less than the allowable. Hence Safe

Moment Calculation

Check Trial Depth against moment (About Z Axis)

Critical Load Case = #10


Effective Depth = = 0.51 m
Governing moment (Mu) = = 179.44 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.46

Limiting Factor2 (Rumax) = = 3318.15 kN/m2


Limit Moment Of Resistance
= = 3044.36 kNm
(Mumax)
Mu <= Mumax hence, safe

Check Trial Depth against moment (About X Axis)

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 10 of
158

Critical Load Case = #10


Effective Depth = = 0.51 m

Governing moment (Mu) = = 290.07 kNm

As Per IS 456 2000 ANNEX G G-1.1C

Limiting Factor1 (Kumax) = = 0.46

Limiting Factor2 (Rumax) = = 3318.15 kN/m2


Limit Moment Of Resistance
= = 3044.36 kNm
(Mumax)
Mu <= Mumax hence, safe

One-Way Shear Along X

(Shear Plane Parallel to Global X Axis)

X 1.625m

Z 0.865 m
1.75 m

0.865 m

Plan

Critical Load Case = # 10


Distance of critical section from top left corner along Z,
= 0.86 m
DZ
Shear Force(S) = 268.25 kN
Shear Stress(Tv) = 149.69 kN/m2
Percentage Of Steel(Pt) = 0.1515

As Per IS 456 2000 Clause 40 Table 19


Shear Strength Of Concrete(Tc) = 292.24 kN/m2
Shear Enhancement Factor (if considered) is applied to (Tc), as per IS456 -2000 Clause No 40 5.1 and Fig 24
Tv< Tc hence, safe

One-Way Shear Along Z

(Shear Plane Parallel to Global Z Axis)

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 11 of 158

X 1.625m

0.54 m 0.54 m

1.625m
Plan

Critical Load Case = # 10


Distance of critical section from top left corner along X,
= 0.54 m
DX
Shear Force(S) = 172.12 kN
Shear Stress(Tv) = 96.05 kN/m2
Percentage Of Steel(Pt) = 0.15
As Per IS 456 2000 Clause 40 Table 19
Shear Strength Of Concrete(Tc) = 292.24 kN/m2
Shear Enhancement Factor (if considered) is applied to (Tc), as per IS456 -2000 Clause No 40 5.1 and Fig 24
Tv< Tc hence, safe

Punching Shear Check

X 1.75 m

Z
0.26 m
1.75 m

Plan

Critical Load Case = #10


Shear Force(S) = 833.95 kN
Shear Stress(Tv) = 253.31 kN/m2
As Per IS 456 2000 Clause 31.6.3.1

Ks = = 1.00

Shear Strength(Tc) = =

1250.00 kN/m2Ks x Tc

= 1250.00 kN/m2

Tv<= Ks x Tc hence, safe

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 12 of 158

Reinforcement Calculation

Calculation of Maximum Bar Size

Along X Axis

Bar diameter corresponding to max bar size (db) = 12 mm


As Per IS 456 2000 Clause 26.2.1

Development Length(ld) = = 0.58 m

Allowable Length(ldb) = = 0.98 m

ldb >=ld hence, safe

Along Z Axis

Bar diameter corresponding to max bar size(db) = 12 mm


As Per IS 456 2000 Clause 26.2.1

Development Length(ld) = = 0.58 m

Allowable Length(ldb) = = 1.30 m

ldb >=ld hence, safe

Flexure About X-Axis

Design For Bottom Reinforcement Parallel to Z Axis

24 - ϕ12

For moment About X Axis (Mx)


As Per IS 456 2000 Clause 26.5.2.1
Critical Load Case = #10
Minimum Area of Steel (Astmin) = 2520 mm2
Calculated Area of Steel (Ast) = 2520 mm2
Provided Area of Steel (Ast,Provided) = 2714 mm2
Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12


Minimum spacing allowed (Smin) = 150.00 mm
Selected spacing (S) = 150.26 mm
Smin<= S <= Smax and selected bar size < selected maximum bar size. The reinforcement is accepted.

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 13 of 158

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 150mm o.c.

Flexure About Z-Axis

Design For Bottom Reinforcement Parallel to X Axis

24 - ϕ12

For moment About Z Axis (Mz)


As Per IS 456 2000 Clause 26.5.2.1
Critical Load Case = #10
Minimum Area of Steel (Astmin) = 2520 mm2
Calculated Area of Steel (Ast) = 2520 mm2
Provided Area of Steel (Ast,Provided) = 2714 mm2
Astmin<= Ast,Provided Steel area is accepted

Selected bar Size (db) = Ø12


Minimum spacing allowed (Smin) = 150.00 mm
Selected spacing (S) = 150.26 mm
Smin<= S <= Smax and selected bar size < selected maximum bar size. The reinforcement is accepted.

Based on spacing reinforcement increment; provided reinforcement is

Ø12 @ 150mm o.c.

Pedestal Design
Pedestal at Support No. Axial Capacity Ratio Flexural Capacity Ratio % of Main Steel Main Reinforcement Links
815 0.09 0.07 0.47 12-T16 + 22-T12 T8 @ 175mm

Longitudinal Reinforcement Details

Area of Longitudinal Bars = 4900.92 sq.mm


Number of Bars and Bar Dia = 12-T16 +
22-T12
Longitudinal Steel Percentage = 0.47
Flexure - Governing Load Case Details
Governing Load Case Number = 10
Critical Location = Bottom

Shear - Governing Load Case Details


Critical Load Case for Shear Along X = 7

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 14 of 158

Critical Load Case for Shear Along Z = 9

Transverse Stirrups Details

Rebar Links = T8 @ 175 mm


No. of Legs in X direction = 8
No. of Legs in Z direction = 12

Capacity Ratios

Flexural Capacity Ratio = 0.07


Axial Capacity Ratio = 0.09

Crack Width Calculation (for Mz)


Modulus of Elasticity of Concrete(Ec) = 25000000.00 kN/m2 Clause No. 6.2.3.1
Modulus of Elasticity of Steel(Es) = 200000000.00 kN/m2 Annexure F
Annexure G, Clause No. G-
Depth of Neutral Axis(X u) = 0.25 m
1.1.a
Effective MOI(Ieff) = 18746324062.68 mm4
Average Steel Strain at Considered Level(Ɛm) = 0.00 X 10-5
Distance from Nearest Tension Rod (acr) = 0.11 m
Crack Width (Wcr) = 0.00 mm Annexure F
From IS 456-2000 Clause No. 35.3.2
Section is uncracked.

Crack Width Calculation (for Mx)


Modulus of Elasticity of Concrete(Ec) = 25000000.00 kN/m2 Clause No. 6.2.3.1
Modulus of Elasticity of Steel(Es) = 200000000.00 kN/m2 Annexure F
Annexure G, Clause No. G-
Depth of Neutral Axis(X u) = 0.25 m
1.1.a
Effective MOI(Ieff) = 18746324062.68 mm4
Average Steel Strain at Considered Level(Ɛm) = 0.00 X 10-5
Distance from Nearest Tension Rod (acr) = 0.11 m
Crack Width (Wcr) = 0.00 mm Annexure F
From IS 456-2000 Clause No. 35.3.2
Section is uncracked.

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
Page 14 of 158

file:///D:/dinesh%20project/factory/final%20file/foundation/001/foundation/F9,P8/P8,F9/... 02-07-2023
X 1.625 m

Z
1.4 m 2.5 m 3.1 m

2m

3.25 m
0.75 m
1.625 m

3.25 m

0.6 m
Plan

1.625 m

Elevation
BOTTOM 24 - ϕ12

Dimensions (m) Reinforcement


TOP N/A

L B D AstX(T) AstZ(T) AstX(B) AstZ(B)


1.625 m

Foundation
3.25 m 3.25 m 0.6 m N/A 24 - ϕ12 24 - ϕ12

l b h Main Reinforcement Trans Reinforcement

TOP N/A Pedestal


1.4 m 0.75 m 2.5 m #10 - 25 #8 @ 175 mm
BOTTOM 24 - ϕ12

Plan