6.4 GCS
Fuel Relay NOTE:- On applicable modules, configure the Fuel Relay Output to CAN ECU Power.
5,8
Output
CAUTION!:- An external slave relay will be needed. Check the current consumption and
specify relay accordingly.
Connect directly to engine starter solenoid.
Start Relay
-
Output CAUTION!:- An external slave relay may be needed. Check the current consumption does
not exceed the DSE unit’s output specification.
RS485 - Use only screened 120Ω impedance cable approved specifically for use in
RS485 A 18
CANbus applications.
RS485 + Use only screened 120Ω impedance cable approved specifically for use in
RS485 B 21
CANbus applications.
19, 22 Link 19 and 22 together to enable Cummins ECU 120Ω termination resistor.
NOTE:- Newer variants of these engines may be fitted with the CM850 ECU (as fitted to the QSL11 engines). Contact Cummins for further
information.
NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with these
controllers (DSE53XX (RS485 version), DSE55XX (RS485 version), DSE73XX, DSE75XX and DSE8XXX).
23
Cummins and DSE Controllers
NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with either of
these controllers DSE73XX, DSE75XX and DSE8XXX.
NOTE:- The GCS uses a MOBUS RS485 protocol and consequently a DSE controller with MODBUS engine control must be used with either of
these controllers DSE53XX (RS485 version) and DSE55XX (RS485 version).
24