PHASE II OF REFINERY IN DOS

BOCAS (HDN, HDDI, HDTGO, REF)

ALARM SET POINT LIST Page 1 / 44


Doc. TITLE
U-52000 Rev. 3

Contract Doc. No. R2B-P2-204-02-P-LST-20002 Contract No. PTI-ID-O-003-3-2020


Contractor
Contractor Doc. No. SO6625-EK0L-SUM-P2520002 Job. No.
SO6625

ALARM SET POINT LIST


U-52000

BETWEEN

PTI-Infraestructura de Desarrollo, S.A. de C.V.

AND

Samsung Ingeniería Manzanillo, S.A. de C.V. /


Asociados Constructores DBNR, S.A. de C.V.

“COMPLEMENTARY ENGINEERING, PROCUREMENT, CONSTRUCTION AND SUPPORT DURING


TESTS AND STARTUP OF THE PLANTS: HYDRODESULPHURIZATION PLANT ULSD No. 1,
HYDRODESULPHURIZATION PLANT ULSD No. 2, GAS OIL HYDRODESULPHURIZATION PLANT,
NAPHTHA HYDRODESULPHURIZATION PLANT No. 1, NAPHTHA HYDRODESULPHURIZATION PLANT
No. 2 AND NAPHTHA REFORMING PLANT FOR THE REFINERY IN DOS BOCAS, PARAÍSO, TABASCO”
(PHASE II)

Contract No. PTI-ID-O-003-3-2020

3 15-Jun-2023 ISSUE FOR CONSTRUCTION JEH SBP KHL

2 28-Dec-2022 ISSUE FOR CONSTRUCTION JEH JHP MKP

1 09-Jun-2022 ISSUE FOR CONSTRUCTION JEH JHP MKP

0 15-Oct-2021 ISSUE FOR CONSTRUCTION JEH JHP MKP

A 03-May-2021 ISSUE FOR REVIEW SOC JHP MKP

Rev. Date Description Prepared by Reviewed by Approved by

This document, including any patented or patentable features, embodies confidential information of Samsung Ingeniería Manzanillo, S.A. de
C.V. and its use is conditioned upon the user’s agreement not to reproduce the document in whole or in part. Nor the material described thereon
nor to use the document for any purpose other than specifically permitted in writing by Samsung Ingeniería Manzanillo, S.A. de. C.V.
PHASE II OF REFINERY IN DOS
BOCAS (HDN, HDDI, HDTGO, REF)

ALARM SET POINT LIST Page 2 / 44


Doc. TITLE
U-52000 Rev. 3

Contract Doc. No. R2B-P2-204-02-P-LST-20002 Contract No. PTI-ID-O-003-3-2020


Contractor
Contractor Doc. No. SO6625-EK0L-SUM-P2520002 Job. No.
SO6625

REVISION HISTORY
Rev DATE DESCRIPTION

A 03-May-2021 Initial Issue for Review

0 15-Oct-2021 Issue for Construction

1 09-Jun-2022 Issue for Construction

2 28-Dec-2022 Issue for Construction

3 15-Jun-2023 Issue for Construction

* Notes:

This page records all revisions on the procedures


PHASE II OF REFINERY IN DOS
BOCAS (HDN, HDDI, HDTGO, REF)

ALARM SET POINT LIST Page 3 / 44


Doc. TITLE
U-52000 Rev. 3

Contract Doc. No. R2B-P2-204-02-P-LST-20002 Contract No. PTI-ID-O-003-3-2020


Contractor
Contractor Doc. No. SO6625-EK0L-SUM-P2520002 Job. No.
SO6625

LEGEND

SYSTEM
SCD Distributed Control System
ESD Emergency Shutdown System
SFG Fire and Gas System
PLC Programmable Logic Controller
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

AT-52101 AI-52101 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER O2 SCD % v/v 10 0 6 1.5


AT-52102 AI-52102 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER CO SCD mg/Nm3 100 0 80
AT-52103A AI-52103A R2B-P2-204-02-A-DTI-20056 BA52002A FRAC REBOILER SCD mg/Nm3 100 0 40
AT-52103B AI-52103B R2B-P2-204-02-A-DTI-20065 BA52002B FRAC REBOILER SCD mg/Nm3 100 0 40
AT-52109A AI-52109A R2B-P2-204-02-A-DTI-20056 BA52002A FLU TO ATM SCD % v/v 10 0 6 1.5
AT-52109B AI-52109B R2B-P2-204-02-A-DTI-20065 BA52002B FLU TO ATM SCD % v/v 10 0 6 1.5
AT-52790 AI-52790 R2B-P2-204-02-A-DTI-20209A AIR DRYER OUTLET SCD °C 20 -110 -40
FT-52117 FFIC-52117 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 SCD Sm³/h 19000 0 15895.93 5868.13
FT-52118 FFIC-52118 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 SCD Sm³/h 19000 0 15895.93 5868.13
FT-52119 FFIC-52119 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 SCD Sm³/h 19000 0 15895.93 5868.13
FT-52120 FFIC-52120 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 SCD Sm³/h 19000 0 15895.93 5868.13
FT-52165A FFIC-52165A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52165B FFIC-52165B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52166A FFIC-52166A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52166B FFIC-52166B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52167A FFIC-52167A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52167B FFIC-52167B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52168A FFIC-52168A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52168B FFIC-52168B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52169A FFIC-52169A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52169B FFIC-52169B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52170A FFIC-52170A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52170B FFIC-52170B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52171A FFIC-52171A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52171B FFIC-52171B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52172A FFIC-52172A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A SCD Sm³/h 150 0 70.79
FT-52172B FFIC-52172B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B SCD Sm³/h 150 0 70.79
FT-52108 FI-52108 R2B-P2-204-02-A-DTI-20001 FG TO HFL BRANCH HDR SCD Nm³/h 40 0 5.12
FT-52142 FI-52142 R2B-P2-204-02-A-DTI-20027A EC52007 H2 TO FA52004 SCD Sm^3/h 106900 0 80203.73
FT-52143 FI-52143 R2B-P2-204-02-A-DTI-20027 BC52001A H2 TO EA52003 SCD Sm³/h 48000 0 39545.1 14692
FT-52144 FI-52144 R2B-P2-204-02-A-DTI-20027A BC52001 H2 TO EA52003 SCD Sm³/h 95000 0 79090.2
FT-52145 FI-52145 R2B-P2-204-02-A-DTI-20027A GB52001 H2 TO EA52003 SCD Sm³/h 30000 0 24948 7740.5
FT-52146 FI-52146 R2B-P2-204-02-A-DTI-20027A BC52001 H2 TO EA52003 SCD Sm³/h 130000 0 106736.81 39121
FT-52148 FI-52148 R2B-P2-204-02-A-DTI-20030 BC52001B H2 TO EA52003 SCD Sm³/h 50000 0 39545.1 14692
FT-52149 FI-52149 R2B-P2-204-02-A-DTI-20033 BC52001C H2 TO EA52003 SCD Sm³/h 50000 0 39545.1 14692
FT-52186 FI-52186 R2B-P2-204-02-A-DTI-20021 FA52013 AMR TO AMR HEAD SCD m^3/h 320 0 269 111.41
FT-52701 FI-52701 R2B-P2-204-02-A-DTI-20301 FG TO FA52051 SCD Nm^3/h 16000 0 5550.02
FT-52704 FI-52704 R2B-P2-204-02-A-DTI-20007 FG TO HFL BRANCH HDR SCD Nm³/h 160 0 14.26
FT-52747 FI-52747 R2B-P2-204-02-A-DTI-20304 CWS TO CWS HEAD SCD Sm³/h 1400 0 460.2

Sheet 1 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

FT-52100 FIC-52100 R2B-P2-204-02-A-DTI-20012 ACL TO FA52016 SCD kg/h 50000 0 16696


FT-52103 FIC-52103 R2B-P2-204-02-A-DTI-20001 ACL TO FG52001 SCD kg/h 55000 0 14444
FT-52105 FIC-52105 R2B-P2-204-02-A-DTI-20001 GOLC TO FG52001 SCD kg/h 170000 0 63099
FT-52106 FIC-52106 R2B-P2-204-02-A-DTI-20001 GOLC TO FG52001 SCD kg/h 80000 0 27879
FT-52107 FIC-52107 R2B-P2-204-02-A-DTI-20001 DIA TO FG52001 SCD kg/h 350000 0 113717
FT-52110A FIC-52110A R2B-P2-204-02-A-DTI-20071A GA52008A WSH WTR TO EC52001 SCD m³/h 70 0 23.9
FT-52110B FIC-52110B R2B-P2-204-02-A-DTI-20071A GA52008B WSH WTR TO EC52001 SCD m³/h 70 0 23.9
FT-52113 FIC-52113 R2B-P2-204-02-A-DTI-20004 GA52001AB MXD DSL TO EA52002 SCD Sm^3/h 750 0 235.51
FT-52121 FIC-52121 R2B-P2-204-02-A-DTI-20007A GB52001 QCH H2 TO DC52001 SCD Sm³/h 85000 0 70471.89 26846.94
FT-52123 FIC-52123 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 SCD m^3/h 125 0 35.73
FT-52124 FIC-52124 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 SCD m^3/h 125 0 35.73
FT-52125 FIC-52125 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 SCD m^3/h 125 0 35.73
FT-52126 FIC-52126 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 SCD m^3/h 125 0 35.73
FT-52129 FIC-52129 R2B-P2-204-02-A-DTI-20008 GB52001 QCH H2 TO DC52002 SCD Sm³/h 90000 0 75229.86 28658.5
FT-52130 FIC-52130 R2B-P2-204-02-A-DTI-20008 GB52001 QCH H2 TO DC52002 SCD Sm³/h 75000 0 60596.84 23084.62
FT-52131 FIC-52131 R2B-P2-204-02-A-DTI-20007A GB52001 QCH H2 TO DC52001 SCD Sm³/h 120000 0 94800.41 36114.47
FT-52132 FIC-52132 R2B-P2-204-02-A-DTI-20008A GB52001 QCH H2 TO DC52002 SCD Sm³/h 70000 0 57095.69 21525.74
FT-52133 FIC-52133 R2B-P2-204-02-A-DTI-20071A GA52008AB WSH WTR TO EC52001 SCD m³/h 70 0 56.81 26.29
FT-52137 FIC-52137 R2B-P2-204-02-A-DTI-20020 GA52002 AML TO DA52001 SCD m^3/h 320 0 257.25 75.35
FT-52139 FIC-52139 R2B-P2-204-02-A-DTI-20047 GA52004 STAB DSL TO EA52006 SCD Sm^3/h 900 0 344.3
FT-52155 FIC-52155 R2B-P2-204-02-A-DTI-20036 FA52008 HOT DSL TO DS52001 SCD m^3/h 800 0 627.5 214.58
FT-52156 FIC-52156 R2B-P2-204-02-A-DTI-20037 FA52009 HOT DSLTO DS52001 SCD m^3/h 120 0 97.6 40.09
FT-52158 FIC-52158 R2B-P2-204-02-A-DTI-20045 MP BFW TO EA52008 SCD m^3/h 38 0 11.84
FT-52189 FIC-52189 R2B-P2-204-02-A-DTI-20038 BA52002 MP STM TO DS52001 SCD kg/h 11700 0 9640.79 4173.5
FT-52190 FIC-52190 R2B-P2-204-02-A-DTI-20036 WSH WTRTO EC52006 SCD m^3/h 8 0 6.35 2.5
LT-52001A1 LI-52001A1 R2B-P2-204-02-A-DTI-20004 GA52001A PUMP SEAL SCD % 100 0 80 56.59
LT-52001A2 LI-52001A2 R2B-P2-204-02-A-DTI-20004 GA52001A PUMP SEAL SCD % 100 0 80 56.59
LT-52001B1 LI-52001B1 R2B-P2-204-02-A-DTI-20004 GA52001B PUMP SEAL SCD % 100 0 80 56.59
LT-52001B2 LI-52001B2 R2B-P2-204-02-A-DTI-20004 GA52001B PUMP SEAL SCD % 100 0 80 56.59
LT-52002A1 LI-52002A1 R2B-P2-204-02-A-DTI-20023 GA52002A PUMP SEAL SCD % 100 0 79.97 51.16
LT-52002A2 LI-52002A2 R2B-P2-204-02-A-DTI-20023 GA52002A PUMP SEAL SCD % 100 0 79.97 51.16
LT-52002B1 LI-52002B1 R2B-P2-204-02-A-DTI-20023 GA52002B PUMP SEAL SCD % 100 0 79.97 51.16
LT-52002B2 LI-52002B2 R2B-P2-204-02-A-DTI-20023 GA52002B PUMP SEAL SCD % 100 0 79.97 51.16
LT-52003A LI-52003A R2B-P2-204-02-A-DTI-20053 GA52003A PUMP SEAL SCD % 100 0 79.96 46.26
LT-52003B LI-52003B R2B-P2-204-02-A-DTI-20053 GA52003B PUMP SEAL SCD % 100 0 79.96 46.26
LT-52004A1 LI-52004A1 R2B-P2-204-02-A-DTI-20047 GA52004A PUMP SEAL SCD % 100 0 79.96 46.18
LT-52004A2 LI-52004A2 R2B-P2-204-02-A-DTI-20047 GA52004A PUMP SEAL SCD % 100 0 79.96 46.18
LT-52004B1 LI-52004B1 R2B-P2-204-02-A-DTI-20047 GA52004B PUMP SEAL SCD % 100 0 79.96 46.18
LT-52004B2 LI-52004B2 R2B-P2-204-02-A-DTI-20047 GA52004B PUMP SEAL SCD % 100 0 79.96 46.18

Sheet 2 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

LT-52005A1 LI-52005A1 R2B-P2-204-02-A-DTI-20048 GA52005A PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005A2 LI-52005A2 R2B-P2-204-02-A-DTI-20048 GA52005A PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005B1 LI-52005B1 R2B-P2-204-02-A-DTI-20048 GA52005B PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005B2 LI-52005B2 R2B-P2-204-02-A-DTI-20048 GA52005B PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005C1 LI-52005C1 R2B-P2-204-02-A-DTI-20049 GA52005C PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005C2 LI-52005C2 R2B-P2-204-02-A-DTI-20049 GA52005C PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005D1 LI-52005D1 R2B-P2-204-02-A-DTI-20049 GA52005D PUMP SEAL SCD % 100 0 79.96 46.18
LT-52005D2 LI-52005D2 R2B-P2-204-02-A-DTI-20049 GA52005D PUMP SEAL SCD % 100 0 79.96 46.18
LT-52006A LI-52006A R2B-P2-204-02-A-DTI-20018A GA52006A PUMP SEAL SCD % 100 0 79.94 49.19
LT-52006B LI-52006B R2B-P2-204-02-A-DTI-20018A GA52006B PUMP SEAL SCD % 100 0 79.94 49.19
LT-52009A LI-52009A R2B-P2-204-02-A-DTI-20018 GA52009A PUMP SEAL SCD % 100 0 79.94 49.19
LT-52009B LI-52009B R2B-P2-204-02-A-DTI-20018 GA52009B PUMP SEAL SCD % 100 0 79.94 49.19
LT-52010A LI-52010A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL RESERVOIR SCD % 100 0 39
LT-52010B LI-52010B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL RESERVOIR SCD % 100 0 39
LT-52051A LI-52051A R2B-P2-204-02-A-DTI-20211 GA52051A PUMP SEAL SCD % 100 0 79.96 46.26
LT-52051B LI-52051B R2B-P2-204-02-A-DTI-20211 GA52051B PUMP SEAL SCD % 100 0 79.96 46.26
LT-52052A LI-52052A R2B-P2-204-02-A-DTI-20213 GA52052A PUMP SEAL SCD % 100 0 79.96 46.26
LT-52052B LI-52052B R2B-P2-204-02-A-DTI-20213 GA52052B PUMP SEAL SCD % 100 0 79.96 46.26
LT-52056A LI-52056A R2B-P2-204-02-A-DTI-20222 GA52056A PUMP SEAL SCD % 100 0 79.96 49.22
LT-52056B LI-52056B R2B-P2-204-02-A-DTI-20222 GA52056B PUMP SEAL SCD % 100 0 79.96 49.22
LT-52057A LI-52057A R2B-P2-204-02-A-DTI-20225 GA52057A PUMP SEAL SCD % 100 0 79.94 49.19
LT-52057B LI-52057B R2B-P2-204-02-A-DTI-20225 GA52057B PUMP SEAL SCD % 100 0 79.94 49.19
LT-52102 LI-52102 R2B-P2-204-02-A-DTI-20015 FA52002 HP HOT SEPARATOR SCD % 100 0 76.7 24.0
LT-52103 LI-52103 R2B-P2-204-02-A-DTI-20015 FA52002 HP HOT SEPARATOR SCD % 100 0 76.7 24.0
LT-52106 LI-52106 R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR SCD % 100 0 73.5 23.1
LT-52107 LI-52107 R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR SCD % 100 0 73.5 23.1
LT-52108 LI-52108 R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR SCD % 100 0 75.4 23.6
LT-52109 LI-52109 R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR SCD % 100 0 75.4 23.6
LT-52111 LI-52111 R2B-P2-204-02-A-DTI-20020 DA52001 SCRUBBER SCD % 100 0 72.6 22.7
LT-52112 LI-52112 R2B-P2-204-02-A-DTI-20020 DA52001 SCRUBBER SCD % 100 0 72.6 22.7
LT-52116 LI-52116 R2B-P2-204-02-A-DTI-20027 FA52005A HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52117 LI-52117 R2B-P2-204-02-A-DTI-20027 FA52005A HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52119 LI-52119 R2B-P2-204-02-A-DTI-20030 FA52006B HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52120 LI-52120 R2B-P2-204-02-A-DTI-20030 FA52006B HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52122 LI-52122 R2B-P2-204-02-A-DTI-20033 FA52006C HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52123 LI-52123 R2B-P2-204-02-A-DTI-20033 FA52006C HYDROGEN MAKEUP CMPR SCD % 100 0 56.5 13.0
LT-52124 LI-52124 R2B-P2-204-02-A-DTI-20034 FA52007 RECYCLE H2 CMPR SUCT DRM SCD % 100 0 65.8 20.6
LT-52125 LI-52125 R2B-P2-204-02-A-DTI-20034 FA52007 RECYCLE H2 CMPR SUCT DRM SCD % 100 0 65.8 20.6
LT-52295 LI-52295 R2B-P2-204-02-A-DTI-20209 FA52061 INSTRUMENT AIR RECEIVER SCD % 100 0 75.0 12.5

Sheet 3 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

LT-52296 LI-52296 R2B-P2-204-02-A-DTI-20244 FA52062 BREATHING AIR RECEIVER SCD % 100 0 75.0 12.5
LT-52450 LI-52450 R2B-P2-204-02-A-DTI-20709 BC-52001-FB04 EXPANSION TANK SCD % 100 0 80 20
LT-52540 LI-52540 R2B-P2-204-02-A-DTI-20058 SPE52001 LEVEL SCD % 100 0 76 17 14
LT-52545 LI-52545 R2B-P2-204-02-A-DTI-20059 SPE52002 LEVEL SCD % 100 0 76 17 14
LT-52650 LI-52650 R2B-P2-204-02-A-DTI-20060 SPE52003 LEVEL SCD % 100 0 76 17 14
LT-52655 LI-52655 R2B-P2-204-02-A-DTI-20061 SPE52004 LEVEL SCD % 100 0 76 17 14
LT-52660 LI-52660 R2B-P2-204-02-A-DTI-20062 SPE52005 LEVEL SCD % 100 0 76 17 14
LT-52665 LI-52665 R2B-P2-204-02-A-DTI-20063 SPE52006 LEVEL SCD % 100 0 76 17 14
LT-52701 LI-52701 R2B-P2-204-02-A-DTI-20201 FA52051 FUEL GAS KNOCKOUT DRUM SCD % 100 0 80.0 20
LT-52702 LI-52702 R2B-P2-204-02-A-DTI-20204 FG52051A COMMON HTR FG FILTER SCD % 100 0 71.2 10.2
LT-52704 LI-52704 R2B-P2-204-02-A-DTI-20204 FG52051B COMMON HTR FG FILTER SCD % 100 0 71.2 10.2
LT-52706 LI-52706 R2B-P2-204-02-A-DTI-20211 FA52052 LOW PRESS FLARE KO DRUM SCD % 100 0 78.8 12.1
LT-52707 LI-52707 R2B-P2-204-02-A-DTI-20213 FA52053 HP FLARE KO DRUM SCD % 100 0 80.0 11.4
LT-52712A LI-52712A R2B-P2-204-02-A-DTI-20222 FA52055 SLOPS DRUM SCD % 100 0 75.0 15.0
LT-52712B LI-52712B R2B-P2-204-02-A-DTI-20222 FA52055 SLOPS DRUM SCD % 100 0 75.0 15.0
LT-52714A LI-52714A R2B-P2-204-02-A-DTI-20225 FA52056 AMINE DRAIN DRUM SCD % 100 0 75.8 21.2
LT-52714B LI-52714B R2B-P2-204-02-A-DTI-20225 FA52056 AMINE DRAIN DRUM SCD % 100 0 75.8 21.2
LT-52716 LI-52716 R2B-P2-204-02-A-DTI-20237 FA52057LOW PRESS CONDENSATE DRUM SCD % 100 0 58.9 17.9
LT-52772 LI-52772 R2B-P2-204-02-A-DTI-20239 FA52058 BLOWDOWN DRUM SCD % 100 0 64.7 11.8
LT-52781 LI-52781 R2B-P2-204-02-A-DTI-20209 FA52063 INSTRUMENT AIR KO DRUM SCD % 100 0 75.0 12.5
LT-52100 LIC-52100 R2B-P2-204-02-A-DTI-20003 FA52001 FEED DRUM SCD % 100 0 76.4 23.9
LT-52101 LIC-52101 R2B-P2-204-02-A-DTI-20003 FA52001 FEED DRUM SCD % 100 0 69.6 21.8
LT-52104 LIC-52104 R2B-P2-204-02-A-DTI-20018 FA52014 SOUR WATER DRUM SCD % 100 0 75.2 23.5
LT-52105 LIC-52105 R2B-P2-204-02-A-DTI-20018 FA52014 SOUR WATER DRUM SCD % 100 0 82.1 14.2
LT-52110 LIC-52110 R2B-P2-204-02-A-DTI-20021 FA52013 RICH AMINE DRUM SCD % 100 0 76.0 23.8
LT-52113 LIC-52113 R2B-P2-204-02-A-DTI-20022 FA52015 LEAN AMINE DRUM SCD % 100 0 76.0 23.8
LT-52114 LIC-52114 R2B-P2-204-02-A-DTI-20024 FA52004 H2 MAKEUP CMPR SUCT DRUM SCD % 100 0 50.0 15.6
LT-52115 LIC-52115 R2B-P2-204-02-A-DTI-20026 FA52005A HYDROGEN MAKEUP CMPR SCD % 100 0 57.1 14.3
LT-52118 LIC-52118 R2B-P2-204-02-A-DTI-20028 FA52005B HYDROGEN MAKEUP CMPR SCD % 100 0 57.1 14.3
LT-52121 LIC-52121 R2B-P2-204-02-A-DTI-20031 FA52005C HYDROGEN MAKEUP CMPR SCD % 100 0 57.1 14.3
LT-52126 LIC-52126 R2B-P2-204-02-A-DTI-20036 FA52008 1ST DIESEL SEPARATOR SCD % 100 0 77.1 24.1
LT-52127 LIC-52127 R2B-P2-204-02-A-DTI-20037 FA52009 2ND DIESEL SEPARATOR SCD % 100 0 73.2 22.9
LT-52128 LIC-52128 R2B-P2-204-02-A-DTI-20037 FA52009 2ND DIESEL SEPARATOR SCD % 100 0 74.0 23.1
LT-52130 LIC-52130 R2B-P2-204-02-A-DTI-20046 DF52001 FRACTIONATOR SCD % 100 0 75.9 23.7
LT-52131 LIC-52131 R2B-P2-204-02-A-DTI-20052 FA52010 FRACTIONATOR REFLUX DRUM SCD % 100 0 74.0 23.1
LT-52132 LIC-52132 R2B-P2-204-02-A-DTI-20052 FA52010 FRACTIONATOR REFLUX DRUM SCD % 100 0 73.2 22.9
LT-52136 LIC-52136 R2B-P2-204-02-A-DTI-20071 FA52012WASH WATER DRUM SCD % 100 0 74.6 23.4
LT-52137 LIC-52137 R2B-P2-204-02-A-DTI-20038 DS52001 STRIPPER SCD % 100 0 74.5 21.8
LT-52138 LIC-52138 R2B-P2-204-02-A-DTI-20041 FA52011 STRIPPER REFLUX DRUM SCD % 100 0 73.4 23.0

Sheet 4 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

LT-52139 LIC-52139 R2B-P2-204-02-A-DTI-20041 FA52011 STRIPPER REFLUX DRUM SCD % 100 0 75.0 23.6
LT-52140 LIC-52140 R2B-P2-204-02-A-DTI-20012 FA52016 COLD FEED COALESCER SCD % 100 0 68.8 18.8
LT-52715 LIC-52715 R2B-P2-204-02-A-DTI-20237 FA52057 LOW PRESS COND DRUM SCD % 100 0 58.9 17.9
LT-52771 LIC-52771 R2B-P2-204-02-A-DTI-20239 FA52058 BLOWDOWN DRUM SCD % 100 0 64.7 11.8
LT-52784 LIC-52784 R2B-P2-204-02-A-DTI-20072 SPE52021 RECYCLE HYDROGEN CMPR SCD % 100 0 58.0 31.0
PDT-52010A PDI-52010A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL FILTER SCD kg/cm2 2 0 1
PDT-52010B PDI-52010B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL FILTER SCD kg/cm2 2 0 1
PDT-52195A PDI-52195A R2B-P2-204-02-A-DTI-20066 DP ACROSS BA52002A_BV01 SCD mmH2O 500 0 95
PDT-52195B PDI-52195B R2B-P2-204-02-A-DTI-20068 DP ACROSS BA52002B_BV01 SCD mmH2O 500 0 95
PDT-52196A PDI-52196A R2B-P2-204-02-A-DTI-20066 DP ACROSS BA52002A_BV02 SCD mmH2O 500 0 95
PDT-52196B PDI-52196B R2B-P2-204-02-A-DTI-20068 DP ACROSS BA52002B_BV02 SCD mmH2O 500 0 95
PDT-52460 PDI-52460 R2B-P2-204-02-A-DTI-20702 BC-52001A-FG01A/B LO FLTR SCD kg/cm2 3 0 1
PDT-52560 PDI-52560 R2B-P2-204-02-A-DTI-20712 BC-52001B-FG01A/B LO FLTR SCD kg/cm2 3 0 1
PDT-52660 PDI-52660 R2B-P2-204-02-A-DTI-20722 BC-52001C-FG01A/B LO FLTR SCD kg/cm2 3 0 1
PDT-52704 PDI-52704 R2B-P2-204-02-A-DTI-20204 FG52051B FG FILTER FOR HTR SCD kg/cm2 1 0 0.7
PDT-52705 PDI-52705 R2B-P2-204-02-A-DTI-20204 FG52051A COMMON HTR FG FILTER SCD kg/cm2 1 0 0.7
PDT-52790 PDI-52790 R2B-P2-204-02-A-DTI-20209A PRE FILTER SCD kg/cm2 0.5 0 0.2
PDT-52791 PDI-52791 R2B-P2-204-02-A-DTI-20209A AFTER FILTER SCD kg/cm2 0.5 0 0.2
PT-52001A1 PI-52001A1 R2B-P2-204-02-A-DTI-20004 GA52001A PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52001A2 PI-52001A2 R2B-P2-204-02-A-DTI-20004 GA52001A PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52001B1 PI-52001B1 R2B-P2-204-02-A-DTI-20004 GA52001B PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52001B2 PI-52001B2 R2B-P2-204-02-A-DTI-20004 GA52001B PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52002A1 PI-52002A1 R2B-P2-204-02-A-DTI-20023 GA52002A PUMP SEAL SCD kg/cm2g 10 0 4
PT-52002A2 PI-52002A2 R2B-P2-204-02-A-DTI-20023 GA52002A PUMP SEAL SCD kg/cm2g 10 0 4
PT-52002B1 PI-52002B1 R2B-P2-204-02-A-DTI-20023 GA52002B PUMP SEAL SCD kg/cm2g 10 0 4
PT-52002B2 PI-52002B2 R2B-P2-204-02-A-DTI-20023 GA52002B PUMP SEAL SCD kg/cm2g 10 0 4
PT-52003A PI-52003A R2B-P2-204-02-A-DTI-20053 GA52003A PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52003B PI-52003B R2B-P2-204-02-A-DTI-20053 GA52003B PUMP SEAL SCD kg/cm2g 2 0 1.2
PT-52004A1 PI-52004A1 R2B-P2-204-02-A-DTI-20047 GA52004A PUMP SEAL SCD kg/cm2g 2 0 1
PT-52004A2 PI-52004A2 R2B-P2-204-02-A-DTI-20047 GA52004A PUMP SEAL SCD kg/cm2g 2 0 1
PT-52004B1 PI-52004B1 R2B-P2-204-02-A-DTI-20047 GA52004B PUMP SEAL SCD kg/cm2g 2 0 1
PT-52004B2 PI-52004B2 R2B-P2-204-02-A-DTI-20047 GA52004B PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005A1 PI-52005A1 R2B-P2-204-02-A-DTI-20048 GA52005A PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005A2 PI-52005A2 R2B-P2-204-02-A-DTI-20048 GA52005A PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005B1 PI-52005B1 R2B-P2-204-02-A-DTI-20048 GA52005B PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005B2 PI-52005B2 R2B-P2-204-02-A-DTI-20048 GA52005B PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005C1 PI-52005C1 R2B-P2-204-02-A-DTI-20049 GA52005C PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005C2 PI-52005C2 R2B-P2-204-02-A-DTI-20049 GA52005C PUMP SEAL SCD kg/cm2g 2 0 1
PT-52005D1 PI-52005D1 R2B-P2-204-02-A-DTI-20049 GA52005D PUMP SEAL SCD kg/cm2g 2 0 1

Sheet 5 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52005D2 PI-52005D2 R2B-P2-204-02-A-DTI-20049 GA52005D PUMP SEAL SCD kg/cm2g 2 0 1


PT-52006A PI-52006A R2B-P2-204-02-A-DTI-20018A GA52006A PUMP SEAL SCD kg/cm2g 10 0 3
PT-52006B PI-52006B R2B-P2-204-02-A-DTI-20018A GA52006B PUMP SEAL SCD kg/cm2g 10 0 3
PT-52007A PI-52007A R2B-P2-204-02-A-DTI-20042 GA52007A PUMP SEAL SCD kg/cm2g 40 0 15.2
PT-52007B PI-52007B R2B-P2-204-02-A-DTI-20042 GA52007B PUMP SEAL SCD kg/cm2g 40 0 15.2
PT-52009A PI-52009A R2B-P2-204-02-A-DTI-20018 GA52009A PUMP SEAL SCD kg/cm2g 10 0 3
PT-52009B PI-52009B R2B-P2-204-02-A-DTI-20018 GA52009B PUMP SEAL SCD kg/cm2g 10 0 3
PT-52020A PI-52020A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL SUPPLY SCD kg/cm2g 3 0 1
PT-52020B PI-52020B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL SUPPLY SCD kg/cm2g 3 0 1
PT-52051A PI-52051A R2B-P2-204-02-A-DTI-20211 GA52051A PUMP SEAL SCD kg/cm2g 10 0 3
PT-52051B PI-52051B R2B-P2-204-02-A-DTI-20211 GA52051B PUMP SEAL SCD kg/cm2g 10 0 3
PT-52052A PI-52052A R2B-P2-204-02-A-DTI-20213 GA52052A PUMP SEAL SCD kg/cm2g 10 0 3
PT-52052B PI-52052B R2B-P2-204-02-A-DTI-20213 GA52052B PUMP SEAL SCD kg/cm2g 10 0 3
PT-52056A PI-52056A R2B-P2-204-02-A-DTI-20222 GA52056A PUMP SEAL SCD kg/cm2g 6 0 2
PT-52056B PI-52056B R2B-P2-204-02-A-DTI-20222 GA52056B PUMP SEAL SCD kg/cm2g 6 0 2
PT-52057A PI-52057A R2B-P2-204-02-A-DTI-20225 GA52057A PUMP SEAL SCD kg/cm2g 6 0 2
PT-52057B PI-52057B R2B-P2-204-02-A-DTI-20225 GA52057B PUMP SEAL SCD kg/cm2g 6 0 2
PT-52103 PI-52103 R2B-P2-204-02-A-DTI-20101 ACL TO FG52001 SCD kg/cm2g 18 0 10
PT-52105 PI-52105 R2B-P2-204-02-A-DTI-20101 GOLC TO FG52001 SCD kg/cm2g 18 0 10
PT-52106 PI-52106 R2B-P2-204-02-A-DTI-20101 GOL TO FG52001 SCD kg/cm2g 16 0 9
PT-52107 PI-52107 R2B-P2-204-02-A-DTI-20101 DIA TO FG52001 SCD kg/cm2g 12 0 8.5
PT-52109 PI-52109 R2B-P2-204-02-A-DTI-20001 FG52001 MXD DSL TO EA52001AB SCD kg/cm2g 7 0 4.5 2.5
PT-52111 PI-52111 R2B-P2-204-02-A-DTI-20002 EA52001B MXD DSL TO FA52001 SCD kg/cm2g 6 0 3.5 1.5
PT-52114 PI-52114 R2B-P2-204-02-A-DTI-20004 GA52001AB MXD DSL TO EA52002 SCD kg/cm2g 141 0 118.1 87.93
PT-52130 PI-52130 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER SCD mmH2O 50 330 0
PT-52131 PI-52131 R2B-P2-204-02-A-DTI-20010 FG TO BA52001 SCD kg/cm2g 10 0 5.2 3.8
PT-52146 PI-52146 R2B-P2-204-02-A-DTI-20025 EC52002A H2 TO FA52005A SCD kg/cm2g 60 0 36.54 33.06
PT-52151 PI-52151 R2B-P2-204-02-A-DTI-20027 EC52003A H2 TO FA52006A SCD kg/cm2g 100 0 61.425 55.575
PT-52152 PI-52152 R2B-P2-204-02-A-DTI-20028 EC52002B H2 TO FA52005B SCD kg/cm2g 60 0 36.54 33.06
PT-52153 PI-52153 R2B-P2-204-02-A-DTI-20030 EC52003B H2 TO FA52006B SCD kg/cm2g 100 0 61.425 55.575
PT-52154 PI-52154 R2B-P2-204-02-A-DTI-20031 EC52002C H2 TO FA52005C SCD kg/cm2g 60 0 36.54 33.06
PT-52155 PI-52155 R2B-P2-204-02-A-DTI-20033 EC52003C H2 TO FA52006C SCD kg/cm2g 100 0 61.425 55.575
PT-52160 PI-52160 R2B-P2-204-02-A-DTI-20001 BL MXD DSLTO FG52001 SCD kg/cm2g 9 0 5.7
PT-52166A PI-52166A R2B-P2-204-02-A-DTI-20045 MP BFW TO EA52008 SCD kg/cm2g 21 0 15.5
PT-52167 PI-52167 R2B-P2-204-02-A-DTI-20045 EA52007 MP STM TO BA52002A SCD kg/cm2g 21 0 15
PT-52171 PI-52171 R2B-P2-204-02-A-DTI-20043 EC52004 DSL PROD TO BL SCD kg/cm2g 19 0 14.3
PT-52172 PI-52172 R2B-P2-204-02-A-DTI-20045 EA52006 DSL PROD TO EA52007 SCD kg/cm2g 21 0 15.1
PT-52174 PI-52174 R2B-P2-204-02-A-DTI-20047 GA52004 DSL PROD TO EA52006 SCD kg/cm2g 21 0 18.34 14.47
PT-52175 PI-52175 R2B-P2-204-02-A-DTI-20047 EA52006 STAB DSL TO DF52001 SCD kg/cm2g 7 0 4.4

Sheet 6 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52177 PI-52177 R2B-P2-204-02-A-DTI-20047 DS52001 STAB DSL TO EA52006 SCD kg/cm2g 12 0 4.9
PT-52179 PI-52179 R2B-P2-204-02-A-DTI-20048 GA52005AB DSL PROD TO BA52002A SCD kg/cm2g 21 0 9.945
PT-52184 PI-52184 R2B-P2-204-02-A-DTI-20052 EC52005 SR NPTHA TO FA52010 SCD kg/cm2g 6 0 3.7 1.7
PT-52187A PI-52187A R2B-P2-204-02-A-DTI-20056 BA52002A MP STM TO BA52002B SCD kg/cm2g 21 0 12.7
PT-52191A PI-52191A R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD mmH2O 50 -50 0 -10
PT-52191B PI-52191B R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD mmH2O 50 -50 0 -10
PT-52192 PI-52192 R2B-P2-204-02-A-DTI-20049 GA52005CD DSL PROD TO BA52002B SCD kg/cm2g 21 0 9.945
PT-52196 PI-52196 R2B-P2-204-02-A-DTI-20070 FG TO BA52002B SCD kg/cm2g 8 0 5.2 3.8
PT-52198 PI-52198 R2B-P2-204-02-A-DTI-20057 FG TO BA52002A SCD kg/cm2g 8 0 5.2 3.8
PT-52211 PI-52211 R2B-P2-204-02-A-DTI-20042 GA52007AB SR NPTHA TO FA52009 SCD kg/cm2g 21 0 16.45
PT-52212 PI-52212 R2B-P2-204-02-A-DTI-20041 FA52011 SR GAS TO BL SCD kg/cm2g 19 0 9.7
PT-52220 PI-52220 R2B-P2-204-02-A-DTI-20103 FA52013 AMR TO BL SCD kg/cm2g 12 0 7
PT-52221 PI-52221 R2B-P2-204-02-A-DTI-20012 FA52016 MXD DSL TO FG52001 SCD kg/cm2g 10 0 7
PT-52226 PI-52226 R2B-P2-204-02-A-DTI-20027 BC52001A3 H2 TO EC52007_EA52003 SCD kg/cm2g 160 0 102 94
PT-52230 PI-52230 R2B-P2-204-02-A-DTI-20030 BC52001B3 H2 TO EA52003 SCD kg/cm2g 160 0 102 94
PT-52233 PI-52233 R2B-P2-204-02-A-DTI-20033 BC52001C3 H2 TO EA52003 SCD kg/cm2g 160 0 102 94
PT-52241A PI-52241A R2B-P2-204-02-A-DTI-20066 BA52002A AIR PREHEATER SCD mmH2O 0 -160 -100
PT-52241B PI-52241B R2B-P2-204-02-A-DTI-20068 BA52002B AIR PREHEATER SCD mmH2O 0 -160 -100
PT-52242A PI-52242A R2B-P2-204-02-A-DTI-20066A BA52002A AIR PREHEATER OUTL SCD mmH2O 200 0 20
PT-52242B PI-52242B R2B-P2-204-02-A-DTI-20068A BA52002B AIR PREHEATER OUTL SCD mmH2O 200 0 20
PT-52243A PI-52243A R2B-P2-204-02-A-DTI-20066B BA52002A COMBUSTION GAS BLOWER SCD mmH2O 100 0 20
PT-52243B PI-52243B R2B-P2-204-02-A-DTI-20068B BA52002B COMBUSTION GAS BLOWER SCD mmH2O 100 0 20
PT-52245A PI-52245A R2B-P2-204-02-A-DTI-20066 BA52002A COLD COMB AIR DUCT SCD mmH2O 300 0 30
PT-52245B PI-52245B R2B-P2-204-02-A-DTI-20068 BA52002B COLD COMB AIR DUCT SCD mmH2O 300 0 30
PT-52247 PI-52247 R2B-P2-204-02-A-DTI-20012 FA52016 WS TO FA52014 SCD kg/cm2g 2 0 0.49
PT-52248 PI-52248 R2B-P2-204-02-A-DTI-20003 FA52001 WS TO FA52014 SCD kg/cm2g 3 0 0.49
PT-52261 PI-52261 R2B-P2-204-02-A-DTI-20036 FA52008 HOT DSL TO EC52006 SCD kg/cm2g 25 0 15.4 13.4
PT-52270 PI-52270 R2B-P2-204-02-A-DTI-20209 FA52061 IA TO IA HEAD SCD kg/cm2g 10 0 5.5
PT-52298 PI-52298 R2B-P2-204-02-A-DTI-20244 FA52062 IA TO IA HEAD SCD kg/cm2g 10 0 5
PT-52450 PI-52450 R2B-P2-204-02-A-DTI-20025 BC-52001A-FA01 SCD kg/cm2g 40 0 19.2
PT-52451 PI-52451 R2B-P2-204-02-A-DTI-20027 BC-52001A-FA06 SCD kg/cm2g 200 0 101.3
PT-52453 PI-52453 R2B-P2-204-02-A-DTI-20701 BC52001A PRESS N2 BUFFER STUFF SCD kg/cm2g 5 0 2.9 2.3
PT-52454 PI-52454 R2B-P2-204-02-A-DTI-20701 BC52001A PRESS N2 BUFFERING SCD kg/cm2g 1 0 0.8 0.2
PT-52457 PI-52457 R2B-P2-204-02-A-DTI-20702 BC52001A PRESS LUBE OIL SYSTEM SCD kg/cm2g 16 0 7
PT-52458 PI-52458 R2B-P2-204-02-A-DTI-20702 BC52001A PRESS LO DOWNSTREAM PCV SCD kg/cm2g 6 0 2.6
PT-52461 PI-52461 R2B-P2-204-02-A-DTI-20703 BC52001A PRESS LUBRICATOR SCD kg/cm2g 40 0 1.5
PT-52462 PI-52462 R2B-P2-204-02-A-DTI-20709 BC52001A PRESS SUPPLY HEADER CW SCD kg/cm2g 7 0 4.5 2.5
PT-52463 PI-52463 R2B-P2-204-02-A-DTI-20706 BC52001A PRESS OIL TANK HYDROCOM SCD kg/cm2g 300 0 60
PT-52464 PI-52464 R2B-P2-204-02-A-DTI-20705 BC52001A PRESSURE JACK OIL SCD kg/cm2g 160 0 68

Sheet 7 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52501A PI-52501A R2B-P2-204-02-A-DTI-20073A DISCHARGE OF 2nd EJECTOR SCD kgf/cm²g 1 -1 0.15


PT-52501B PI-52501B R2B-P2-204-02-A-DTI-20073A CONDENSATE DRAIN OF AFTER CONDENSER SCD kgf/cm²g 1 -1 0.15
PT-52501C PI-52501C R2B-P2-204-02-A-DTI-20073A CONDENSATE WATER OUTLET SCD kgf/cm²g 15 0 9.2
PT-52502A PI-52502A R2B-P2-204-02-A-DTI-20073A DISCHARGE OF 1st EJECTOR SCD inH2O-a 400 0 236.25
PT-52502B PI-52502B R2B-P2-204-02-A-DTI-20073A CONDENSATE DRAIN OF INTER CONDENSER SCD inH2O-a 400 0 236.25
PT-52502D PI-52502D R2B-P2-204-02-A-DTI-20073A CONDENSATE WATER INLET SCD kgf/cm²g 15 0 9.2
PT-52540 PI-52540 R2B-P2-204-02-A-DTI-20058 SPE52001 PRESS SCD kg/cm2g 56 0 5.09
PT-52544A PI-52544A R2B-P2-204-02-A-DTI-20058 MSPE_52001_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52544B PI-52544B R2B-P2-204-02-A-DTI-20058 MSPE_52001_BD01B PRESS SCD kg/cm2g 56 0 1.4
PT-52545 PI-52545 R2B-P2-204-02-A-DTI-20059 SPE52002 PRESS SCD kg/cm2g 56 0 5.06
PT-52549A PI-52549A R2B-P2-204-02-A-DTI-20059 MSPE_52002_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52549B PI-52549B R2B-P2-204-02-A-DTI-20059 MSPE_52002_BD01B PRESS SCD kg/cm2g 56 0 1.4
PT-52550 PI-52550 R2B-P2-204-02-A-DTI-20028 BC-52001B-FA01 SCD kg/cm2g 40 0 19.2
PT-52551 PI-52551 R2B-P2-204-02-A-DTI-20030 BC-52001B-FA06 SCD kg/cm2g 200 0 101.3
PT-52553 PI-52553 R2B-P2-204-02-A-DTI-20711 BC52001B PRESS N2 BUFFE STUFF SCD kg/cm2g 5 0 2.9 2.3
PT-52554 PI-52554 R2B-P2-204-02-A-DTI-20711 BC52001B PRESS N2 BUFFERING I.C SCD kg/cm2g 1 0 0.8 0.2
PT-52557 PI-52557 R2B-P2-204-02-A-DTI-20712 BC52001B PRESS LUBE OIL SYSTEM SCD kg/cm2g 16 0 7
PT-52558 PI-52558 R2B-P2-204-02-A-DTI-20712 BC52001B PRESS LO DOWNSTREAM PCV SCD kg/cm2g 6 0 2.6
PT-52561 PI-52561 R2B-P2-204-02-A-DTI-20713 BC52001B PRESS LUBRICATOR SCD kg/cm2g 40 0 1.5
PT-52563 PI-52563 R2B-P2-204-02-A-DTI-20716 BC52001B PRESS OIL TANK HYDROCOM SCD kg/cm2g 300 0 60
PT-52564 PI-52564 R2B-P2-204-02-A-DTI-20715 BC52001B PRESSURE JACK OIL SCD kg/cm2g 160 0 68
PT-52650 PI-52650 R2B-P2-204-02-A-DTI-20031 BC-52001C-FA01 SCD kg/cm2g 40 0 19.2
PT-52651 PI-52651 R2B-P2-204-02-A-DTI-20033 BC-52001C-FA06 SCD kg/cm2g 200 0 101.3
PT-52653 PI-52653 R2B-P2-204-02-A-DTI-20721 BC52001C PRESS N2 BUFFER STUFF SCD kg/cm2g 5 0 2.9 2.3
PT-52654 PI-52654 R2B-P2-204-02-A-DTI-20721 BC52001C PRESS N2 BUFFERING SCD kg/cm2g 1 0 0.8 0.2
PT-52654A PI-52654A R2B-P2-204-02-A-DTI-20060 MSPE_52003_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52654B PI-52654B R2B-P2-204-02-A-DTI-20060 MSPE_52003_BD01B PRESS SCD kg/cm2g 56 0 1.4
PT-52654C PI-52654C R2B-P2-204-02-A-DTI-20060 SPE52003 PRESS SCD kg/cm2g 56 0 6.72
PT-52655 PI-52655 R2B-P2-204-02-A-DTI-20061 SPE52004 PRESS SCD kg/cm2g 56 0 20.96
PT-52657 PI-52657 R2B-P2-204-02-A-DTI-20722 BC52001C PRESS LUBE OIL SYSTEM SCD kg/cm2g 16 0 7
PT-52658 PI-52658 R2B-P2-204-02-A-DTI-20722 BC52001C PRESS LO DOWNSTREAM PCV SCD kg/cm2g 6 0 2.6
PT-52659A PI-52659A R2B-P2-204-02-A-DTI-20061 MSPE_52004_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52659B PI-52659B R2B-P2-204-02-A-DTI-20061 MSPE_52004_BD01B PRESS SCD kg/cm2g 56 0 1.4
PT-52660 PI-52660 R2B-P2-204-02-A-DTI-20062 SPE52005 PRESS SCD kg/cm2g 56 0 18.16
PT-52661 PI-52661 R2B-P2-204-02-A-DTI-20723 BC52001C PRESS LUBRICATOR SCD kg/cm2g 40 0 1.5
PT-52663 PI-52663 R2B-P2-204-02-A-DTI-20726 BC52001C PRESS OIL TANK HYDROCOM SCD kg/cm2g 300 0 60
PT-52664 PI-52664 R2B-P2-204-02-A-DTI-20725 BC52001C PRESSURE JACK OIL SCD kg/cm2g 160 0 68
PT-52664A PI-52664A R2B-P2-204-02-A-DTI-20062 MSPE_52005_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52664B PI-52664B R2B-P2-204-02-A-DTI-20062 MSPE_52005_BD01A PRESS SCD kg/cm2g 56 0 1.4

Sheet 8 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52665 PI-52665 R2B-P2-204-02-A-DTI-20063 SPE52006 PRESS SCD kg/cm2g 56 0 8.13


PT-52669A PI-52669A R2B-P2-204-02-A-DTI-20063 MSPE_52006_BD01A PRESS SCD kg/cm2g 56 0 1.4
PT-52669B PI-52669B R2B-P2-204-02-A-DTI-20063 MSPE_52006_BD01B PRESS SCD kg/cm2g 56 0 1.4
PT-52702 PI-52702 R2B-P2-204-02-A-DTI-20201 FA52051 FG TO FG52051AB SCD kg/cm2g 10 0 5.5 3.5
PT-52706 PI-52706 R2B-P2-204-02-A-DTI-20302 FA52052 LFL TO BL SCD kg/cm2g 3 -1 2.1
PT-52708 PI-52708 R2B-P2-204-02-A-DTI-20302 FA52053 HFL TO BL SCD kg/cm2g 4.1 -1 3.1
PT-52709 PI-52709 R2B-P2-204-02-A-DTI-20301 N2 TO N2 HEAD SCD kg/cm2g 16 0 9
PT-52718 PI-52718 R2B-P2-204-02-A-DTI-20304 GA52058 LP OILY COND TO BL SCD kg/cm2g 12 0 8.6 3.5
PT-52737 PI-52737 R2B-P2-204-02-A-DTI-20222 FA52055 SLOP DRAIN DRUM SCD kg/cm2g 1.6 0 1.05 0.49
PT-52741 PI-52741 R2B-P2-204-02-A-DTI-20225 FA52056 AMINE DRAIN DRUM SCD kg/cm2g 1.6 0 1.05 0.49
PT-52743 PI-52743 R2B-P2-204-02-A-DTI-20303 HP STM TO HP STM HEAD SCD kg/cm2g 100 0 41.2
PT-52747 PI-52747 R2B-P2-204-02-A-DTI-20304 CWS TO CWS HEAD SCD kg/cm2g 10 0 5.5
PT-52749 PI-52749 R2B-P2-204-02-A-DTI-20304 SPE52021EA1 LP CCD TO BL SCD kg/cm2g 10 0 7 3.5
PT-52775 PI-52775 R2B-P2-204-02-A-DTI-20304 SERV WTR TO SERV WTR HEAD SCD kg/cm2g 10 0 4.5
PT-52784 PI-52784 R2B-P2-204-02-A-DTI-20072 SPE52021EA1 RECYCLE H2 CMPR SCD inH2O-a 410 0 231
PT-52785 PI-52785 R2B-P2-204-02-A-DTI-20072 GA52021AB LP CCD TO SPE52021EA2 SCD kg/cm2g 16 0 7.47
PT-52792 PI-52792 R2B-P2-204-02-A-DTI-20209A A DRYING TOWER OUTLET LINE SCD kg/cm2g 10 0 2.5 6.5
PT-52793 PI-52793 R2B-P2-204-02-A-DTI-20209A B DRYING TOWER OUTLET LINE SCD kg/cm2g 10 0 2.5 6.5
PT-52113 PIC-52113 R2B-P2-204-02-A-DTI-20003 FG TO FA52001 SCD kg/cm2g 9 0 3.5 1.5
PT-52136 PIC-52136 R2B-P2-204-02-A-DTI-20018 FG TO LFL HEAD SCD kg/cm2g 1 0 1 0.49
PT-52137 PIC-52137 R2B-P2-204-02-A-DTI-20019 FA52003 SR GAS TO HFL HEAD SCD kg/cm2g 141 0 78.8 70.8
PT-52138A PIC-52138A R2B-P2-204-02-A-DTI-20019 FA52003 SR GAS TO HFL HEAD SCD kg/cm2g 92 0 78.8 70.8
PT-52138B PIC-52138B R2B-P2-204-02-A-DTI-20019 FA52003 SR GAS TO HFL HEAD SCD kg/cm2g 92 0 78.8 70.8
PT-52140 PIC-52140 R2B-P2-204-02-A-DTI-20021 FA52013 SR GAS TO BL SCD kg/cm2g 19 0 12 8.5
PT-52143 PIC-52143 R2B-P2-204-02-A-DTI-20022 FA52015 AML TO LFL HEAD SCD kg/cm2g 6 0 4 2
PT-52144 PIC-52144 R2B-P2-204-02-A-DTI-20024 H2 TO FA52004 SCD kg/cm2g 44 0 21.525 19.475
PT-52145 PIC-52145 R2B-P2-204-02-A-DTI-20024 FA52004 H2TO BC52001A1_B1_C1 SCD kg/cm2g 40 0 19.475
PT-52186A PIC-52186A R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD mmH2O 75 -75 20 -10
PT-52186B PIC-52186B R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD mmH2O 75 -75 20 -10
PT-52206 PIC-52206 R2B-P2-204-02-A-DTI-20071 FA52012 FG TO LFL SCD kg/cm2g 8 0 5
PT-52209 PIC-52209 R2B-P2-204-02-A-DTI-20037 FA52009 SR GAS TO BL SCD kg/cm2g 21 0 15
PT-52214 PIC-52214 R2B-P2-204-02-A-DTI-20052 FA52010 SR NPTHA TO LFL HEAD SCD kg/cm2g 6 0 3.7 1.7
PT-52227 PIC-52227 R2B-P2-204-02-A-DTI-20041 FA52011 SR GAS TO BL SCD kg/cm2g 19 0 11.7
PT-52260 PIC-52260 R2B-P2-204-02-A-DTI-20065 BA52002AB MP STMTO MP STM HEAD SCD kg/cm2g 21 0 14.7
N/A TDI-52183 R2B-P2-204-02-A-DTI-20016 RECYCLE H2 TO FA52003 SCD °C 11
TE-52003 TI-52003 R2B-P2-204-02-A-DTI-20032 EC52003C H2 TO FA52006C SCD °C 100 0 60.5
TE-52111 TI-52111 R2B-P2-204-02-A-DTI-20002 EA52001B DSL TO FA52001 SCD °C 300 0 145 125
TE-52115 TI-52115 R2B-P2-204-02-A-DTI-20005 EA52002 EFFL TO FA52002 SCD °C 300 0 251.7
TE-52122 TI-52122 R2B-P2-204-02-A-DTI-20006A EA52005 EFFL TO EA52003 SCD °C 450 0 365.8

Sheet 9 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52129A TI-52129A R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129B TI-52129B R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129C TI-52129C R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129D TI-52129D R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129E TI-52129E R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129F TI-52129F R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129G TI-52129G R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129H TI-52129H R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129I TI-52129I R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129J TI-52129J R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129K TI-52129K R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129L TI-52129L R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129M TI-52129M R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129N TI-52129N R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129O TI-52129O R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129P TI-52129P R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129Q TI-52129Q R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129R TI-52129R R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129S TI-52129S R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129T TI-52129T R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129U TI-52129U R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129V TI-52129V R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129W TI-52129W R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52129X TI-52129X R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131A TI-52131A R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131B TI-52131B R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131C TI-52131C R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131D TI-52131D R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131E TI-52131E R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131F TI-52131F R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131G TI-52131G R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131H TI-52131H R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131I TI-52131I R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131J TI-52131J R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131K TI-52131K R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52131L TI-52131L R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
TE-52132 TI-52132 R2B-P2-204-02-A-DTI-20072 SPE52021EA1 GAS TO BY52021 SCD °C 100 0 63.82
TE-52136 TI-52136 R2B-P2-204-02-A-DTI-20008 DC52001 DSL H2 TO DC002 SCD °C 450 0 336
TE-52137A TI-52137A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338

Sheet 10 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52137B TI-52137B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137C TI-52137C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137D TI-52137D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137E TI-52137E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137F TI-52137F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137G TI-52137G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137H TI-52137H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137I TI-52137I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137J TI-52137J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137K TI-52137K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137L TI-52137L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137M TI-52137M R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137N TI-52137N R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137O TI-52137O R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137P TI-52137P R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137Q TI-52137Q R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137R TI-52137R R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137S TI-52137S R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137T TI-52137T R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137U TI-52137U R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137V TI-52137V R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137W TI-52137W R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52137X TI-52137X R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139A TI-52139A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139B TI-52139B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139C TI-52139C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139D TI-52139D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139E TI-52139E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139F TI-52139F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139G TI-52139G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139H TI-52139H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139I TI-52139I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139J TI-52139J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139K TI-52139K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52139L TI-52139L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TE-52145 TI-52145 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER SCD °C 1000 0 795
TE-52146 TI-52146 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER SCD °C 1000 0 795
TE-52147 TI-52147 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52148 TI-52148 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470

Sheet 11 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52149 TI-52149 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470


TE-52150 TI-52150 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52151 TI-52151 R2B-P2-204-02-A-DTI-20009A BA52001 DSL H2 TO DC52001 SCD °C 450 0 309.2
TE-52152 TI-52152 R2B-P2-204-02-A-DTI-20009A BA52001 DSL H2 TO DC52001 SCD °C 450 0 309.2
TE-52153 TI-52153 R2B-P2-204-02-A-DTI-20009A BA52001 DSL H2 TO DC52001 SCD °C 450 0 309.2
TE-52154 TI-52154 R2B-P2-204-02-A-DTI-20009A BA52001 DSL H2 TO DC52001 SCD °C 450 0 309.2
TE-52156 TI-52156 R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER SCD °C 400 0 350
TE-52164A TI-52164A R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164B TI-52164B R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164C TI-52164C R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164D TI-52164D R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164E TI-52164E R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164F TI-52164F R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164G TI-52164G R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164H TI-52164H R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52164I TI-52164I R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165A TI-52165A R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165B TI-52165B R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165C TI-52165C R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165D TI-52165D R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165E TI-52165E R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165F TI-52165F R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165G TI-52165G R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165H TI-52165H R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165I TI-52165I R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165J TI-52165J R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165K TI-52165K R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165L TI-52165L R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165M TI-52165M R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165N TI-52165N R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165O TI-52165O R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165P TI-52165P R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165Q TI-52165Q R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52165R TI-52165R R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
TE-52166A TI-52166A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166B TI-52166B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166C TI-52166C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166D TI-52166D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166E TI-52166E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344

Sheet 12 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52166F TI-52166F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166G TI-52166G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166H TI-52166H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52166I TI-52166I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167A TI-52167A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167B TI-52167B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167C TI-52167C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167D TI-52167D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167E TI-52167E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167F TI-52167F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167G TI-52167G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167H TI-52167H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167I TI-52167I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167J TI-52167J R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167K TI-52167K R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167L TI-52167L R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167M TI-52167M R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167N TI-52167N R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167O TI-52167O R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167P TI-52167P R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167Q TI-52167Q R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52167R TI-52167R R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
TE-52171 TI-52171 R2B-P2-204-02-A-DTI-20025 EC52002A H2 TO FA52005A SCD °C 100 0 60.5
TE-52173 TI-52173 R2B-P2-204-02-A-DTI-20026 EC52003A H2 TO FA52006A SCD °C 100 0 60.5
TE-52175A TI-52175A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175B TI-52175B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175C TI-52175C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175D TI-52175D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175E TI-52175E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175F TI-52175F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175G TI-52175G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175H TI-52175H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175I TI-52175I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175J TI-52175J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175K TI-52175K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52175L TI-52175L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176A TI-52176A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176B TI-52176B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176C TI-52176C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348

Sheet 13 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52176D TI-52176D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176E TI-52176E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176F TI-52176F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176G TI-52176G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176H TI-52176H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176I TI-52176I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176J TI-52176J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176K TI-52176K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176L TI-52176L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176M TI-52176M R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176N TI-52176N R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176O TI-52176O R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176P TI-52176P R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176Q TI-52176Q R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176R TI-52176R R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176S TI-52176S R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176T TI-52176T R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176U TI-52176U R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176V TI-52176V R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176W TI-52176W R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52176X TI-52176X R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177A TI-52177A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177B TI-52177B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177C TI-52177C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177D TI-52177D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177E TI-52177E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177F TI-52177F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177G TI-52177G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177H TI-52177H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52177I TI-52177I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178A TI-52178A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178B TI-52178B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178C TI-52178C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178D TI-52178D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178E TI-52178E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178F TI-52178F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178G TI-52178G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178H TI-52178H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178I TI-52178I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348

Sheet 14 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52178J TI-52178J R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178K TI-52178K R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178L TI-52178L R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178M TI-52178M R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178N TI-52178N R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178O TI-52178O R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178P TI-52178P R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178Q TI-52178Q R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52178R TI-52178R R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348
TE-52181 TI-52181 R2B-P2-204-02-A-DTI-20029 EC52003A H2 TO FA52006A SCD °C 150 0 60.5
TT-52183 TI-52183 R2B-P2-204-02-A-DTI-20016 EC52001 SR GAS TO FA52003 SCD °C 100 0 59.4
TE-52217 TI-52217 R2B-P2-204-02-A-DTI-20035 GB52001 RECY H2 TO EC52001 SCD °C 200 0 107.8
TE-52220 TI-52220 R2B-P2-204-02-A-DTI-20036 EC52006 HOT DSL TO FA52009 SCD °C 100 0 59.4
TE-52234 TI-52234 R2B-P2-204-02-A-DTI-20104 EC52004 DSL PROD TO BL SCD °C 100 0 60.5
TE-52241 TI-52241 R2B-P2-204-02-A-DTI-20046 DF52001 FRACTIONATOR SCD °C 450 0 221 191
TE-52251 TI-52251 R2B-P2-204-02-A-DTI-20104 EA52009 NPTHA TO BL SCD °C 100 0 41.8
TE-52252 TI-52252 R2B-P2-204-02-A-DTI-20104 EA52009 NPTHA TO BL SCD °C 100 0 41.8
TT-52253 TI-52253 R2B-P2-204-02-A-DTI-20053 GA52003AB SR NPTHA TO DF52001 SCD °C 100 0 59.4
TT-52258 TI-52258 R2B-P2-204-02-A-DTI-20052 EA52009 SR NPTHA TO BL SCD °C 100 0 59.4
TE-52259A TI-52259A R2B-P2-204-02-A-DTI-20056 BA52002A MP STM TO BA52002B SCD °C 300 0 245.2 215.2
TE-52259B TI-52259B R2B-P2-204-02-A-DTI-20065 BA52002B MP STM TO STM HEAD SCD °C 300 0 245.2 215.2
TE-52264A TI-52264A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52264B TI-52264B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52266A TI-52266A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52266B TI-52266B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52268A TI-52268A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52268B TI-52268B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52270A TI-52270A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52270B TI-52270B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52271A TI-52271A R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52271B TI-52271B R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52272A TI-52272A R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD °C 600 0 390
TE-52272B TI-52272B R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD °C 600 0 390
TE-52273 TI-52273 R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52274 TI-52274 R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52275 TI-52275 R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52276 TI-52276 R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD °C 1000 0 855
TE-52277A TI-52277A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52277B TI-52277B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415

Sheet 15 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52278A TI-52278A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415


TE-52278B TI-52278B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52279A TI-52279A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52279B TI-52279B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52280A TI-52280A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52280B TI-52280B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52281A TI-52281A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52281B TI-52281B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52282A TI-52282A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52282B TI-52282B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52283A TI-52283A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52283B TI-52283B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52284A TI-52284A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52284B TI-52284B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52285A TI-52285A R2B-P2-204-02-A-DTI-20056 BA52002A FRACTIONATOR REBOILER SCD °C 600 0 390
TE-52285B TI-52285B R2B-P2-204-02-A-DTI-20065 BA52002B FRACTIONATOR REBOILER SCD °C 600 0 390
TE-52287A TI-52287A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52287B TI-52287B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52289A TI-52289A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52289B TI-52289B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52291A TI-52291A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52291B TI-52291B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52293A TI-52293A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52293B TI-52293B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7
TE-52295A TI-52295A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 0 334.7 304.7
TE-52295B TI-52295B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 0 334.7 304.7
TE-52310 TI-52310 R2B-P2-204-02-A-DTI-20038 DS52001 SR NPTHA TO EC52008 SCD °C 300 0 233.3 203.3
TT-52311 TI-52311 R2B-P2-204-02-A-DTI-20041 EA52004 SR NPTHA TO FA52011 SCD °C 100 0 41.8
TE-52327A TI-52327A R2B-P2-204-02-A-DTI-20066A BA52002A FRACTIONATOR REBOILER SCD °C 500 0 300
TE-52327B TI-52327B R2B-P2-204-02-A-DTI-20068A BA52002B FRACTIONATOR REBOILER SCD °C 500 0 300
TE-52329A TI-52329A R2B-P2-204-02-A-DTI-20066 BA52002A AIR PREHEATER SCD °C 200 0 155 125
TE-52329B TI-52329B R2B-P2-204-02-A-DTI-20068 BA52002B AIR PREHEATER SCD °C 200 0 155 125
TE-52330A TI-52330A R2B-P2-204-02-A-DTI-20066 BA52002A COLD COMB AIR DUCT SCD °C 100 0 10
TE-52330B TI-52330B R2B-P2-204-02-A-DTI-20068 BA52002B COLD COMB AIR DUCT SCD °C 100 0 10
TE-52333A TI-52333A R2B-P2-204-02-A-DTI-20066 BA52002A_EA01 AIR PREHEATER SCD °C 200 0 124
TE-52333B TI-52333B R2B-P2-204-02-A-DTI-20068 BA52002B_EA01 AIR PREHEATER SCD °C 200 0 124
TE-52334A TI-52334A R2B-P2-204-02-A-DTI-20066 BA52002A_EA01 AIR PREHEATER SCD °C 200 0 124
TE-52334B TI-52334B R2B-P2-204-02-A-DTI-20068 BA52002B_EA01 AIR PREHEATER SCD °C 200 0 124
TE-52420 TI-52420 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470

Sheet 16 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52421 TI-52421 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470


TE-52422 TI-52422 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52423 TI-52423 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52424 TI-52424 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52425 TI-52425 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52426 TI-52426 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52427 TI-52427 R2B-P2-204-02-A-DTI-20009A BA52001FEED HEATER SCD °C 600 0 470
TE-52429A TI-52429A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52429B TI-52429B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52430A TI-52430A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52430B TI-52430B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52431A TI-52431A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52431B TI-52431B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52432A TI-52432A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52432B TI-52432B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52433A TI-52433A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52433B TI-52433B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52434A TI-52434A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52434B TI-52434B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52435A TI-52435A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52435B TI-52435B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52436A TI-52436A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52436B TI-52436B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52437A TI-52437A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52437B TI-52437B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52438A TI-52438A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52438B TI-52438B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52439A TI-52439A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52439B TI-52439B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52440A TI-52440A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52440B TI-52440B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52441A TI-52441A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52441B TI-52441B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52442A TI-52442A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52442B TI-52442B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52443A TI-52443A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52443B TI-52443B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52444A TI-52444A R2B-P2-204-02-A-DTI-20056 BA52002AFRACTIONATOR REBOILER SCD °C 600 0 415
TE-52444B TI-52444B R2B-P2-204-02-A-DTI-20065 BA52002BFRACTIONATOR REBOILER SCD °C 600 0 415

Sheet 17 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52451 TI-52451 R2B-P2-204-02-A-DTI-20025 BC-52001A 1ST STG OUTL SCD °C 190 0 108
TE-52454 TI-52454 R2B-P2-204-02-A-DTI-20026 BC-52001A 2ND STG OUTL SCD °C 230 0 130
TE-52457 TI-52457 R2B-P2-204-02-A-DTI-20027 BC-52001A 3RD STG OUTL SCD °C 230 0 131
TE-52459 TI-52459 R2B-P2-204-02-A-DTI-20702 BC52001A TEMP LO DOWNSTR COOLER SCD °C 115 0 60 20
TT-52460 TI-52460 R2B-P2-204-02-A-DTI-20702 BC52001A TEMP LUBE OIL CRANCK SCD °C 115 0 40 25
TT-52461 TI-52461 R2B-P2-204-02-A-DTI-20709 BC52001A TEMP RETURN HEADER CW SCD °C 115 0 80 60
TT-52462 TI-52462 R2B-P2-204-02-A-DTI-20709 BC52001A TEMP SUPPLY HEADER CW SCD °C 115 0 80 50
TE-52463 TI-52463 R2B-P2-204-02-A-DTI-20706 BC52001A TEMP OIL TANK HYDROCOM SCD °C 130 0 70
TE-52467 TI-52467 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 1 CE SCD °C 190 0 103
TE-52468 TI-52468 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 1 HE SCD °C 190 0 103
TE-52469 TI-52469 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP STUFF VENT STG1 SCD °C 115 0 81
TE-52472 TI-52472 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 2 CE SCD °C 230 0 125
TE-52473 TI-52473 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 2 HE SCD °C 230 0 125
TE-52474 TI-52474 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP STUFF VENT STG2 SCD °C 115 0 100
TE-52477 TI-52477 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 3 CE SCD °C 230 0 126
TE-52478 TI-52478 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP DISCH VLV STG 3 HE SCD °C 230 0 126
TE-52479 TI-52479 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP STUFF VENT STG3 SCD °C 115 0 98
TE-52493 TI-52493 R2B-P2-204-02-A-DTI-20705 BC52001A MAIN DRIVE COLD AIR SCD °C 190 0 110 100
TE-52494 TI-52494 R2B-P2-204-02-A-DTI-20705 BC52001A MAIN DRIVE HOT AIR SCD °C 190 0 130 120
TE-52551 TI-52551 R2B-P2-204-02-A-DTI-20028 BC-52001B 1ST STG OUTL SCD °C 190 0 108
TE-52554 TI-52554 R2B-P2-204-02-A-DTI-20029 BC-52001B 2ND STG OUTL SCD °C 230 0 130
TE-52557 TI-52557 R2B-P2-204-02-A-DTI-20030 BC-52001B 3RD STG OUTL SCD °C 230 0 131
TE-52559 TI-52559 R2B-P2-204-02-A-DTI-20712 BC52001B TEMP LO DOWNSTR COOLER SCD °C 115 0 60 20
TT-52560 TI-52560 R2B-P2-204-02-A-DTI-20712 BC52001B TEMP LO CRANCKCASE SCD °C 115 0 40 25
TE-52563 TI-52563 R2B-P2-204-02-A-DTI-20716 BC52001B TEMP OIL TANK HYDROCOM SCD °C 130 0 70
TE-52567 TI-52567 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 1 CE SCD °C 190 0 103
TE-52568 TI-52568 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 1 HE SCD °C 190 0 103
TE-52569 TI-52569 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP VENT STG1 SCD °C 115 0 81
TE-52572 TI-52572 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 2 CE SCD °C 230 0 125
TE-52573 TI-52573 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 2 HE SCD °C 230 0 125
TE-52574 TI-52574 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP VENT STG2 SCD °C 115 0 100
TE-52577 TI-52577 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 3 CE SCD °C 230 0 126
TE-52578 TI-52578 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP DISCH VLV STG 3 HE SCD °C 230 0 126
TE-52579 TI-52579 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP VENT STG3 SCD °C 115 0 98
TE-52593 TI-52593 R2B-P2-204-02-A-DTI-20715 BC52001B MAIN DRIVE COLD AIR SCD °C 190 0 110 100
TE-52594 TI-52594 R2B-P2-204-02-A-DTI-20715 BC52001B MAIN DRIVE HOT AIR SCD °C 190 0 130 120
TE-52651 TI-52651 R2B-P2-204-02-A-DTI-20031 BC-52001C 1ST STG OUTL SCD °C 190 0 108
TE-52654 TI-52654 R2B-P2-204-02-A-DTI-20032 BC-52001C 2ND STG OUTL SCD °C 230 0 130
TE-52657 TI-52657 R2B-P2-204-02-A-DTI-20033 BC-52001C 3RD STG OUTL SCD °C 230 0 131

Sheet 18 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52659 TI-52659 R2B-P2-204-02-A-DTI-20722 BC52001C TEMP LO DOWNSTR COOLER SCD °C 115 0 60 20


TT-52660 TI-52660 R2B-P2-204-02-A-DTI-20722 BC52001C TEMP LO CRANCKCASE SCD °C 115 0 40 25
TE-52663 TI-52663 R2B-P2-204-02-A-DTI-20726 BC52001C TEMP OIL TANK HYDROCOM SCD °C 130 0 70
TE-52667 TI-52667 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 1 CE SCD °C 190 0 103
TE-52668 TI-52668 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 1 HE SCD °C 190 0 103
TE-52669 TI-52669 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP STUFF VENT STG1 SCD °C 115 0 81
TE-52672 TI-52672 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 2 CE SCD °C 230 0 125
TE-52673 TI-52673 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 2 HE SCD °C 230 0 125
TE-52674 TI-52674 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP STUFF VENT STG2 SCD °C 115 0 100
TE-52677 TI-52677 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 3 CE SCD °C 230 0 126
TE-52678 TI-52678 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP DISCH VLV STG 3 HE SCD °C 230 0 126
TE-52679 TI-52679 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP STUFF VENT STG3 SCD °C 115 0 98
TE-52693 TI-52693 R2B-P2-204-02-A-DTI-20725 BC52001C MAIN DRIVE COLD AIR SCD °C 190 0 110 100
TE-52694 TI-52694 R2B-P2-204-02-A-DTI-20725 BC52001C MAIN DRIVE HOT AIR SCD °C 190 0 130 120
TE-52705 TI-52705 R2B-P2-204-02-A-DTI-20211 FA52052 LFL KO DRM SCD °C 100 0 66
TE-52707 TI-52707 R2B-P2-204-02-A-DTI-20213 FA52053 HFL KO DRM SCD °C 100 0 66
TT-52718 TI-52718 R2B-P2-204-02-A-DTI-20222 FA52055 SLOPS DRM SCD °C 200 0 133
TT-52719 TI-52719 R2B-P2-204-02-A-DTI-20225 FA52056 AMN DRN DRM SCD °C 100 0 71.5
TE-52721 TI-52721 R2B-P2-204-02-A-DTI-20072A HPS TO GA52021 SCD °C 600 0 400 370
TE-52723 TI-52723 R2B-P2-204-02-A-DTI-20222 EC52052 Slop OIL TO BL SCD °C 100 0 60.5
TE-52747 TI-52747 R2B-P2-204-02-A-DTI-20304 CWS TO CWS HD SCD °C 100 0 35.2
TE-52748 TI-52748 R2B-P2-204-02-A-DTI-20304 CWR TO BL SCD °C 100 0 37.8
TT-52790 TI-52790 R2B-P2-204-02-A-DTI-20209A A DRYING TOWER SCD °C 100 0 50
TT-52791 TI-52791 R2B-P2-204-02-A-DTI-20209A B DRYING TOWER SCD °C 100 0 50
TT-52792 TI-52792 R2B-P2-204-02-A-DTI-20209A Air Dryer Outlet SCD °C 100 0 50
TT-52116 TIC-52116 R2B-P2-204-02-A-DTI-20005 EA52002 EFFL TO FA52002 SCD °C 300 0 251.7 221.7
TT-52125 TIC-52125 R2B-P2-204-02-A-DTI-20007 EA52005 DSL H2 TO DC52001 SCD °C 450 50 318
N/A TIC-52129 R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
N/A TIC-52131 R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 328
N/A TIC-52137 R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
N/A TIC-52139 R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 338
TT-52163 TIC-52163 R2B-P2-204-02-A-DTI-20008 DC52001 DSL H2 TO DC002 SCD °C 450 50 336
N/A TIC-52164 R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 340
N/A TIC-52165 R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR SCD °C 450 0 340
N/A TIC-52166 R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
N/A TIC-52167 R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 344
N/A TIC-52175 R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 500 0 348
N/A TIC-52176 R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR SCD °C 450 0 348
N/A TIC-52177 R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 500 0 348

Sheet 19 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

N/A TIC-52178 R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR SCD °C 450 0 348
TT-52196 TIC-52196 R2B-P2-204-02-A-DTI-20027A EC52007 TO FA52004 SCD °C 100 0 60.5
TT-52240 TIC-52240 R2B-P2-204-02-A-DTI-20046 EA52006 STAB DSL TO DF52001 SCD °C 300 0 237
TT-52242 TIC-52242 R2B-P2-204-02-A-DTI-20046 DF52001 SR NPTHA TO EC52005 SCD °C 300 0 228 158
TT-52257 TIC-52257 R2B-P2-204-02-A-DTI-20052 EA52009 SR NPTHA TO BL SCD °C 100 0 59.4 48.6
TT-52294A TIC-52294A R2B-P2-204-02-A-DTI-20056 BA52002A DSL PROD TO DF52001 SCD °C 450 50 334.7 304.7
TT-52294B TIC-52294B R2B-P2-204-02-A-DTI-20065 BA52002B DSL PROD TO DF52001 SCD °C 450 50 334.7 304.7
TT-52331A TIC-52331A R2B-P2-204-02-A-DTI-20066 BA52002A AIR PREHEATER SCD °C 300 0 155 125
TT-52331B TIC-52331B R2B-P2-204-02-A-DTI-20068 BA52002B AIR PREHEATER SCD °C 300 0 155 125
VT-52051A VI-52051A R2B-P2-204-02-A-DTI-20237 MEC_52051A VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52051B VI-52051B R2B-P2-204-02-A-DTI-20237 MEC_52051B VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52052A VI-52052A R2B-P2-204-02-A-DTI-20222 MEC_52052A VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52052B VI-52052B R2B-P2-204-02-A-DTI-20222 MEC_52052B VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52062A VI-52062A R2B-P2-204-02-A-DTI-20025 MEC_52002A VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52062B VI-52062B R2B-P2-204-02-A-DTI-20025 MEC_52002B VIBRATION SCD mm/s RMS 50 0 8.5 7.6
VT-52102A VI-52102A R2B-P2-204-02-A-DTI-20016 MEC_52001A SCD mm/s RMS 50 0 9 7
VT-52102B VI-52102B R2B-P2-204-02-A-DTI-20016 MEC_52001B SCD mm/s RMS 50 0 9 7
VT-52102C VI-52102C R2B-P2-204-02-A-DTI-20016 MEC_52001C SCD mm/s RMS 50 0 9 7
VT-52102D VI-52102D R2B-P2-204-02-A-DTI-20016 MEC_52001D SCD mm/s RMS 50 0 9 7
VT-52102E VI-52102E R2B-P2-204-02-A-DTI-20016 MEC_52001E SCD mm/s RMS 50 0 9 7
VT-52102F VI-52102F R2B-P2-204-02-A-DTI-20016 MEC_52001F SCD mm/s RMS 50 0 9 7
VT-52102G VI-52102G R2B-P2-204-02-A-DTI-20016 MEC_52001G SCD mm/s RMS 50 0 9 7
VT-52102H VI-52102H R2B-P2-204-02-A-DTI-20016 MEC_52001H SCD mm/s RMS 50 0 9 7
VT-52102I VI-52102I R2B-P2-204-02-A-DTI-20016 MEC_52001I SCD mm/s RMS 50 0 9 7
VT-52102J VI-52102J R2B-P2-204-02-A-DTI-20016 MEC_52001J SCD mm/s RMS 50 0 9 7
VT-52102K VI-52102K R2B-P2-204-02-A-DTI-20016 MEC_52001K SCD mm/s RMS 50 0 9 7
VT-52102L VI-52102L R2B-P2-204-02-A-DTI-20016 MEC_52001L SCD mm/s RMS 50 0 9 7
VT-52102M VI-52102M R2B-P2-204-02-A-DTI-20016 MEC_52001M SCD mm/s RMS 50 0 9 7
VT-52102N VI-52102N R2B-P2-204-02-A-DTI-20016 MEC_52001N SCD mm/s RMS 50 0 9 7
VT-52102O VI-52102O R2B-P2-204-02-A-DTI-20016 MEC_52001O SCD mm/s RMS 50 0 9 7
VT-52102P VI-52102P R2B-P2-204-02-A-DTI-20016 MEC_52001P SCD mm/s RMS 50 0 9 7
VT-52109A VI-52109A R2B-P2-204-02-A-DTI-20027A MEC_52007A VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52109B VI-52109B R2B-P2-204-02-A-DTI-20027A MEC_52007B VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52114A VI-52114A R2B-P2-204-02-A-DTI-20036 MEC_52006A VIBRATION SCD mm/s RMS 50 0 9 7
VT-52114B VI-52114B R2B-P2-204-02-A-DTI-20036 MEC_52006B VIBRATION SCD mm/s RMS 50 0 9 7
VT-52115A VI-52115A R2B-P2-204-02-A-DTI-20043 MEC_52004A VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115B VI-52115B R2B-P2-204-02-A-DTI-20043 MEC_52004B VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115C VI-52115C R2B-P2-204-02-A-DTI-20043 MEC_52004C VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115D VI-52115D R2B-P2-204-02-A-DTI-20043 MEC_52004D VIBRATION SCD mm/s RMS 50 0 8.5 5.3

Sheet 20 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SCD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

VT-52115E VI-52115E R2B-P2-204-02-A-DTI-20043 MEC_52004E VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115F VI-52115F R2B-P2-204-02-A-DTI-20043 MEC_52004F VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115G VI-52115G R2B-P2-204-02-A-DTI-20043 MEC_52004G VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115H VI-52115H R2B-P2-204-02-A-DTI-20043 MEC_52004H VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115I VI-52115I R2B-P2-204-02-A-DTI-20043 MEC_52004I VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52115J VI-52115J R2B-P2-204-02-A-DTI-20043 MEC_52004J VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52117A VI-52117A R2B-P2-204-02-A-DTI-20039 MEC_52008A VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52117B VI-52117B R2B-P2-204-02-A-DTI-20039 MEC_52008B VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52117C VI-52117C R2B-P2-204-02-A-DTI-20039 MEC_52008C VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52117D VI-52117D R2B-P2-204-02-A-DTI-20039 MEC_52008D VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411A VI-52411A R2B-P2-204-02-A-DTI-20050 MEC52005A VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411B VI-52411B R2B-P2-204-02-A-DTI-20050 MEC52005B VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411C VI-52411C R2B-P2-204-02-A-DTI-20050 MEC52005C VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411D VI-52411D R2B-P2-204-02-A-DTI-20050 MEC52005D VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411E VI-52411E R2B-P2-204-02-A-DTI-20050 MEC52005E VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411F VI-52411F R2B-P2-204-02-A-DTI-20050 MEC52005F VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411G VI-52411G R2B-P2-204-02-A-DTI-20050 MEC52005G VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411H VI-52411H R2B-P2-204-02-A-DTI-20050 MEC52005H VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411I VI-52411I R2B-P2-204-02-A-DTI-20050 MEC52005I VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411J VI-52411J R2B-P2-204-02-A-DTI-20050 MEC52005J VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411K VI-52411K R2B-P2-204-02-A-DTI-20050 MEC52005K VIBRATION SCD mm/s RMS 50 0 8.5 5.3
VT-52411L VI-52411L R2B-P2-204-02-A-DTI-20050 MEC52005L VIBRATION SCD mm/s RMS 50 0 8.5 5.3

Sheet 21 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

FT-52901A FI-52901A R2B-P2-204-02-A-DTI-20004 GA52001AB MXD DSL TO EA52002 ESD Sm^3/h 750 0 235.51 224.81
FT-52901B FI-52901B R2B-P2-204-02-A-DTI-20004 GA52001AB MXD DSL TO EA52002 ESD Sm^3/h 750 0 235.51 224.81
FT-52901C FI-52901C R2B-P2-204-02-A-DTI-20004 GA52001AB MXD DSL TO EA52002 ESD Sm^3/h 750 0 235.51 224.81
FT-52903A FI-52903A R2B-P2-204-02-A-DTI-20027A BC52001 H2 TO EA52003 ESD Sm³/h 128000 0 39121 35208.9
FT-52903B FI-52903B R2B-P2-204-02-A-DTI-20027A BC52001 H2 TO EA52003 ESD Sm³/h 128000 0 39121 35208.9
FT-52903C FI-52903C R2B-P2-204-02-A-DTI-20027A BC52001 H2 TO EA52003 ESD Sm³/h 128000 0 39121 35208.9
FT-52904 FI-52904 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 ESD Sm³/h 19000 0 5868.13 5281.31
FT-52905 FI-52905 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 ESD Sm³/h 19000 0 5868.13 5281.31
FT-52906 FI-52906 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 ESD Sm³/h 19000 0 5868.13 5281.31
FT-52907 FI-52907 R2B-P2-204-02-A-DTI-20006 EA52003 RECY H2 TO BA52001 ESD Sm³/h 19000 0 5868.13 5281.31
FT-52908 FI-52908 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 ESD m^3/h 125 0 35.73 32.16
FT-52909 FI-52909 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 ESD m^3/h 125 0 35.73 32.16
FT-52910 FI-52910 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 ESD m^3/h 125 0 35.73 32.16
FT-52911 FI-52911 R2B-P2-204-02-A-DTI-20009 EA52002 MXD DSL TO BA52001 ESD m^3/h 125 0 35.73 32.16
FT-52912A FI-52912A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52912B FI-52912B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52913A FI-52913A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52913B FI-52913B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52914A FI-52914A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52914B FI-52914B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52915A FI-52915A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52915B FI-52915B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52916A FI-52916A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52916B FI-52916B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52917A FI-52917A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52917B FI-52917B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52918A FI-52918A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52918B FI-52918B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52919A FI-52919A R2B-P2-204-02-A-DTI-20055 GA52005AB DSL PROD TO BA52002A ESD Sm³/h 150 0 70.79 67.57
FT-52919B FI-52919B R2B-P2-204-02-A-DTI-20064 GA52005CD DSL PROD TO BA52002B ESD Sm³/h 150 0 70.79 67.57
FT-52920A FI-52920A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 AIR BLWR BMS kg/h 38900 0 6000 4500
FT-52920B FI-52920B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 AIR BLWR BMS kg/h 38900 0 6000 4500
FT-52921 FI-52921 R2B-P2-204-02-A-DTI-20020 GA52002 AML TO DA52001 ESD m^3/h 320 0 75.35 71.93
LT-52900A LI-52900A R2B-P2-204-02-A-DTI-20003 FA52001 FEED DRUM ESD % 100 0 95.5 76.4 23.9 0
LT-52900B LI-52900B R2B-P2-204-02-A-DTI-20003 FA52001 FEED DRUM ESD % 100 0 95.5 76.4 23.9 0
LT-52900C LI-52900C R2B-P2-204-02-A-DTI-20003 FA52001 FEED DRUM ESD % 100 0 95.5 76.4 23.9 0
LT-52901 LI-52901 R2B-P2-204-02-A-DTI-20021 FA52013 RICH AMINE DRUM ESD % 100 0 95.0 76.0 23.8 0
LT-52902A LI-52902A R2B-P2-204-02-A-DTI-20015 FA52002 HP HOT SEPARATOR ESD % 100 0 24.0 0
LT-52902B LI-52902B R2B-P2-204-02-A-DTI-20015 FA52002 HP HOT SEPARATOR ESD % 100 0 24.0 0

Sheet 22 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

LT-52903A LI-52903A R2B-P2-204-02-A-DTI-20022 FA52015 LEAN AMINE DRUM ESD % 100 0 95.0 76.0 23.8 0
LT-52903B LI-52903B R2B-P2-204-02-A-DTI-20022 FA52015 LEAN AMINE DRUM ESD % 100 0 95.0 76.0 23.8 0
LT-52903C LI-52903C R2B-P2-204-02-A-DTI-20022 FA52015 LEAN AMINE DRUM ESD % 100 0 95.0 76.0 23.8 0
LT-52905A LI-52905A R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR ESD % 100 0 23.1 0
LT-52905B LI-52905B R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR ESD % 100 0 23.1 0
LT-52907A LI-52907A R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR ESD % 100 0 23.6 0
LT-52907B LI-52907B R2B-P2-204-02-A-DTI-20019 FA52003 HP COLD SEPARATOR ESD % 100 0 23.6 0
LT-52909A LI-52909A R2B-P2-204-02-A-DTI-20020 DA52001 SCRUBBER ESD % 100 0 22.7 2.9
LT-52909B LI-52909B R2B-P2-204-02-A-DTI-20020 DA52001 SCRUBBER ESD % 100 0 22.7 2.9
LT-52911 LI-52911 R2B-P2-204-02-A-DTI-20024 FA52004 H2 MAKEUP CMPR SUCT DRUM ESD % 100 0 62.5 50.0
LT-52912 LI-52912 R2B-P2-204-02-A-DTI-20026 FA52005A HYDROGEN MAKEUP CMPR ESD % 100 0 92.9 57.1
LT-52915 LI-52915 R2B-P2-204-02-A-DTI-20027 FA52005A HYDROGEN MAKEUP CMPR ESD % 100 0 92.8 56.5
LT-52916 LI-52916 R2B-P2-204-02-A-DTI-20028 FA52005B HYDROGEN MAKEUP CMPR ESD % 100 0 92.9 57.1
LT-52919 LI-52919 R2B-P2-204-02-A-DTI-20030 FA52006B HYDROGEN MAKEUP CMPR ESD % 100 0 92.8
LT-52920 LI-52920 R2B-P2-204-02-A-DTI-20031 FA52005C HYDROGEN MAKEUP CMPR ESD % 100 0 92.9 57.1
LT-52923 LI-52923 R2B-P2-204-02-A-DTI-20033 FA52006C HYDROGEN MAKEUP CMPR ESD % 100 0 92.8 56.5 13.0
LT-52924A LI-52924A R2B-P2-204-02-A-DTI-20034 FA52007 RECYCLE H2 CMPR SUCT DRM ESD % 100 0 20.6 0
LT-52924B LI-52924B R2B-P2-204-02-A-DTI-20034 FA52007 RECYCLE H2 CMPR SUCT DRM ESD % 100 0 20.6 0
LT-52926 LI-52926 R2B-P2-204-02-A-DTI-20034 FA52007 RECYCLE H2 CMPR SUCT DRM ESD % 100 0 82.2 65.8
LT-52928 LI-52928 R2B-P2-204-02-A-DTI-20038 DS52001 STRIPPER ESD % 100 0 95.1
LT-52929 LI-52929 R2B-P2-204-02-A-DTI-20038 DS52001 STRIPPER ESD % 100 0 95.1
LT-52930 LI-52930 R2B-P2-204-02-A-DTI-20041 FA52011 STRIPPER REFLUX DRUM ESD % 100 0 23.0 0
LT-52931 LI-52931 R2B-P2-204-02-A-DTI-20046 DF52001 FRACTIONATOR ESD % 100 0 0
LT-52932 LI-52932 R2B-P2-204-02-A-DTI-20052 FA52010 FRACTIONATOR REFLUX DRUM ESD % 100 0 74.0 23.1 0
LT-52933A LI-52933A R2B-P2-204-02-A-DTI-20071 FA52012 WASH WATER DRUM ESD % 100 0 93.3 74.6 23.4 0
LT-52933B LI-52933B R2B-P2-204-02-A-DTI-20071 FA52012 WASH WATER DRUM ESD % 100 0 93.3 74.6 23.4 0
LT-52933C LI-52933C R2B-P2-204-02-A-DTI-20071 FA52012 WASH WATER DRUM ESD % 100 0 93.3 74.6 23.4 0
LT-52934 LI-52934 R2B-P2-204-02-A-DTI-20018 FA52014 SOUR WATER DRUM ESD % 100 0 0
LT-52935 LI-52935 R2B-P2-204-02-A-DTI-20072 SPE52021 SURFACE COND PKG ESD % 100 0 58.0 31.0 22.0
PDT-52935A PDI-52935A R2B-P2-204-02-A-DTI-20066B DP ACROSS BA52002A_BV03 BMS mmH2O 350 0 50 40
PDT-52935B PDI-52935B R2B-P2-204-02-A-DTI-20068B DP ACROSS BA52002B_BV03 BMS mmH2O 350 0 50 40
PT-52900A PI-52900A R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER BMS mmH2O 50 -50 5 0
PT-52900B PI-52900B R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER BMS mmH2O 50 -50 5 0
PT-52900C PI-52900C R2B-P2-204-02-A-DTI-20009A BA52001 FEED HEATER BMS mmH2O 50 -50 5 0
PT-52901A PI-52901A R2B-P2-204-02-A-DTI-20010 LP NG TO BA52001 BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52901B PI-52901B R2B-P2-204-02-A-DTI-20010 LP NG TO BA52001 BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52901C PI-52901C R2B-P2-204-02-A-DTI-20010 LP NG TO BA52001 BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52902A PI-52902A R2B-P2-204-02-A-DTI-20010 FG TO BA52001 BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52902B PI-52902B R2B-P2-204-02-A-DTI-20010 FG TO BA52001 BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055

Sheet 23 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52902C PI-52902C R2B-P2-204-02-A-DTI-20010 FG TO BA52001 BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52903 PI-52903 R2B-P2-204-02-A-DTI-20022 AML TO FA52015 ESD kg/cm2g 10 0 6.5 6
PT-52904 PI-52904 R2B-P2-204-02-A-DTI-20022 AML TO FA52015 ESD kg/cm2g 10 0 4 3.5
PT-52905 PI-52905 R2B-P2-204-02-A-DTI-20024 FA52004 H2 TO BC52001A1_B1_C1 ESD kg/cm2g 40 0 19.475 18.86
PT-52906 PI-52906 R2B-P2-204-02-A-DTI-20026 FA52005A H2 TO BC52001A2 ESD kg/cm2g 60 0 33.06 32.02
PT-52907 PI-52907 R2B-P2-204-02-A-DTI-20027 FA52006A H2 TO BC52001A3 ESD kg/cm2g 100 0 55.575 53.82
PT-52909 PI-52909 R2B-P2-204-02-A-DTI-20029 FA52005B H2 TO BC52001B2 ESD kg/cm2g 60 0 33.06 32.02
PT-52910 PI-52910 R2B-P2-204-02-A-DTI-20030 FA52006B H2 TO BC52001B3 ESD kg/cm2g 100 0 55.575 53.82
PT-52912 PI-52912 R2B-P2-204-02-A-DTI-20032 FA52005C H2 TO BC52001C2 ESD kg/cm2g 60 0 33.06 32.02
PT-52913 PI-52913 R2B-P2-204-02-A-DTI-20033 FA52006C H2 TO BC52001C3 ESD kg/cm2g 100 0 55.575 53.82
PT-52914 PI-52914 R2B-P2-204-02-A-DTI-20034 FA52007 RECY H2 TO GB52001 ESD kg/cm2g 160 0 70.5 68.5
PT-52915A PI-52915A R2B-P2-204-02-A-DTI-20046 DF52001 SR NPTHA TO EC52005 ESD kg/cm2g 6 0 4.6 4.1
PT-52915B PI-52915B R2B-P2-204-02-A-DTI-20046 DF52001 SR NPTHA TO EC52005 ESD kg/cm2g 6 0 4.6 4.1
PT-52915C PI-52915C R2B-P2-204-02-A-DTI-20046 DF52001 SR NPTHA TO EC52005 ESD kg/cm2g 6 0 4.6 4.1
PT-52916A PI-52916A R2B-P2-204-02-A-DTI-20066A BA52002A FRACTIONATOR REBOILER BMS mmH2O 20 -20 5 0
PT-52916B PI-52916B R2B-P2-204-02-A-DTI-20066A BA52002A FRACTIONATOR REBOILER BMS mmH2O 20 -20 5 0
PT-52916C PI-52916C R2B-P2-204-02-A-DTI-20066A BA52002A FRACTIONATOR REBOILER BMS mmH2O 20 -20 5 0
PT-52917A PI-52917A R2B-P2-204-02-A-DTI-20068A BA52002B FRACTIONATOR REBOILER BMS mmH2O 50 -50 5 0
PT-52917B PI-52917B R2B-P2-204-02-A-DTI-20068A BA52002B FRACTIONATOR REBOILER BMS mmH2O 50 -50 5 0
PT-52917C PI-52917C R2B-P2-204-02-A-DTI-20068A BA52002B FRACTIONATOR REBOILER BMS mmH2O 50 -50 5 0
PT-52918A PI-52918A R2B-P2-204-02-A-DTI-20057 LP NG TO BA52002A BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52918B PI-52918B R2B-P2-204-02-A-DTI-20057 LP NG TO BA52002A BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52918C PI-52918C R2B-P2-204-02-A-DTI-20057 LP NG TO BA52002A BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52919A PI-52919A R2B-P2-204-02-A-DTI-20057 FG TO BA52002A BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52919B PI-52919B R2B-P2-204-02-A-DTI-20057 FG TO BA52002A BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52919C PI-52919C R2B-P2-204-02-A-DTI-20057 FG TO BA52002A BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52920A PI-52920A R2B-P2-204-02-A-DTI-20070 LP NG TO BA52002B BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52920B PI-52920B R2B-P2-204-02-A-DTI-20070 LP NG TO BA52002B BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52920C PI-52920C R2B-P2-204-02-A-DTI-20070 LP NG TO BA52002B BMS kg/cm2g 1.5 0 0.9 0.8 0.6 0.5
PT-52921A PI-52921A R2B-P2-204-02-A-DTI-20070 FG TO BA52002B BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52921B PI-52921B R2B-P2-204-02-A-DTI-20070 FG TO BA52002B BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52921C PI-52921C R2B-P2-204-02-A-DTI-20070 FG TO BA52002B BMS kg/cm2g 2 0 1.65 1.5 0.06 0.055
PT-52922 PI-52922 R2B-P2-204-02-A-DTI-20025 BC52001A1 H2 TO EC52002A ESD kg/cm2g 60 0 37.3 35.9
PT-52922A PI-52922A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52922B PI-52922B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52923 PI-52923 R2B-P2-204-02-A-DTI-20026 BC52001A2 H2 TO EC52003A ESD kg/cm2g 100 0 62.6 60.3
PT-52923A PI-52923A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52923B PI-52923B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52924 PI-52924 R2B-P2-204-02-A-DTI-20028 BC52001B1 TO EC52002B ESD kg/cm2g 60 0 37.3 35.9

Sheet 24 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52924A PI-52924A R2B-P2-204-02-A-DTI-20761 GA52001A LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52924B PI-52924B R2B-P2-204-02-A-DTI-20762 GA52001B LUBE OIL SUPPLY ESD kg/cm2g 3 0 1 0.8
PT-52925A PI-52925A R2B-P2-204-02-A-DTI-20018 FA52003 WS TO FA52014 ESD kg/cm2g 1.3 0 1.23 1.05
PT-52925B PI-52925B R2B-P2-204-02-A-DTI-20018 FA52003 WS TO FA52014 ESD kg/cm2g 1.3 0 1.23 1.05
PT-52926 PI-52926 R2B-P2-204-02-A-DTI-20029 BC52001B2 H2 TO EC52003B ESD kg/cm2g 100 0 62.6 60.3
PT-52927A PI-52927A R2B-P2-204-02-A-DTI-20021 FA52013 SR GAS TO BL ESD kg/cm2g 19 0 12.5 12 10
PT-52927B PI-52927B R2B-P2-204-02-A-DTI-20021 FA52013 SR GAS TO BL ESD kg/cm2g 19 0 12.5 12 10
PT-52929A PI-52929A R2B-P2-204-02-A-DTI-20036 FA52002 HOT DSL TO FA52008 ESD kg/cm2g 21 0 15.9 15.4
PT-52929B PI-52929B R2B-P2-204-02-A-DTI-20036 FA52002 HOT DSL TO FA52008 ESD kg/cm2g 21 0 15.9 15.4
PT-52930 PI-52930 R2B-P2-204-02-A-DTI-20031 BC52001C1 H2 TO EC52002C ESD kg/cm2g 60 0 37.3 35.9
PT-52931A PI-52931A R2B-P2-204-02-A-DTI-20037 FA52003 COLD DSL TO FA52009 ESD kg/cm2g 21 0 15.5 15
PT-52931B PI-52931B R2B-P2-204-02-A-DTI-20037 FA52003 COLD DSL TO FA52009 ESD kg/cm2g 21 0 15.5 15
PT-52932 PI-52932 R2B-P2-204-02-A-DTI-20032 BC52001C2 H2TO EC52003C ESD kg/cm2g 100 0 62.6 60.3
PT-52933A PI-52933A R2B-P2-204-02-A-DTI-20039 DS52001 SR NPTHA TO EC52008 ESD kg/cm2g 21 0 12.9 12.4
PT-52933B PI-52933B R2B-P2-204-02-A-DTI-20039 DS52001 SR NPTHA TO EC52008 ESD kg/cm2g 21 0 12.9 12.4
PT-52933C PI-52933C R2B-P2-204-02-A-DTI-20039 DS52001 SR NPTHA TO EC52008 ESD kg/cm2g 21 0 12.9 12.4
PT-52936A PI-52936A R2B-P2-204-02-A-DTI-20066 CX52001AC AIR BLOWER BMS mmH2O 300 0 30 25
PT-52936B PI-52936B R2B-P2-204-02-A-DTI-20066 CX52001AC AIR BLOWER BMS mmH2O 300 0 30 25
PT-52936C PI-52936C R2B-P2-204-02-A-DTI-20066 CX52001AC AIR BLOWER BMS mmH2O 300 0 30 25
PT-52937A PI-52937A R2B-P2-204-02-A-DTI-20068 BA52002B COLD COMB AIR DUCT BMS mmH2O 300 0 30 25
PT-52937B PI-52937B R2B-P2-204-02-A-DTI-20068 BA52002B COLD COMB AIR DUCT BMS mmH2O 300 0 30 25
PT-52937C PI-52937C R2B-P2-204-02-A-DTI-20068 BA52002B COLD COMB AIR DUCT BMS mmH2O 300 0 30 25
PT-52951 PI-52951 R2B-P2-204-02-A-DTI-20027 BC-52001A-FA06 ESD kg/cm2g 200 0 104.6
PT-52952A PI-52952A R2B-P2-204-02-A-DTI-20702 BC52001A PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52952B PI-52952B R2B-P2-204-02-A-DTI-20702 BC52001A PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52952C PI-52952C R2B-P2-204-02-A-DTI-20702 BC52001A PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52961 PI-52961 R2B-P2-204-02-A-DTI-20030 BC-52001B-FA06 ESD kg/cm2g 200 0 104.6
PT-52962A PI-52962A R2B-P2-204-02-A-DTI-20712 BC52001B PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52962B PI-52962B R2B-P2-204-02-A-DTI-20712 BC52001B PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52962C PI-52962C R2B-P2-204-02-A-DTI-20712 BC52001B PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52971 PI-52971 R2B-P2-204-02-A-DTI-20033 BC-52001C-FA06 ESD kg/cm2g 200 0 104.6
PT-52972A PI-52972A R2B-P2-204-02-A-DTI-20722 BC52001C PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52972B PI-52972B R2B-P2-204-02-A-DTI-20722 BC52001C PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
PT-52972C PI-52972C R2B-P2-204-02-A-DTI-20722 BC52001C PRESS LUB OIL DOWNSTRM ESD kg/cm2g 6 0 1.9
ST-52201A SI-52201A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 FAN SPEED ESD rpm 2000 0 300 250
ST-52201B SI-52201B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 FAN SPEED ESD rpm 2000 0 300 250
ST-52203A SI-52203A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 FAN SPEED ESD rpm 2000 0 300 250
ST-52203B SI-52203B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 FAN SPEED ESD rpm 2000 0 300 250
ST-52205A SI-52205A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 FAN SPEED ESD rpm 2000 0 300 250

Sheet 25 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

ST-52205B SI-52205B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 FAN SPEED ESD rpm 2000 0 300 250
TT-52901A TI-52901A R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901B TI-52901B R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901C TI-52901C R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901D TI-52901D R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901E TI-52901E R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901F TI-52901F R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901G TI-52901G R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901H TI-52901H R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52901I TI-52901I R2B-P2-204-02-A-DTI-20008 DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 345 340
TT-52902A TI-52902A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902B TI-52902B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902C TI-52902C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902D TI-52902D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902E TI-52902E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902F TI-52902F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902G TI-52902G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902H TI-52902H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52902I TI-52902I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 349 344
TT-52904A TI-52904A R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904B TI-52904B R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904C TI-52904C R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904D TI-52904D R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904E TI-52904E R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904F TI-52904F R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904G TI-52904G R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904H TI-52904H R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52904I TI-52904I R2B-P2-204-02-A-DTI-20008A DC52002 2ND HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52906 TI-52906 R2B-P2-204-02-A-DTI-20025 BC52001A1 H2 TO EC52002A ESD °C 150 0 108.675 103.95
TT-52907 TI-52907 R2B-P2-204-02-A-DTI-20026 BC52001A2 H2 TO EC52003A ESD °C 200 0 129.6 124.6
TT-52908 TI-52908 R2B-P2-204-02-A-DTI-20027 BC52001A3 H2 TO EA52003 ESD °C 200 0 130 125
TT-52909 TI-52909 R2B-P2-204-02-A-DTI-20028 BC52001B1 H2 TO EC52002B ESD °C 150 0 108.675 103.95
TT-52910 TI-52910 R2B-P2-204-02-A-DTI-20029 BC52001B2 H2 TO EC52003B ESD °C 200 0 129.6 124.6
TT-52911 TI-52911 R2B-P2-204-02-A-DTI-20030 BC52001B3 H2 TO EA52003 ESD °C 200 0 130 125
TT-52912 TI-52912 R2B-P2-204-02-A-DTI-20031 BC52001C1 H2 TO EC52002C ESD °C 150 0 108.675 103.95
TT-52913 TI-52913 R2B-P2-204-02-A-DTI-20032 BC52001C2 H2 TO EC52003C ESD °C 200 0 129.6 124.6
TT-52914 TI-52914 R2B-P2-204-02-A-DTI-20033 BC52001C3 H2 TO EA52003 ESD °C 200 0 130 125
TT-52915 TI-52915 R2B-P2-204-02-A-DTI-20035 GB52001 RECY H2 TO EC52001 ESD °C 150 0 112.7 107.8
TT-52916A TI-52916A R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328

Sheet 26 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TT-52916B TI-52916B R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916C TI-52916C R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916D TI-52916D R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916E TI-52916E R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916F TI-52916F R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916G TI-52916G R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916H TI-52916H R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916I TI-52916I R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916J TI-52916J R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916K TI-52916K R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52916L TI-52916L R2B-P2-204-02-A-DTI-20007 DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 333 328
TT-52917A TI-52917A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917B TI-52917B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917C TI-52917C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917D TI-52917D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917E TI-52917E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917F TI-52917F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917G TI-52917G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917H TI-52917H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917I TI-52917I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917J TI-52917J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917K TI-52917K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52917L TI-52917L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 343 338
TT-52918A TI-52918A R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918B TI-52918B R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918C TI-52918C R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918D TI-52918D R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918E TI-52918E R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918F TI-52918F R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918G TI-52918G R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918H TI-52918H R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918I TI-52918I R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918J TI-52918J R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918K TI-52918K R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52918L TI-52918L R2B-P2-204-02-A-DTI-20007A DC52001 1ST HYDROTREAT REACTOR ESD °C 450 50 353 348
TT-52919A TI-52919A R2B-P2-204-02-A-DTI-20007A DC52001 DSL H2 TO DC52002 ESD °C 600 0 353
TT-52919B TI-52919B R2B-P2-204-02-A-DTI-20008A DC52002 EFFL TO EA52005AB ESD °C 600 0 353
TT-52920 TI-52920 R2B-P2-204-02-A-DTI-20009A BA52001 DSL H2 TO DC52001 ESD °C 600 0 314.2
TT-52951 TI-52951 R2B-P2-204-02-A-DTI-20025 BC-52001A 1ST STG OUTL ESD °C 190 0 118

Sheet 27 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (ESD) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TT-52952 TI-52952 R2B-P2-204-02-A-DTI-20026 BC-52001A 2ND STG OUTL ESD °C 230 0 140
TT-52953 TI-52953 R2B-P2-204-02-A-DTI-20027 BC-52001A 3RD STG OUTL ESD °C 230 0 141
TT-52961 TI-52961 R2B-P2-204-02-A-DTI-20028 BC-52001B 1ST STG OUTL ESD °C 190 0 118
TT-52962 TI-52962 R2B-P2-204-02-A-DTI-20029 BC-52001B 2ND STG OUTL ESD °C 230 0 140
TT-52963 TI-52963 R2B-P2-204-02-A-DTI-20030 BC-52001B 3RD STG OUTL ESD °C 230 0 141
TT-52971 TI-52971 R2B-P2-204-02-A-DTI-20031 BC-52001C 1ST STG OUTL ESD °C 190 0 118
TT-52972 TI-52972 R2B-P2-204-02-A-DTI-20032 BC-52001C 2ND STG OUTL ESD °C 230 0 140
TT-52973 TI-52973 R2B-P2-204-02-A-DTI-20033 BC-52001C 3RD STG OUTL ESD °C 230 0 141
VT-52101A VI-52101A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52101B VI-52101B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52103A VI-52103A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52103B VI-52103B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52104A VI-52104A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52104B VI-52104B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52105A VI-52105A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52105B VI-52105B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 DE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52106A VI-52106A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52106B VI-52106B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52107A VI-52107A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0
VT-52107B VI-52107B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 NDE BEARING VIB ESD mm/s 25.4 0 11.0 6.0

Sheet 28 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SFG) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

DF-52801 DF-52801 R2B-P2-204-02-P-PL-20805 Hydrogen Replacement Compressor SFG mA 20 0 20 16


DF-52802 DF-52802 R2B-P2-204-02-P-PL-20805 Hydrogen Replacement Compressor SFG mA 20 0 20 16
DF-52803 DF-52803 R2B-P2-204-02-P-PL-20805 Hydrogen Replacement Compressor SFG mA 20 0 20 16
DF-52804 DF-52804 R2B-P2-204-02-P-PL-20805 Hydrogen Replacement Compressor SFG mA 20 0 20 16
DF-52805 DF-52805 R2B-P2-204-02-P-PL-20805 Recycle Hydrogen Compressor SFG mA 20 0 20 16
DF-52806 DF-52806 R2B-P2-204-02-P-PL-20805 Recycle Hydrogen Compressor SFG mA 20 0 20 16
DF-52807 DF-52807 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52808 DF-52808 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52809 DF-52809 R2B-P2-204-02-P-PL-20806 Stripper Reflux Pumps SFG mA 20 0 20 16
DF-52810 DF-52810 R2B-P2-204-02-P-PL-20806 Steam Generator SFG mA 20 0 20 16
DF-52811 DF-52811 R2B-P2-204-02-P-PL-20806 First Diesel Separator, Second Diesel Separator SFG mA 20 0 20 16
DF-52812 DF-52812 R2B-P2-204-02-P-PL-20806 Steam Generator SFG mA 20 0 20 16
DF-52813 DF-52813 R2B-P2-204-02-P-PL-20806 Feed Fractionator Bottoms Exchanger SFG mA 20 0 20 16
DF-52814 DF-52814 R2B-P2-204-02-P-PL-20806 Feed Fractionator Bottoms Exchanger SFG mA 20 0 20 16
DF-52815 DF-52815 R2B-P2-204-02-P-PL-20806 Fractionator Reflux Drum SFG mA 20 0 20 16
DF-52816 DF-52816 R2B-P2-204-02-P-PL-20806 Fractionator Reflux Drum SFG mA 20 0 20 16
DF-52817 DF-52817 R2B-P2-204-02-P-PL-20806 Fractionator Reflux Pumps, Diesel Product Pumps SFG mA 20 0 20 16
DF-52818 DF-52818 R2B-P2-204-02-P-PL-20806 Fractionator Reboilerrecirculation Pumps SFG mA 20 0 20 16
DF-52819 DF-52819 R2B-P2-204-02-P-PL-20807 Reactor Effluent_Hydrogen Exchanger SFG mA 20 0 20 16
DF-52820 DF-52820 R2B-P2-204-02-P-PL-20807 Reactor Effluent_Hydrogen Exchanger SFG mA 20 0 20 16
DF-52821 DF-52821 R2B-P2-204-02-P-PL-20807 Cold Feed Coalescer SFG mA 20 0 20 16
DF-52822 DF-52822 R2B-P2-204-02-P-PL-20805 Slop Oil Air Cooler SFG mA 20 0 20 16
DF-52823 DF-52823 R2B-P2-204-02-P-PL-20805 Slop Oil Air Cooler SFG mA 20 0 20 16
DF-52824 DF-52824 R2B-P2-204-02-P-PL-20807 High Pressure Lean Amine Pumps SFG mA 20 0 20 16
DF-52825 DF-52825 R2B-P2-204-02-P-PL-20806 High Pressure Hot Separator Vaporcooler SFG mA 20 0 20 16
DF-52826 DF-52826 R2B-P2-204-02-P-PL-20807 High Pressure Lean Amine Pumps SFG mA 20 0 20 16
DF-52827 DF-52827 R2B-P2-204-02-P-PL-20806 High Pressure Hot Separator Vaporcooler SFG mA 20 0 20 16
DF-52828 DF-52828 R2B-P2-204-02-P-PL-20806 High Pressure Hot Separator Vaporcooler SFG mA 20 0 20 16
DF-52829 DF-52829 R2B-P2-204-02-P-PL-20806 Stripper Reflux Pumps SFG mA 20 0 20 16
DF-52830 DF-52830 R2B-P2-204-02-P-PL-20806 High Pressure Hot Separator Vaporcooler SFG mA 20 0 20 16
DF-52831 DF-52831 R2B-P2-204-02-P-PL-20806 First Diesel Separator, Second Diesel Separator SFG mA 20 0 20 16
DF-52832 DF-52832 R2B-P2-204-02-P-PL-20806 Stripper First Condenser/ Final Gas Cooler SFG mA 20 0 20 16
DF-52833 DF-52833 R2B-P2-204-02-P-PL-20808 High Pressure Hot Separator SFG mA 20 0 20 16
DF-52834 DF-52834 R2B-P2-204-02-P-PL-20806 Stripper First Condenser/ Final Gas Cooler SFG mA 20 0 20 16
DF-52835 DF-52835 R2B-P2-204-02-P-PL-20806 Diesel Product Cooler SFG mA 20 0 20 16
DF-52836 DF-52836 R2B-P2-204-02-P-PL-20808 Feed Pumps SFG mA 20 0 20 16
DF-52837 DF-52837 R2B-P2-204-02-P-PL-20806 Fractionator Reflux Pumps, Diesel Product Pumps SFG mA 20 0 20 16
DF-52838 DF-52838 R2B-P2-204-02-P-PL-20808 Feed Pumps SFG mA 20 0 20 16
DF-52839 DF-52839 R2B-P2-204-02-P-PL-20806 Diesel Product Cooler SFG mA 20 0 20 16

Sheet 29 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SFG) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

DF-52840 DF-52840 R2B-P2-204-02-P-PL-20806 Fractionator Condenser SFG mA 20 0 20 16


DF-52841 DF-52841 R2B-P2-204-02-P-PL-20806 Fractionator Condenser SFG mA 20 0 20 16
DF-52842 DF-52842 R2B-P2-204-02-P-PL-20806 Fractionator Reboilerrecirculation Pumps SFG mA 20 0 20 16
DF-52843 DF-52843 R2B-P2-204-02-P-PL-20807 Cold Feed Coalescer SFG mA 20 0 20 16
DF-52844 DF-52844 R2B-P2-204-02-P-PL-20808 Feed / Diesel Product Exchanger SFG mA 20 0 20 16
DF-52845 DF-52845 R2B-P2-204-02-P-PL-20808 High Pressure Hot Separator SFG mA 20 0 20 16
DF-52846 DF-52846 R2B-P2-204-02-P-PL-20807 Feed / Diesel Product Exchanger SFG mA 20 0 20 16
DF-52847 DF-52847 R2B-P2-204-02-P-PL-20808 Feed Drum SFG mA 20 0 20 16
DF-52848 DF-52848 R2B-P2-204-02-P-PL-20808 Feed Drum SFG mA 20 0 20 16
DF-52849 DF-52849 R2B-P2-204-02-P-PL-20808 Feed / Reactor Effluent First Exchanger SFG mA 20 0 20 16
DF-52850 DF-52850 R2B-P2-204-02-P-PL-20808 Feed / Reactor Effluent First Exchanger SFG mA 20 0 20 16
DF-52851 DF-52851 R2B-P2-204-02-P-PL-20808 Reactor Effluent_Hydrogen Exchanger SFG mA 20 0 20 16
DF-52852 DF-52852 R2B-P2-204-02-P-PL-20808 Reactor Effluent_Hydrogen Exchanger SFG mA 20 0 20 16
DF-52853 DF-52853 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52854 DF-52854 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52855 DF-52855 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52856 DF-52856 R2B-P2-204-02-P-PL-20805 Lube Oil Console SFG mA 20 0 20 16
DF-52857 DF-52857 R2B-P2-204-02-P-PL-20806 Slop Drain Drum SFG mA 20 0 20 16
DF-52858 DF-52858 R2B-P2-204-02-P-PL-20806 Amine Drain Drum SFG mA 20 0 20 16
DF-52859 DF-52859 R2B-P2-204-02-P-PL-20806 Hddi1-Par-007 Grade Area SFG mA 20 0 20 16
DF-52860 DF-52860 R2B-P2-204-02-P-PL-20806 Hddi1-Par-007 Grade Area SFG mA 20 0 20 16
DG-52801 DG-52801 R2B-P2-204-02-P-PL-20802 Stripper Reflux Pumps SFG %LEL 100 0 40 20
DG-52802 DG-52802 R2B-P2-204-02-P-PL-20802 Stripper SFG %LEL 100 0 40 20
DG-52803 DG-52803 R2B-P2-204-02-P-PL-20802 Stripper SFG %LEL 100 0 40 20
DG-52804 DG-52804 R2B-P2-204-02-P-PL-20802 First Diesel Separator SFG %LEL 100 0 40 20
DG-52805 DG-52805 R2B-P2-204-02-P-PL-20802 Steam Generator Preheater SFG %LEL 100 0 40 20
DG-52806 DG-52806 R2B-P2-204-02-P-PL-20802 Feed Fractionator Bottoms Exchanger SFG %LEL 100 0 40 20
DG-52807 DG-52807 R2B-P2-204-02-P-PL-20802 Naphtha Cooler SFG %LEL 100 0 40 20
DG-52808 DG-52808 R2B-P2-204-02-P-PL-20802 Fractionator Reflux Drum SFG %LEL 100 0 40 20
DG-52809 DG-52809 R2B-P2-204-02-P-PL-20802 Fractionator Reflux Pumps SFG %LEL 100 0 40 20
DG-52810 DG-52810 R2B-P2-204-02-P-PL-20802 Diesel Product Pumps SFG %LEL 100 0 40 20
DG-52811 DG-52811 R2B-P2-204-02-P-PL-20802 Fractionator Reboilerrecirculation Pumps SFG %LEL 100 0 40 20
DG-52812 DG-52812 R2B-P2-204-02-P-PL-20802 Fractionator Reboilerrecirculation Pumps SFG %LEL 100 0 40 20
DG-52813 DG-52813 R2B-P2-204-02-P-PL-20802 Fractionator SFG %LEL 100 0 40 20
DG-52814 DG-52814 R2B-P2-204-02-P-PL-20802 Fractionator SFG %LEL 100 0 40 20
DG-52815 DG-52815 R2B-P2-204-02-P-PL-20802 Fuel Gas Knockout Drum SFG %LEL 100 0 40 20
DG-52816 DG-52816 R2B-P2-204-02-P-PL-20802 Stripper Second Condenser SFG %LEL 100 0 40 20
DG-52817 DG-52817 R2B-P2-204-02-P-PL-20802 Steam Generator SFG %LEL 100 0 40 20
DG-52818 DG-52818 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20

Sheet 30 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SFG) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

DG-52819 DG-52819 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20


DG-52820 DG-52820 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52821 DG-52821 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52822 DG-52822 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52823 DG-52823 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52824 DG-52824 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52825 DG-52825 R2B-P2-204-02-P-PL-20802 Fractionator Reboiler SFG %LEL 100 0 40 20
DG-52826 DG-52826 R2B-P2-204-02-P-PL-20804 Fuel Gas Filter For Heaters SFG %LEL 100 0 40 20
DG-52827 DG-52827 R2B-P2-204-02-P-PL-20804 Feed / Diesel Product Exchanger SFG %LEL 100 0 40 20
DG-52828 DG-52828 R2B-P2-204-02-P-PL-20804 Feed Drum SFG %LEL 100 0 40 20
DG-52829 DG-52829 R2B-P2-204-02-P-PL-20804 Feed Pumps SFG %LEL 100 0 40 20
DG-52830 DG-52830 R2B-P2-204-02-P-PL-20804 Feed Pumps SFG %LEL 100 0 40 20
DG-52831 DG-52831 R2B-P2-204-02-P-PL-20803 High Pressure Cold Separator SFG %LEL 100 0 40 20
DG-52832 DG-52832 R2B-P2-204-02-P-PL-20803 Feed Filter SFG %LEL 100 0 40 20
DG-52833 DG-52833 R2B-P2-204-02-P-PL-20803 Feed Filter SFG %LEL 100 0 40 20
DG-52834 DG-52834 R2B-P2-204-02-P-PL-20803 Cold Feed Coalescer SFG %LEL 100 0 40 20
DG-52835 DG-52835 R2B-P2-204-02-P-PL-20801 Slop Oil Air Cooler SFG %LEL 100 0 40 20
DG-52836 DG-52836 R2B-P2-204-02-P-PL-20802 Final Gas Cooler / Stripper First Condenser SFG %LEL 100 0 40 20
DG-52837 DG-52837 R2B-P2-204-02-P-PL-20802 Diesel Product Cooler SFG %LEL 100 0 40 20
DG-52838 DG-52838 R2B-P2-204-02-P-PL-20802 Diesel Product Cooler SFG %LEL 100 0 40 20
DG-52839 DG-52839 R2B-P2-204-02-P-PL-20802 Fractionator Condenser SFG %LEL 100 0 40 20
DG-52840 DG-52840 R2B-P2-204-02-P-PL-20802 Fractionator Condenser SFG %LEL 100 0 40 20
DGC-52801R DGC-52801R R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor SFG LEL.M 5 0 2 1
DGC-52802R DGC-52802R R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor SFG LEL.M 5 0 2 1
DH-52801 DH-52801 R2B-P2-204-02-P-PL-20801 BC-52001A HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DH-52802 DH-52802 R2B-P2-204-02-P-PL-20801 BC-52001B HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DH-52803 DH-52803 R2B-P2-204-02-P-PL-20801 BC-52001C HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DH-52804 DH-52804 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor Suction K.O.Drum SFG %LEL 100 0 40 20
DH-52805 DH-52805 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor Suction K.O.Drum SFG %LEL 100 0 40 20
DH-52806 DH-52806 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52807 DH-52807 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52808 DH-52808 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52809 DH-52809 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor Suction K.O.Drum SFG %LEL 100 0 40 20
DH-52810 DH-52810 R2B-P2-204-02-P-PL-20804 BA-52001 FEED HEATER SFG %LEL 100 0 40 20
DH-52811 DH-52811 R2B-P2-204-02-P-PL-20804 BA-52001 FEED HEATER SFG %LEL 100 0 40 20
DH-52812 DH-52812 R2B-P2-204-02-P-PL-20804 BA-52001 FEED HEATER SFG %LEL 100 0 40 20
DH-52813 DH-52813 R2B-P2-204-02-P-PL-20804 BA-52001 FEED HEATER SFG %LEL 100 0 40 20
DH-52814 DH-52814 R2B-P2-204-02-P-PL-20804 FA-52002 HIGH PRESSURE HOT SEPARATOR SFG %LEL 100 0 40 20
DH-52815 DH-52815 R2B-P2-204-02-P-PL-20804 FA-52002 HIGH PRESSURE HOT SEPARATOR SFG %LEL 100 0 40 20

Sheet 31 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SFG) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

DH-52816 DH-52816 R2B-P2-204-02-P-PL-20804 DC-52001 FIRST HYDROTREATING REACTOR SFG %LEL 100 0 40 20
DH-52817 DH-52817 R2B-P2-204-02-P-PL-20804 DC-52001 FIRST HYDROTREATING REACTOR SFG %LEL 100 0 40 20
DH-52818 DH-52818 R2B-P2-204-02-P-PL-20804 DC-52002 SECOND HYDROTREATING REACTOR SFG %LEL 100 0 40 20
DH-52819 DH-52819 R2B-P2-204-02-P-PL-20804 DC-52002 SECOND HYDROTREATING REACTOR SFG %LEL 100 0 40 20
DH-52820 DH-52820 R2B-P2-204-02-P-PL-20804 Feed / Reactor Effluent First Exchanger SFG %LEL 100 0 40 20
DH-52821 DH-52821 R2B-P2-204-02-P-PL-20804 EA-52003A/B REACTOR EFFLUENT/ HYDROGEN EX SFG %LEL 100 0 40 20
DH-52822 DH-52822 R2B-P2-204-02-P-PL-20804 Feed / Reactor Effluent Second Exchanger SFG %LEL 100 0 40 20
DH-52823 DH-52823 R2B-P2-204-02-P-PL-20803 DA-52001 SCRUBBER SFG %LEL 100 0 40 20
DH-52824 DH-52824 R2B-P2-204-02-P-PL-20803 DA-52001 SCRUBBER SFG %LEL 100 0 40 20
DH-52825 DH-52825 R2B-P2-204-02-P-PL-20801 GB-52001 RECYCLE HYDROGEN COMPRESSOR SFG %LEL 100 0 40 20
DH-52826 DH-52826 R2B-P2-204-02-P-PL-20801 Note 7 SFG %LEL 100 0 40 20
DH-52827 DH-52827 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor Spillback Cooler SFG %LEL 100 0 40 20
DH-52828 DH-52828 R2B-P2-204-02-P-PL-20802 EC-52001 HIGH PRESSURE HOT SEPARATOR VAPO SFG %LEL 100 0 40 20
DH-52829 DH-52829 R2B-P2-204-02-P-PL-20802 EC-52001 HIGH PRESSURE HOT SEPARATOR VAPO SFG %LEL 100 0 40 20
DH-52830 DH-52830 R2B-P2-204-02-P-PL-20802 EC-52001 HIGH PRESSURE HOT SEPARATOR VAPO SFG %LEL 100 0 40 20
DH-52831 DH-52831 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52832 DH-52832 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52833 DH-52833 R2B-P2-204-02-P-PL-20801 Hydrogen Make-Up Compressor First Stageseparator SFG %LEL 100 0 40 20
DH-52834 DH-52834 R2B-P2-204-02-P-PL-20801 BC-52001A HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DH-52835 DH-52835 R2B-P2-204-02-P-PL-20801 BC-52001B HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DH-52836 DH-52836 R2B-P2-204-02-P-PL-20801 BC-52001C HYDROGEN REPLACEMENT COMPRESS SFG %LEL 100 0 40 20
DHS-52801 DHS-52801 R2B-P2-204-02-P-PL-20802 Stripper Reflux Drum SFG ppm 100 0 20 5
DHS-52802 DHS-52802 R2B-P2-204-02-P-PL-20802 Amine Drain Drum SFG ppm 100 0 20 5
DHS-52803 DHS-52803 R2B-P2-204-02-P-PL-20802 Amine Drain Drum SFG ppm 100 0 20 5
DHS-52804 DHS-52804 R2B-P2-204-02-P-PL-20802 Slop Drain Drum SFG ppm 100 0 20 5
DHS-52805 DHS-52805 R2B-P2-204-02-P-PL-20802 Slop Drain Drum SFG ppm 100 0 20 5
DHS-52806 DHS-52806 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52807 DHS-52807 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52808 DHS-52808 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52809 DHS-52809 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52810 DHS-52810 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52811 DHS-52811 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52812 DHS-52812 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52813 DHS-52813 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52814 DHS-52814 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52815 DHS-52815 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor SFG ppm 100 0 20 5
DHS-52816 DHS-52816 R2B-P2-204-02-P-PL-20803 Note 6 SFG ppm 100 0 20 5
DHS-52817 DHS-52817 R2B-P2-204-02-P-PL-20803 Low Pressure Flare Knockoutdrum Pumps SFG ppm 100 0 20 5
DHS-52818 DHS-52818 R2B-P2-204-02-P-PL-20803 High Pressure Flare Knockoutdrum Pumps SFG ppm 100 0 20 5

Sheet 32 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (SFG) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

DHS-52819 DHS-52819 R2B-P2-204-02-P-PL-20803 High Pressure Lean Amine Pumps SFG ppm 100 0 20 5
DHS-52820 DHS-52820 R2B-P2-204-02-P-PL-20803 Sour Water Pumps SFG ppm 100 0 20 5
DHS-52821 DHS-52821 R2B-P2-204-02-P-PL-20803 Recovered Hydrocarbon Pumps SFG ppm 100 0 20 5
DHS-52822 DHS-52822 R2B-P2-204-02-P-PL-20803 Lean Amine Drum SFG ppm 100 0 20 5
DHS-52823 DHS-52823 R2B-P2-204-02-P-PL-20803 Sour Water Drum SFG ppm 100 0 20 5
DHS-52824 DHS-52824 R2B-P2-204-02-P-PL-20802 Stripper SFG ppm 100 0 20 5
DHS-52825 DHS-52825 R2B-P2-204-02-P-PL-20802 Stripper SFG ppm 100 0 20 5
DHS-52826 DHS-52826 R2B-P2-204-02-P-PL-20803 Scrubber SFG ppm 100 0 20 5
DHS-52827 DHS-52827 R2B-P2-204-02-P-PL-20803 Scrubber SFG ppm 100 0 20 5
DHS-52828 DHS-52828 R2B-P2-204-02-P-PL-20804 Second Hydrotreating Reactor SFG ppm 100 0 20 5
DHS-52829 DHS-52829 R2B-P2-204-02-P-PL-20804 Second Hydrotreating Reactor SFG ppm 100 0 20 5
DHS-52830 DHS-52830 R2B-P2-204-02-P-PL-20804 High Pressure Hot Separator SFG ppm 100 0 20 5
DHS-52831 DHS-52831 R2B-P2-204-02-P-PL-20804 High Pressure Hot Separator SFG ppm 100 0 20 5
DHS-52832 DHS-52832 R2B-P2-204-02-P-PL-20803 High Pressure Cold Separator SFG ppm 100 0 20 5
DHS-52833 DHS-52833 R2B-P2-204-02-P-PL-20801 Recycle Hydrogen Compressor Suction K.O.Drum SFG ppm 100 0 20 5
DHS-52834 DHS-52834 R2B-P2-204-02-P-PL-20802 First Diesel Separator SFG ppm 100 0 20 5
DHS-52835 DHS-52835 R2B-P2-204-02-P-PL-20804 Feed / Reactor Effluent First Exchanger SFG ppm 100 0 20 5
DHS-52836 DHS-52836 R2B-P2-204-02-P-PL-20804 Reactor Effluent/ Hydrogen Exchanger SFG ppm 100 0 20 5
DHS-52837 DHS-52837 R2B-P2-204-02-P-PL-20802 Stripper Second Condenser SFG ppm 100 0 20 5
DHS-52838 DHS-52838 R2B-P2-204-02-P-PL-20804 Feed / Reactor Effluent Second Exchanger SFG ppm 100 0 20 5
DHS-52839 DHS-52839 R2B-P2-204-02-P-PL-20802 Note 6 SFG ppm 100 0 20 5
DHS-52840 DHS-52840 R2B-P2-204-02-P-PL-20802 Note 6 SFG ppm 100 0 20 5
DHS-52841 DHS-52841 R2B-P2-204-02-P-PL-20802 Stripper First Condenser SFG ppm 100 0 20 5
DHS-52842 DHS-52842 R2B-P2-204-02-P-PL-20802 Stripper First Condenser SFG ppm 100 0 20 5
DHS-52843 DHS-52843 R2B-P2-204-02-P-PL-20802 Stripper Reflux Pumps SFG ppm 100 0 20 5
DHS-52844 DHS-52844 R2B-P2-204-02-P-PL-20802 Second Diesel Separator SFG ppm 100 0 20 5
DHS-52845 DHS-52845 R2B-P2-204-02-P-PL-20803 Note 6 SFG ppm 100 0 20 5
DHS-52846 DHS-52846 R2B-P2-204-02-P-PL-20803 Rich Amine Drum SFG ppm 100 0 20 5
DHS-52847 DHS-52847 R2B-P2-204-02-P-PL-20803 LOW PRESSURE FLARE KNOCKOUTDRUM PUMPS SFG ppm 100 0 20 5
DHS-52848 DHS-52848 R2B-P2-204-02-P-PL-20803 HIGH PRESSURE LEAN AMINE PUMPS SFG ppm 100 0 20 5

Sheet 33 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

AT-52520 AI-52520 R2B-P2-204-02-A-DTI-20244A Breathing Air Conditioning Package Outlet PLC °C 20 -110 -54
AT-52521 AI-52521 R2B-P2-204-02-A-DTI-20244A Breathing Air Conditioning Package Outlet PLC ppm 2000 0 1000
AT-52522 AI-52522 R2B-P2-204-02-A-DTI-20244A Breathing Air Conditioning Package Outlet PLC ppm 50 0 10
AT-52523 AI-52523 R2B-P2-204-02-A-DTI-20244A Breathing Air Conditioning Package Outlet PLC ppm 25 0 15
LT-52560 LI-52560 R2B-P2-204-02-A-DTI-20001A CONDENSATE POT FG-52001-FA08 PLC % 100 0 70
LT-52601 LI-52601 R2B-P2-204-02-A-DTI-20751 LUBE OIL TANK PLC % 100 0 15.14 1.25
LT-52620 LI-52620 R2B-P2-204-02-A-DTI-20754 RUN DOWN TANK PLC % 100 0 33.45
PDT-52520 PDI-52520 R2B-P2-204-02-A-DTI-20244A WATER AND PARTICLE REMOVING FILTER PLC kg/cm2 0.5 0 0.2
PDT-52521 PDI-52521 R2B-P2-204-02-A-DTI-20244A OIL REMOVING FILTER PLC kg/cm2 0.5 0 0.2
PDT-52522 PDI-52522 R2B-P2-204-02-A-DTI-20244A ABSORBING FILTER PLC kg/cm2 0.5 0 0.2
PDT-52523 PDI-52523 R2B-P2-204-02-A-DTI-20244A FINE PARTICLE FILTER PLC kg/cm2 0.5 0 0.2
PDT-52569 PDI-52569 R2B-P2-204-02-A-DTI-20001A FEED INLET OUTLET PLC kg/cm2 1.5 0 1.2
PDT-52608 PDI-52608 R2B-P2-204-02-A-DTI-20751 GB52001FG01AB LUBE OIL FILTER DP PLC kg/cm2 2 0 1.5
PDT-52644 PDI-52644 R2B-P2-204-02-A-DTI-20758 GB52001FG03AB N2 FILTER DP PLC kg/cm2 2 0 1.5
PDT-52647 PDI-52647 R2B-P2-204-02-A-DTI-20759 GB52001FG02AB SEAL GAS FILTER DP PLC kg/cm2 2 0 1
PDT-52648 PDI-52648 R2B-P2-204-02-A-DTI-20759 GB52001BC01 SEAL GAS BOOSTER DP PLC kg/cm2 2 0 0.05
PT-52524 PI-52524 R2B-P2-204-02-A-DTI-20244A A DRYING TOWER PLC kg/cm2g 10 0 2.5 6.5
PT-52525 PI-52525 R2B-P2-204-02-A-DTI-20244A B DRYING TOWER PLC kg/cm2g 10 0 2.5 6.5
PT-52526 PI-52526 R2B-P2-204-02-A-DTI-20244A Breathing Air Conditioning Package Outlet PLC kg/cm2g 10 0 6.5
PT-52606 PI-52606 R2B-P2-204-02-A-DTI-20751 LO PUMPS HEADER UPSTRM COOLERS PLC kg/cm2g 16 0 10.5
PT-52607A PI-52607A R2B-P2-204-02-A-DTI-20760 CMPR DISCH SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52607B PI-52607B R2B-P2-204-02-A-DTI-20760 CMPR DISCH SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52607C PI-52607C R2B-P2-204-02-A-DTI-20760 CMPR DISCH SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52609A PI-52609A R2B-P2-204-02-A-DTI-20760 CMPR SUCT SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52609B PI-52609B R2B-P2-204-02-A-DTI-20760 CMPR SUCT SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52609C PI-52609C R2B-P2-204-02-A-DTI-20760 CMPR SUCT SIDE SEAL CHAMB PLC kg/cm2g 20 0 15 10
PT-52617 PI-52617 R2B-P2-204-02-A-DTI-20754 CONTROL OIL HEADER PLC kg/cm2g 16 0 6.5
PT-52620A PI-52620A R2B-P2-204-02-A-DTI-20754 LUBE OIL HEADER PLC kg/cm2g 6 0 1.6 1.2
PT-52620B PI-52620B R2B-P2-204-02-A-DTI-20754 LUBE OIL HEADER PLC kg/cm2g 6 0 1.6 1.2
PT-52620C PI-52620C R2B-P2-204-02-A-DTI-20754 LUBE OIL HEADER PLC kg/cm2g 6 0 1.6 1.2
PT-52620D PI-52620D R2B-P2-204-02-A-DTI-20754 LUBE OIL HEADER PLC kg/cm2g 6 0 1.6 1.2
PT-52621A PI-52621A R2B-P2-204-02-A-DTI-20755 STM TURB TRIP OIL LINE PLC kg/cm2g 16 0 2.5
PT-52621B PI-52621B R2B-P2-204-02-A-DTI-20755 STM TURB TRIP OIL LINE PLC kg/cm2g 16 0 2.5
PT-52621C PI-52621C R2B-P2-204-02-A-DTI-20755 STM TURB TRIP OIL LINE PLC kg/cm2g 16 0 2.5
PT-52634 PI-52634 R2B-P2-204-02-A-DTI-20756 STM TO TURB SEALS FEEDING LINE PLC kg/cm2a 4 0 1
PT-52636 PI-52636 R2B-P2-204-02-A-DTI-20757 CMPR 2NDRY SEAL GAS HEADER PLC kg/cm2g 10 0 6 3
PT-52639 PI-52639 R2B-P2-204-02-A-DTI-20757 CMPR BALANCING DRUM PLC kg/cm2g 100 0 3
PT-52642A PI-52642A R2B-P2-204-02-A-DTI-20757 CMPR DISCH END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1
PT-52642B PI-52642B R2B-P2-204-02-A-DTI-20757 CMPR DISCH END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1

Sheet 34 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PT-52642C PI-52642C R2B-P2-204-02-A-DTI-20757 CMPR DISCH END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1
PT-52643A PI-52643A R2B-P2-204-02-A-DTI-20757 CMPR SUCT END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1
PT-52643B PI-52643B R2B-P2-204-02-A-DTI-20757 CMPR SUCT END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1
PT-52643C PI-52643C R2B-P2-204-02-A-DTI-20757 CMPR SUCT END PRIMARY VENT PLC kg/cm2g 6 0 3.5 0.2 0.1
PT-52646A PI-52646A R2B-P2-204-02-A-DTI-20758 CMPR SEPARATION GAS HEADER PLC kg/cm2g 16 0 1.1
PT-52646B PI-52646B R2B-P2-204-02-A-DTI-20758 CMPR SEPARATION GAS HEADER PLC kg/cm2g 16 0 1.1
PT-52646C PI-52646C R2B-P2-204-02-A-DTI-20758 CMPR SEPARATION GAS HEADER PLC kg/cm2g 16 0 1.1
PT-52646D PI-52646D R2B-P2-204-02-A-DTI-20758 CMPR SEPARATION GAS HEADER PLC kg/cm2g 16 0 5.5 2
SE-52625A SI-52625A R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB GOVERNER SDS rpm 14500 0 1138
SE-52625B SI-52625B R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB GOVERNER SDS rpm 14500 0 1138
ST-52626A SI-52626A R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB OVER SPEED ODS rpm 14500 0 12521 11952
ST-52626B SI-52626B R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB OVER SPEED ODS rpm 14500 0 12521 11952
ST-52626C SI-52626C R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB OVER SPEED ODS rpm 14500 0 12521 11952
TE-52335A TI-52335A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 DE BEARING TEMP MMS °C 150 0 100 82
TE-52335B TI-52335B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 DE BEARING TEMP MMS °C 150 0 100 82
TE-52336A TI-52336A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52336B TI-52336B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52343A TI-52343A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 DE BEARING TEMP MMS °C 150 0 100 82
TE-52343B TI-52343B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 DE BEARING TEMP MMS °C 150 0 100 82
TE-52345A TI-52345A R2B-P2-204-02-A-DTI-20066 BA52002A_BV01 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52345B TI-52345B R2B-P2-204-02-A-DTI-20068 BA52002B_BV01 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52347A TI-52347A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 DE BEARING TEMP MMS °C 150 0 100 82
TE-52347B TI-52347B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 DE BEARING TEMP MMS °C 150 0 100 82
TE-52348A TI-52348A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52348B TI-52348B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52355A TI-52355A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 DE BEARING TEMP MMS °C 150 0 100 82
TE-52355B TI-52355B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 DE BEARING TEMP MMS °C 150 0 100 82
TE-52357A TI-52357A R2B-P2-204-02-A-DTI-20066 BA52002A_BV02 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52357B TI-52357B R2B-P2-204-02-A-DTI-20068 BA52002B_BV02 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52359A TI-52359A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 DE BEARING TEMP MMS °C 150 0 100 82
TE-52359B TI-52359B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 DE BEARING TEMP MMS °C 150 0 100 82
TE-52360A TI-52360A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52360B TI-52360B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52367A TI-52367A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 DE BEARING TEMP MMS °C 150 0 100 82
TE-52367B TI-52367B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 DE BEARING TEMP MMS °C 150 0 100 82
TE-52369A TI-52369A R2B-P2-204-02-A-DTI-20066B BA52002A_BV03 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52369B TI-52369B R2B-P2-204-02-A-DTI-20068B BA52002B_BV03 NDE BEARING TEMP MMS °C 150 0 100 82
TE-52464A TI-52464A R2B-P2-204-02-A-DTI-20708 BC52001A TEMP MAIN DRIVE BRG MMS °C 150 0 105 95
TE-52464B TI-52464B R2B-P2-204-02-A-DTI-20708 BC52001A TEMP MAIN DRIVE BRG MMS °C 150 0 105 95

Sheet 35 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52480 TI-52480 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP BRG4_DE MMS °C 100 0 85 70


TE-52481 TI-52481 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP BRG2 MMS °C 100 0 85 70
TE-52482 TI-52482 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP BRG3 MMS °C 100 0 85 70
TE-52483 TI-52483 R2B-P2-204-02-A-DTI-20708 BC52001A TEMP BRG1_NDE MMS °C 100 0 85 70
TE-52511A TI-52511A R2B-P2-204-02-A-DTI-20791 GA52001A PUMP DE BRG TEMP MMS °C 350 0 100 95
TE-52511B TI-52511B R2B-P2-204-02-A-DTI-20791 GA52001A PUMP DE BRG TEMP MMS °C 350 0 100 95
TE-52512A TI-52512A R2B-P2-204-02-A-DTI-20791 GA52001A PUMP NDE BRG TEMP MMS °C 350 0 100 95
TE-52512B TI-52512B R2B-P2-204-02-A-DTI-20791 GA52001A PUMP NDE BRG TEMP MMS °C 350 0 100 95
TE-52513A TI-52513A R2B-P2-204-02-A-DTI-20791 GA52001A PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52513B TI-52513B R2B-P2-204-02-A-DTI-20791 GA52001A PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52513C TI-52513C R2B-P2-204-02-A-DTI-20791 GA52001A PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52513D TI-52513D R2B-P2-204-02-A-DTI-20791 GA52001A PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52514A TI-52514A R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR DE BRG TEMP MMS °C 200 0 98 93
TE-52514B TI-52514B R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR DE BRG TEMP MMS °C 200 0 98 93
TE-52516A TI-52516A R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR NDE BRG TEMP MMS °C 200 0 98 93
TE-52516B TI-52516B R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR NDE BRG TEMP MMS °C 200 0 98 93
TT-52520 TI-52520 R2B-P2-204-02-A-DTI-20244A A DRYING TOWER PLC °C 100 0 50
TT-52521 TI-52521 R2B-P2-204-02-A-DTI-20244A B DRYING TOWER PLC °C 100 0 50
TE-52521A TI-52521A R2B-P2-204-02-A-DTI-20791 GA52001B PUMP DE BRG TEMP MMS °C 350 0 100 95
TE-52521B TI-52521B R2B-P2-204-02-A-DTI-20791 GA52001B PUMP DE BRG TEMP MMS °C 350 0 100 95
TT-52522 TI-52522 R2B-P2-204-02-A-DTI-20244A SPE52007 AIR DRYER OUTLET PLC °C 100 0 50
TE-52522A TI-52522A R2B-P2-204-02-A-DTI-20791 GA52001B PUMP NDE BRG TEMP MMS °C 350 0 100 95
TE-52522B TI-52522B R2B-P2-204-02-A-DTI-20791 GA52001B PUMP NDE BRG TEMP MMS °C 350 0 100 95
TE-52523A TI-52523A R2B-P2-204-02-A-DTI-20791 GA52001B PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52523B TI-52523B R2B-P2-204-02-A-DTI-20791 GA52001B PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52523C TI-52523C R2B-P2-204-02-A-DTI-20791 GA52001B PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52523D TI-52523D R2B-P2-204-02-A-DTI-20791 GA52001B PUMP THRUST BRG TEMP MMS °C 350 0 100 95
TE-52524A TI-52524A R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR DE BRG TEMP MMS °C 200 0 98 93
TE-52524B TI-52524B R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR DE BRG TEMP MMS °C 200 0 98 93
TE-52526A TI-52526A R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR NDE BRG TEMP MMS °C 200 0 98 93
TE-52526B TI-52526B R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR NDE BRG TEMP MMS °C 200 0 98 93
TE-52531A TI-52531A R2B-P2-204-02-A-DTI-20792 GA-52002A_BRG TEMP DE MMS °C 200 0 98 93
TE-52531B TI-52531B R2B-P2-204-02-A-DTI-20792 GA-52002A_BRG TEMP DE MMS °C 200 0 98 93
TE-52532A TI-52532A R2B-P2-204-02-A-DTI-20792 GA-52002A_BRG TEMP NDE MMS °C 200 0 98 93
TE-52532B TI-52532B R2B-P2-204-02-A-DTI-20792 GA-52002A_BRG TEMP NDE MMS °C 200 0 98 93
TE-52536A TI-52536A R2B-P2-204-02-A-DTI-20792 GA-52002B_BRG TEMP DE MMS °C 200 0 98 93
TE-52536B TI-52536B R2B-P2-204-02-A-DTI-20792 GA-52002B_BRG TEMP DE MMS °C 200 0 98 93
TE-52537A TI-52537A R2B-P2-204-02-A-DTI-20792 GA-52002B_BRG TEMP NDE MMS °C 200 0 98 93
TE-52537B TI-52537B R2B-P2-204-02-A-DTI-20792 GA-52002B_BRG TEMP NDE MMS °C 200 0 98 93

Sheet 36 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52541A TI-52541A R2B-P2-204-02-A-DTI-20792 GA-52004A_BRG TEMP DE MMS °C 200 0 98 93


TE-52541B TI-52541B R2B-P2-204-02-A-DTI-20792 GA-52004A_BRG TEMP DE MMS °C 200 0 98 93
TE-52542A TI-52542A R2B-P2-204-02-A-DTI-20792 GA-52004A_BRG TEMP NDE MMS °C 200 0 98 93
TE-52542B TI-52542B R2B-P2-204-02-A-DTI-20792 GA-52004A_BRG TEMP NDE MMS °C 200 0 98 93
TE-52546A TI-52546A R2B-P2-204-02-A-DTI-20792 GA-52004B_BRG TEMP DE MMS °C 200 0 98 93
TE-52546B TI-52546B R2B-P2-204-02-A-DTI-20792 GA-52004B_BRG TEMP DE MMS °C 200 0 98 93
TE-52547A TI-52547A R2B-P2-204-02-A-DTI-20792 GA-52004B_BRG TEMP NDE MMS °C 200 0 98 93
TE-52547B TI-52547B R2B-P2-204-02-A-DTI-20792 GA-52004B_BRG TEMP NDE MMS °C 200 0 98 93
TE-52564A TI-52564A R2B-P2-204-02-A-DTI-20718 BC52001B TEMP MAIN DRIVE BRG MMS °C 150 0 105 95
TE-52564B TI-52564B R2B-P2-204-02-A-DTI-20718 BC52001B TEMP MAIN DRIVE BRG MMS °C 150 0 105 95
TE-52580 TI-52580 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP BRG4_DE MMS °C 100 0 85 70
TE-52581 TI-52581 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP BRG2 MMS °C 100 0 85 70
TE-52582 TI-52582 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP BRG3 MMS °C 100 0 85 70
TE-52583 TI-52583 R2B-P2-204-02-A-DTI-20718 BC52001B TEMP BRG1_NDE MMS °C 100 0 85 70
TT-52602 TI-52602 R2B-P2-204-02-A-DTI-20751 GB52001FB01 LUBE OIL TANK PLC °C 160 0 40 35 25
TT-52606 TI-52606 R2B-P2-204-02-A-DTI-20751 LUBE OIL HEADER DOWNSTRM COOLER PLC °C 160 0 60 35
TE-52620A TI-52620A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG NDE MMS °C 160 0 110
TE-52621A TI-52621A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG NDE MMS °C 160 0 110
TE-52622A TI-52622A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG DE MMS °C 160 0 110
TE-52623A TI-52623A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG DE MMS °C 160 0 110
TE-52624A TI-52624A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG MMS °C 160 0 110
TE-52625A TI-52625A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG MMS °C 160 0 110
TE-52626A TI-52626A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG MMS °C 160 0 110
TE-52627A TI-52627A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG MMS °C 160 0 110
TE-52632A TI-52632A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG MMS °C 160 0 110
TE-52633A TI-52633A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG MMS °C 160 0 110
TE-52634A TI-52634A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG MMS °C 160 0 110
TE-52635A TI-52635A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG MMS °C 160 0 110
TE-52636A TI-52636A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG DE MMS °C 160 0 125 115
TE-52637A TI-52637A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG DE MMS °C 160 0 125 115
TE-52638A TI-52638A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG NDE MMS °C 160 0 125 115
TE-52639A TI-52639A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG NDE MMS °C 160 0 125 115
TT-52644A TI-52644A R2B-P2-204-02-A-DTI-20756 TGB52001 TURB EXHAUST CASING PLC °C 200 0 180 150
TT-52644B TI-52644B R2B-P2-204-02-A-DTI-20756 TGB52001 TURB EXHAUST CASING PLC °C 200 0 180 150
TT-52644C TI-52644C R2B-P2-204-02-A-DTI-20756 TGB52001 TURB EXHAUST CASING PLC °C 200 0 180 150
TT-52645 TI-52645 R2B-P2-204-02-A-DTI-20759 CMPR SEAL GAS BOOSTER PLC °C 200 0 195 185
TE-52646A TI-52646A R2B-P2-204-02-A-DTI-20759 SEAL GAS ELECTRIC HEATER CUT OFF PLC °C 200 0 195
TE-52646B TI-52646B R2B-P2-204-02-A-DTI-20759 SEAL GAS ELECTRIC HEATER CUT OFF PLC °C 200 0 195
TE-52647A TI-52647A R2B-P2-204-02-A-DTI-20759 SEAL GAS ELECTRIC HEATER CONTROL PLC °C 200 0 185 150

Sheet 37 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

TE-52647B TI-52647B R2B-P2-204-02-A-DTI-20759 SEAL GAS ELECTRIC HEATER CONTROL PLC °C 200 0 185 150
TE-52647C TI-52647C R2B-P2-204-02-A-DTI-20759 SEAL GAS ELECTRIC HEATER CONTROL PLC °C 200 0 185 150
TT-52647D TI-52647D R2B-P2-204-02-A-DTI-20759 CMPR SEAL GAS INLET PLC °C 200 0 110
TE-52664A TI-52664A R2B-P2-204-02-A-DTI-20728 BC52001C TEMP MAIN DRIVE BRG MMS °C 150 0 105 95
TE-52664B TI-52664B R2B-P2-204-02-A-DTI-20728 BC52001C TEMP MAIN DRIVE BRG MMS °C 150 0 105 95
TE-52680 TI-52680 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP BRG4_DE MMS °C 100 0 85 70
TE-52681 TI-52681 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP BRG2 MMS °C 100 0 85 70
TE-52682 TI-52682 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP BRG3 MMS °C 100 0 85 70
TE-52683 TI-52683 R2B-P2-204-02-A-DTI-20728 BC52001C TEMP BRG1_NDE MMS °C 100 0 85 70
TE-52801 TI-52801 R2B-P2-204-02-A-DTI-20072B GA-52021A_BRG TEMP NDE MMS °C 200 0 120 110
TE-52802 TI-52802 R2B-P2-204-02-A-DTI-20072B GA-52021A_BRG TEMP NDE MMS °C 200 0 120 110
TE-52811A TI-52811A R2B-P2-204-02-A-DTI-20792 GA-52005A_BRG TEMP DE MMS °C 200 0 100 95
TE-52811B TI-52811B R2B-P2-204-02-A-DTI-20792 GA-52005A_BRG TEMP DE MMS °C 200 0 100 95
TE-52812A TI-52812A R2B-P2-204-02-A-DTI-20792 GA-52005A_BRG TEMP NDE MMS °C 200 0 100 95
TE-52812B TI-52812B R2B-P2-204-02-A-DTI-20792 GA-52005A_BRG TEMP NDE MMS °C 200 0 100 95
TE-52816A TI-52816A R2B-P2-204-02-A-DTI-20792 GA-52005B_BRG TEMP DE MMS °C 200 0 100 95
TE-52816B TI-52816B R2B-P2-204-02-A-DTI-20792 GA-52005B_BRG TEMP DE MMS °C 200 0 100 95
TE-52817A TI-52817A R2B-P2-204-02-A-DTI-20792 GA-52005B_BRG TEMP DE MMS °C 200 0 100 95
TE-52817B TI-52817B R2B-P2-204-02-A-DTI-20792 GA-52005B_BRG TEMP DE MMS °C 200 0 100 95
TE-52821A TI-52821A R2B-P2-204-02-A-DTI-20792 GA-52005C_BRG TEMP DE MMS °C 200 0 100 95
TE-52821B TI-52821B R2B-P2-204-02-A-DTI-20792 GA-52005C_BRG TEMP DE MMS °C 200 0 100 95
TE-52822A TI-52822A R2B-P2-204-02-A-DTI-20792 GA-52005C_BRG TEMP NDE MMS °C 200 0 100 95
TE-52822B TI-52822B R2B-P2-204-02-A-DTI-20792 GA-52005C_BRG TEMP NDE MMS °C 200 0 100 95
TE-52826A TI-52826A R2B-P2-204-02-A-DTI-20792 GA-52005D_BRG TEMP DE MMS °C 200 0 100 95
TE-52826B TI-52826B R2B-P2-204-02-A-DTI-20792 GA-52005D_BRG TEMP DE MMS °C 200 0 100 95
TE-52827A TI-52827A R2B-P2-204-02-A-DTI-20792 GA-52005D_BRG TEMP NDE MMS °C 200 0 100 95
TE-52827B TI-52827B R2B-P2-204-02-A-DTI-20792 GA-52005D_BRG TEMP NDE MMS °C 200 0 100 95
TE-52831A TI-52831A R2B-P2-204-02-A-DTI-20792 GA-52008A_BRG TEMP DE MMS °C 200 0 100 95
TE-52831B TI-52831B R2B-P2-204-02-A-DTI-20792 GA-52008A_BRG TEMP DE MMS °C 200 0 100 95
TE-52832A TI-52832A R2B-P2-204-02-A-DTI-20792 GA-52008A_BRG TEMP NDE MMS °C 200 0 100 95
TE-52832B TI-52832B R2B-P2-204-02-A-DTI-20792 GA-52008A_BRG TEMP NDE MMS °C 200 0 100 95
TE-52836A TI-52836A R2B-P2-204-02-A-DTI-20792 GA-52008B_BRG TEMP DE MMS °C 200 0 100 95
TE-52836B TI-52836B R2B-P2-204-02-A-DTI-20792 GA-52008B_BRG TEMP DE MMS °C 200 0 100 95
TE-52837A TI-52837A R2B-P2-204-02-A-DTI-20792 GA-52008B_BRG TEMP NDE MMS °C 200 0 100 95
TE-52837B TI-52837B R2B-P2-204-02-A-DTI-20792 GA-52008B_BRG TEMP NDE MMS °C 200 0 100 95
VE-52450A VI-52450A R2B-P2-204-02-A-DTI-20708 BC52001A VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5
VE-52450B VI-52450B R2B-P2-204-02-A-DTI-20708 BC52001A VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5
VE-52451A VI-52451A R2B-P2-204-02-A-DTI-20708 BC52001A VIB FRAME MMS mm/s pk 63 0 13 10
VE-52451B VI-52451B R2B-P2-204-02-A-DTI-20708 BC52001A VIB FRAME MMS mm/s pk 63 0 13 10

Sheet 38 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

VE-52452 VI-52452 R2B-P2-204-02-A-DTI-20708 BC52001A VIB FRAME MMS mm/s pk 63 0 13 10


VT-52511X VI-52511X R2B-P2-204-02-A-DTI-20791 GA52001A PUMP DE RADIAL VIB MMS µm 200 0 160 100
VT-52511Y VI-52511Y R2B-P2-204-02-A-DTI-20791 GA52001A PUMP DE RADIAL VIB MMS µm 200 0 160 100
VT-52512X VI-52512X R2B-P2-204-02-A-DTI-20791 GA52001A PUMP NDE RADIAL VIB MMS µm 200 0 160 100
VT-52512Y VI-52512Y R2B-P2-204-02-A-DTI-20791 GA52001A PUMP NDE RADIAL VIB MMS µm 200 0 160 100
VT-52513A VI-52513A R2B-P2-204-02-A-DTI-20791 GA52001A PUMP AXIAL DISPLACEMENT MMS mm 1 -1 0.8 0.5 -0.5 -0.8
VT-52513B VI-52513B R2B-P2-204-02-A-DTI-20791 GA52001A PUMP AXIAL DISPLACEMENT MMS mm 1 -1 0.8 0.5 -0.5 -0.8
VT-52514X VI-52514X R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR DE RADIAL VIB MMS µm 400 0 185 150
VT-52514Y VI-52514Y R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR DE RADIAL VIB MMS µm 400 0 185 150
VT-52515X VI-52515X R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR NDE RADIAL VIB MMS µm 400 0 185 150
VT-52515Y VI-52515Y R2B-P2-204-02-A-DTI-20791 GA52001A MOTOR NDE RADIAL VIB MMS µm 400 0 185 150
VT-52521X VI-52521X R2B-P2-204-02-A-DTI-20791 GA52001B PUMP DE RADIAL VIB MMS µm 200 0 160 100
VT-52521Y VI-52521Y R2B-P2-204-02-A-DTI-20791 GA52001B PUMP DE RADIAL VIB MMS µm 200 0 160 100
VT-52522X VI-52522X R2B-P2-204-02-A-DTI-20791 GA52001B PUMP NDE RADIAL VIB MMS µm 200 0 160 100
VT-52522Y VI-52522Y R2B-P2-204-02-A-DTI-20791 GA52001B PUMP NDE RADIAL VIB MMS µm 200 0 160 100
VT-52523A VI-52523A R2B-P2-204-02-A-DTI-20791 GA52001B PUMP AXIAL DISPLACEMENT MMS mm 1 -1 0.8 0.5 -0.5 -0.8
VT-52523B VI-52523B R2B-P2-204-02-A-DTI-20791 GA52001B PUMP AXIAL DISPLACEMENT MMS mm 1 -1 0.8 0.5 -0.5 -0.8
VT-52524X VI-52524X R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR DE RADIAL VIB MMS µm 400 0 185 150
VT-52524Y VI-52524Y R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR DE RADIAL VIB MMS µm 400 0 185 150
VT-52525X VI-52525X R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR NDE RADIAL VIB MMS µm 400 0 185 150
VT-52525Y VI-52525Y R2B-P2-204-02-A-DTI-20791 GA52001B MOTOR NDE RADIAL VIB MMS µm 400 0 185 150
VE-52550A VI-52550A R2B-P2-204-02-A-DTI-20718 BC52001B VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5
VE-52550B VI-52550B R2B-P2-204-02-A-DTI-20718 BC52001B VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5
VE-52551A VI-52551A R2B-P2-204-02-A-DTI-20718 BC52001B VIB FRAME MMS mm/s pk 63 0 13 10
VE-52551B VI-52551B R2B-P2-204-02-A-DTI-20718 BC52001B VIB FRAME MMS mm/s pk 63 0 13 10
VE-52552 VI-52552 R2B-P2-204-02-A-DTI-20718 BC52001B VIB FRAME MMS mm/s pk 63 0 13 10
VT-52619A VI-52619A R2B-P2-204-02-A-DTI-20754 TGB52001 TURB SHAFT AXIAL VIB MMS mm 1 -1 0.55 0.35 -0.35 -0.55
VT-52619B VI-52619B R2B-P2-204-02-A-DTI-20754 TGB52001 TURB SHAFT AXIAL VIB MMS mm 1 -1 0.55 0.35 -0.35 -0.55
VT-52620X VI-52620X R2B-P2-204-02-A-DTI-20754 GB52001 TURB SHAFT RADIAL VIB DE MMS µm 200 0 85 65
VT-52620Y VI-52620Y R2B-P2-204-02-A-DTI-20754 GB52001 TURB SHAFT RADIAL VIB DE MMS µm 200 0 85 65
VT-52621X VI-52621X R2B-P2-204-02-A-DTI-20754 GB52001 TURB RADIAL VIB DE MMS µm 200 0 85 65
VT-52621Y VI-52621Y R2B-P2-204-02-A-DTI-20754 GB52001 TURB RADIAL VIB DE MMS µm 200 0 85 65
VT-52632X VI-52632X R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT X RADIAL VIB MMS µm 200 0 70 50
VT-52632Y VI-52632Y R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT Y RADIAL VIB MMS µm 200 0 70 50
VT-52634X VI-52634X R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT X RADIAL VIB MMS µm 200 0 70 50
VT-52634Y VI-52634Y R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT Y RADIAL VIB MMS µm 200 0 70 50
VT-52636A VI-52636A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT AXIAL VIB MMS mm 1 -1 0.75 0.55 -0.55 -0.75
VT-52636B VI-52636B R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT AXIAL VIB MMS mm 1 -1 0.75 0.55 -0.55 -0.75
VE-52650A VI-52650A R2B-P2-204-02-A-DTI-20728 BC52001C VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5

Sheet 39 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

VE-52650B VI-52650B R2B-P2-204-02-A-DTI-20728 BC52001C VIB MAIN DRIVE BRG MMS mm/s pk 63 0 4.5
VE-52651A VI-52651A R2B-P2-204-02-A-DTI-20728 BC52001C VIB FRAME MMS mm/s pk 63 0 13 10
VE-52651B VI-52651B R2B-P2-204-02-A-DTI-20728 BC52001C VIB FRAME MMS mm/s pk 63 0 13 10
VE-52652 VI-52652 R2B-P2-204-02-A-DTI-20728 BC52001C VIB FRAME MMS mm/s pk 63 0 13 10
VT-52801A VI-52801A R2B-P2-204-02-A-DTI-20072B TGA-52021A_RADIAL VIB NDE MMS µm 250 0 147 92
VT-52801B VI-52801B R2B-P2-204-02-A-DTI-20072B TGA-52021A_RADIAL VIB NDE MMS µm 250 0 147 92
VT-52802A VI-52802A R2B-P2-204-02-A-DTI-20072B TGA-52021A_RADIAL VIB DE MMS µm 250 0 147 92
VT-52802B VI-52802B R2B-P2-204-02-A-DTI-20072B TGA-52021A_RADIAL VIB DE MMS µm 250 0 147 92
ZT-52450 ZI-52450 R2B-P2-204-02-A-DTI-20708 BC52001A ROD DROP STG1 MMS mm 4.5 0.5 0.7
ZT-52451 ZI-52451 R2B-P2-204-02-A-DTI-20708 BC52001A ROD DROP STG2 MMS mm 4.5 0.5 0.7
ZT-52452 ZI-52452 R2B-P2-204-02-A-DTI-20708 BC52001A ROD DROP STG3 MMS mm 4.5 0.5 0.7
ZT-52550 ZI-52550 R2B-P2-204-02-A-DTI-20718 BC52001B ROD DROP STG1 MMS mm 4.5 0.5 0.7
ZT-52551 ZI-52551 R2B-P2-204-02-A-DTI-20718 BC52001B ROD DROP STG2 MMS mm 4.5 0.5 0.7
ZT-52552 ZI-52552 R2B-P2-204-02-A-DTI-20718 BC52001B ROD DROP STG3 MMS mm 4.5 0.5 0.7
ZT-52630 ZI-52630 R2B-P2-204-02-A-DTI-20759 CMPR SEAL GAS BOOSTER VLV PLC % 100 0 95 5
ZT-52638 ZI-52638 R2B-P2-204-02-A-DTI-20759 CMPR SEAL GAS INLET VLV PLC % 100 0 15
ZT-52650 ZI-52650 R2B-P2-204-02-A-DTI-20728 BC52001C ROD DROP STG1 MMS mm 4.5 0.5 0.7
ZT-52651 ZI-52651 R2B-P2-204-02-A-DTI-20728 BC52001C ROD DROP STG2 MMS mm 4.5 0.5 0.7
ZT-52652 ZI-52652 R2B-P2-204-02-A-DTI-20728 BC52001C ROD DROP STG3 MMS mm 4.5 0.5 0.7
TE-52647D TI-52647D R2B-P2-204-02-A-DTI-20759 CMPR SEAL GAS INLET PLC °C 200 0 110
TT-52641 TI-52641 R2B-P2-204-02-A-DTI-20756 STM TO TURB SEALS FEEDING LINE PLC °C 300 0 210
PT-52641 PI-52641 R2B-P2-204-02-A-DTI-20756 STM TO TURB SEALS FEEDING LINE PLC kg/cm² G 18 0 10
PDT-52164 PDI-52164 R2B-P2-204-02-A-DTI-20035 FA52007 RECY H2 TO GB52001 PLC kg/cm² 2.5 0 2 1.5
FT-52638B FI-52638B R2B-P2-204-02-A-DTI-20757 CMPR SUCT END SEAL GAS INLET PLC Am³/h 33 0 2.9 1.3
FT-52638A FI-52638A R2B-P2-204-02-A-DTI-20757 CMPR DISCH END SEAL GAS INLET PLC Am³/h 33 0 2.9 1.3
FT-52641B FI-52641B R2B-P2-204-02-A-DTI-20757 CMPR SUCT END PRIMARY VENT PLC Nm³/h 17 0 15.2 1.5
FT-52641A FI-52641A R2B-P2-204-02-A-DTI-20757 CMPR DISCH END PRIMARY VENT PLC Nm³/h 17 0 15.2 1.5
TI-52647 TI-52647 R2B-P2-204-02-A-DTI-20759 SEAL GAS ELEC HEATER CUT OFF PLC °C 200 0 185 150
TT-52640A TI-52640A R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC °C 450 0 400 395 350
TT-52640B TI-52640B R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC °C 450 0 400 395 350
TT-52640C TI-52640C R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC °C 450 0 400 395 350
PT-52635A PI-52635A R2B-P2-204-02-A-DTI-20756 TGB52001 STMCD TO SPE52021EA1 PLC kg/cm² A 1 0 0.8 0.6
PT-52635B PI-52635B R2B-P2-204-02-A-DTI-20756 TGB52001 STMCD TO SPE52021EA1 PLC kg/cm² A 1 0 0.8 0.6
PT-52635C PI-52635C R2B-P2-204-02-A-DTI-20756 TGB52001 STMCD TO SPE52021EA1 PLC kg/cm² A 1 0 0.8 0.6
PT-52640A PI-52640A R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC kg/cm² G 60 0 49.5 48.5
PT-52640B PI-52640B R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC kg/cm² G 60 0 49.5 48.5
PT-52640C PI-52640C R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC kg/cm² G 60 0 49.5 48.5
TI-52644 TI-52644 R2B-P2-204-02-A-DTI-20756 TGB52001 TURB EXHAUST CASING PLC °C 200 0 180 150
TI-52640 TI-52640 R2B-P2-204-02-A-DTI-20035 HP STM TO TGB51001 PLC °C 450 0 400 395 350

Sheet 40 of 41
PHASE II OF REFINERY IN DOS BOCAS (HDDI)
ContractNo PTI-ID-O-003-3-2020 Doc. No R2B-P2-204-02-P-LST-20002
ContractorJob.No. SO6625
ALARM SET POINT LIST (PLC) Rev. 3
Tag Number Tag Number
P&ID Service System Engineering Unit Range Max Range Min Alarm HH Alarm H Alarm L Alarm LL Remark
(Sensing Element) (HMI Indication)

PI-52643 PI-52643 R2B-P2-204-02-A-DTI-20757 CMPR SUCT END PRIMARY VENT PLC kg/cm² G 6 0 3.5 0.2 0.1
PI-52642 PI-52642 R2B-P2-204-02-A-DTI-20757 CMPR DISCH END PRIMARY VENT PLC kg/cm² G 6 0 3.5 0.2 0.1
PI-52609 PI-52609 R2B-P2-204-02-A-DTI-20760 CMPR SUCT SIDE SEAL CHAMB PLC kg/cm² G 20 0 15 10
PI-52607 PI-52607 R2B-P2-204-02-A-DTI-20760 CMPR DISCH SIDE SEAL CHAMB PLC kg/cm² G 20 0 15 10
PI-52646 PI-52646 R2B-P2-204-02-A-DTI-20758 CMPR SEPARATION GAS HEADER PLC kg/cm² G 16 0 1.1
PI-52621 PI-52621 R2B-P2-204-02-A-DTI-20755 STM TURB TRIP OIL LINE PLC kg/cm² G 16 0 2.5
PI-52620 PI-52620 R2B-P2-204-02-A-DTI-20754 LUBE OIL HEADER PLC kg/cm² G 16 0 1.6 1.2
PI-52635 PI-52635 R2B-P2-204-02-A-DTI-20756 STM TURB EXHAUST HEADER PLC kg/cm² A 1 0 0.8 0.6
PI-52640 PI-52640 R2B-P2-204-02-A-DTI-20035 HP STM TO TGB52001 PLC kg/cm² G 60 0 49.5 48.5
TE-52632A TI-52632A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG PLC °C 160 0 110
TE-52633A TI-52633A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG PLC °C 160 0 110
TE-52634A TI-52634A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG PLC °C 160 0 110
TE-52635A TI-52635A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR JOURNAL BRG PLC °C 160 0 110
TE-52636A TI-52636A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG DE PLC °C 160 0 125 115
TE-52637A TI-52637A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG DE PLC °C 160 0 125 115
TE-52638A TI-52638A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG NDE PLC °C 160 0 125 115
TE-52639A TI-52639A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR THRUST BRG NDE PLC °C 160 0 125 115
TE-52624A TI-52624A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG PLC °C 160 0 110
TE-52625A TI-52625A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG PLC °C 160 0 110
TE-52626A TI-52626A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG PLC °C 160 0 110
TE-52627A TI-52627A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB JOURNAL BRG PLC °C 160 0 110
TE-52620A TI-52620A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG NDE PLC °C 160 0 110
TE-52621A TI-52621A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG NDE PLC °C 160 0 110
TE-52622A TI-52622A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG DE PLC °C 160 0 110
TE-52623A TI-52623A R2B-P2-204-02-A-DTI-20754 TGB52001 STM TURB THRUST BRG DE PLC °C 160 0 110
VT-52632X VI-52632X R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT X RADIAL VIB PLC µm 200 0 70 50
VT-52632Y VI-52632Y R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT Y RADIAL VIB PLC µm 200 0 70 50
VT-52634X VI-52634X R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT X RADIAL VIB PLC µm 200 0 70 50
VT-52634Y VI-52634Y R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT Y RADIAL VIB PLC µm 200 0 70 50
VT-52620X VI-52620X R2B-P2-204-02-A-DTI-20754 GB52001 TURB SHAFT RADIAL VIB DE PLC µm 200 0 85 65
VT-52620Y VI-52620Y R2B-P2-204-02-A-DTI-20754 GB52001 TURB SHAFT RADIAL VIB DE PLC µm 200 0 85 65
VT-52621X VI-52621X R2B-P2-204-02-A-DTI-20754 GB52001 TURB RADIAL VIB DE PLC µm 200 0 85 65
VT-52621Y VI-52621Y R2B-P2-204-02-A-DTI-20754 GB52001 TURB RADIAL VIB DE PLC µm 200 0 85 65
ST-52627A SI-52627A R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB ZERO SPEED PLC rpm 14500 0 0
ST-52627B SI-52627B R2B-P2-204-02-A-DTI-20755 TGB52001 STM TURB ZERO SPEED PLC rpm 14500 0 0
VT-52636A VI-52636A R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT AXIAL VIB PLC mm 1 -1 0.75 0.55 -0.55 -0.75
VT-52636B VI-52636B R2B-P2-204-02-A-DTI-20754 GB52001 CMPR SHAFT AXIAL VIB PLC mm 1 -1 0.75 0.55 -0.55 -0.75
VT-52619A VI-52619A R2B-P2-204-02-A-DTI-20754 TGB52001 TURB SHAFT AXIAL VIB PLC mm 1 -1 0.55 0.35 -0.35 -0.55
VT-52619B VI-52619B R2B-P2-204-02-A-DTI-20754 TGB52001 TURB SHAFT AXIAL VIB PLC mm 1 -1 0.55 0.35 -0.35 -0.55

Sheet 41 of 41