SAMSUNG

ENGINEERING CO., LTD

Received
15 Mar 2023
DOCUMENT TITLE: Hazardous Area Equipment List & Certificates

PTI-ID V/P NO : R2B-P2-204-03-P-CER-KAR701-5-5-01013


SECL V/P NO : SO6627-KAR701-5-5-01-K0CER001-001
REQUISITION NO : KAR701-5-5
PURCHASE ORDER NO : 5000071282-0
ITEM DESCRIPTION : Document

□ APPROVED □ WITH COMMENT


□ REVIEWED □ RESUBMIT

This approval or review does not relieve the vendor /


subcontractor of his responsibilities to meet all
requirements of the purchase order

ORIGINAL CHECKED APPD(PRJ)

SIGN

DATE
SAMSUNG ENGINEERING CO., LTD

D 2023-3-14 Issued for Approval Jenny Zhou Felix Deng Felix Deng
C 2022-6-9 Issued for Approval Jenny Zhou Felix Deng Felix Deng
B 2022-5-9 Issued for Approval Jenny Zhou Felix Deng Felix Deng
A 2022-2-21 Issued for Approval Jenny Zhou Felix Deng Felix Deng
REV DATE DESCRIPTION PREPARED CHECKED APPROVED

Dos Bocas New Refinery Project

PTI-Infraestructura de Desarrollo, S.A. de C.V. (PTI-ID)

SAMSUNG Ingeniería Manzanillo, S.A. de C.V.

ABB Engineering (Shanghai) LTD

Page 1 of 3
 
ABB Engineering (Shanghai) Ltd.

Document Title: Hazardous Area Equipment List & Certificates


Dos Bocas New Refinery
Project Name: PO Number: 5000071282-0 Approved: Felix
Project

PTI-Infraestructura de Customer R2B-P2-204-03-P-CER-KAR701-


Customer Name: Date: 2023-3-14
Desarrollo, S.A. de C.V. Doc. No: 5-5-01013

Project Number: AUS-4498-00239 ABB Doc. No: AUS-4498-00239-002-013 Revision: D

Hazardous Area Equipment List & Certificates


Index of Equipment

BOM Item Manufacturer Equipment Description Certification Type Certificate No.

Total Sulfur Analyzer


AN001 Hobre Class 1 Division 2 Group B,C,D T3 LR1643-2
Part No: C-Quand
Total Sulfur Analyzer
AN002 Thermo Fisher Class 1 Division 1 Group B,C,D T4 70169008
Part No: SOLA IQ Trace
CO Analyzer
AN003 ABB Class 1 Division 2 Group B,C,D T4 1105720
Part No: AO2040 Uras26
Hydrogen Analyzer
AN005 ABB Class 1 Division 2 Group B,C,D T4 1105720
Part No: AO2040 Caldos25
Oxygen Analyzer
AN006A Emerson Class 1 Division 1 Group B,C,D T4 RAD 1124 Rev. B
Part No: 5081FG
Level Switch
LS301
Emerson Part No: Class 1 Division 1 Group A, B,C,D T6 FM20US0047
LS302
2120D1GV1E5YH0000Q8
SRS Control Panel 20190805-
CP101 Appleton Class 1 Division 2 Group B,C,D T3
Part No: ACSEW E10449
Electrical Cooler & Pump
EC10101 Buhler Part No: Class 1 Division 2 Group A,B,C,D T4 FM18CA0010X
449631122111536000000
Heated Sample Probe
CP10110 Buhler Class 1 Division 2 Group B,C,D T4 1728394
Part No: 4622220CD23003
Flow Indicator
FM12220 Brooks Part No: Class 1 Division 1 Group A,B,C,D T6 1379260
3750CC2A11BEFAFAA0
Transformer 20140903-
TFR101 HPS Class 1 Division 2 Group A,B,C,D T3
Part No: TN2A0006KBKC E258346
Circuit Breaker
CB101 Eaton Part No: EIBA3030 S178 S214 Class 1 Division 2 Group B,C,D T3 FTRV.E71278
S756V
NON-UPS Over Current Protector
OCP101 Eaton Class 1 Division 2 Group B,C,D T3 FTRV.E71278
Part No: EJB080806
Motor Starter
MS001 Eaton Class 1 Division 2 Group A,B,C,D T3 240700
Part No: GHG619
LED Lighting
FL100 Appleton Class 1 Division 2 Group A,B,C,D T3 70212106
Part No: RMB22CPLBUNGT
Lighting Switch
SW120 Appleton Class 1 Division 2 Group B,C,D T3 WSQX.E10523
Part No: EDSC175-F1-A
Isolation Switch
SW121 Appleton Class 1 Division 2 Group B,C,D T3 WSQX.E10523
Part No: EDSC175-F1-A
Isolation Switch
SW124 Appleton Class 1 Division 2 Group B,C,D T3 WSQX.E10523
Part No: EDSC175-F2-A

Base Document: CNAUS-EN-LIS-011_B Page 2 of 3


 
ABB Engineering (Shanghai) Ltd.

Document Title: Hazardous Area Equipment List & Certificates


Dos Bocas New Refinery
Project Name: PO Number: 5000071282-0 Approved: Felix
Project

PTI-Infraestructura de Customer R2B-P2-204-03-P-CER-KAR701-


Customer Name: Date: 2023-3-14
Desarrollo, S.A. de C.V. Doc. No: 5-5-01013

Project Number: AUS-4498-00239 ABB Doc. No: AUS-4498-00239-002-013 Revision: D

BOM Item Manufacturer Equipment Description Certification Type Certificate No.

PJB101A
NON-UPS Power Junction Box 1538493
PJB101B Appleton Class 1 Division 2 Group A,B,C,D T5
Part No: SJB2226150 (013017_0_000)
PJB101C
PJB102C
PJB102F UPS Power Junction Box 1538493
Appleton Class 1 Division 2 Group A,B,C,D T5
PJB102H Part No: SJB2226150 (013017_0_000)
PJB102J
Power Junction Box 1538493
PJB103 Appleton Class 1 Division 2 Group A,B,C,D T5
Part No: SJB1218950 (013017_0_000)
JB101A Analogue / Digital Junction Box 1538493
Appleton Class 1 Division 2 Group A,B,C,D T5
JB102A Part No: SJB2226150 (013017_0_000)
NE001A Network Enclosure 1538493
Appleton Class 1 Division 2 Group A,B,C,D T5
NE001B Part No: SJB5637200 (013017_0_000)
Electrical traced tubing bundle
HTB101 Thermon Part No: SE-2F1-71-7-ATP-049- Class 1 Division 2 Group A,B,C,D T3 2238701
XINS(2)
Electrical traced tubing bundle
HTB103 Thermon Class 1 Division 2 Group A,B,C,D T3 2238704
Part No: SE-2F1-45-7-ATP-049
Temperature Controller
TC10101 Thermon Class 1 Division 2 Group A,B,C,D T4 2709489
Part No: ECM-CL
Fast Loop Pump
LP30101 Tuthill Part No: TXS2.6EEET3NN00000 Class 1 Division 2 Group A,B,C,D T3 70088957
00136ET3EW56C-S
SRS Pump
LP30102 Tuthill Part No: DGS.68EEET2NN00000 Class 1 Division 2 Group A,B,C,D T3 70088957
00136ET3EW56C-S
Solenoid Valve
3SOV12104 Norgren Class 1 Division 1 Group B,C,D T4 LR1380-2R7
Part No: Y013AA1H2BS-LP
Ethernet Switch
ESA001 MOXA Class 1 Division 2 Group A,B,C,D T3 E312544
Part No: EDS-205A-S-SC
24VDC PSU Module
PSU001A
ABB Part No: CP-E 24/5.0 Class 1 Division 2 Group A,B,C,D T3 QQPX8.E317914
PSU001B
CP-E 24/10.0

Base Document: AUS-4498-SIU-EN-011_A Page 3 of 3


QPS Evaluation Services Inc
Testing, Certification and Field Evaluation Body
Accredited in Canada, the USA, and Internationally

File
LR1643

CERTIFICATE OF COMPLIANCE
(ISO TYPE 3 CERTIFICATION SYSTEM)
Issued to Hobré Instruments B.V.

Address
Netwerk 4, 1446 WK
Purmerend, the Netherlands

Project Number
LR1643-2
Product
X-ray Fluorescence Liquid Analyzer.
Model Number
C-Quand
Ratings Class I, Div. 2, Group B,C,D, T3, Tamb: +5°C to 40°C, Type Z purge.
Electrical Rating: 115/ 230 Vac 47- 63 HZ, 500 Watts.

Condition of Safety use: The external device or equipment(s) that connect to the field wiring circuit of the
X-ray Fluorescence Liquid Analyzer required to comply to the Intrinsically Safe
circuit parameters as listed for the Intrinsically safe Barriers module.

Applicable Standards CSA C22.2 No. 213-17


UL121201 9th ed.
UL 61010-1 3rd (as Guide)
CSA C22.2 No. 61010-1:12 (as Guide)
NFPA 496
Factory Location Hobré Instruments B.V.
Netwerk 4, 1446 WK, Purmerend, the Netherlands

Manufacturing Location Hobré Instruments B.V.


Netwerk 4, 1446 WK, Purmerend, the Netherlands

Statement of Compliance: The product(s) identified in this Certificate and described in the Report covered under the
above referenced project number have been investigated and found to be in compliance with the relevant requirements of
the above referenced standard(s). As such, they are eligible to bear the QPS Certification Mark shown below, in accordance
with the provisions of QPS’s Service Agreement.

Issued By: Dave Adams, P.Eng.


Certification Manager, Hazardous Locations [Ex Equipment] Department

Signature: Date: January 28, 2022

81 Kelfield St., Units 7-9, Toronto, ON M9W 5A3 Tel: 416-241-8857; Fax: 416-241-0682
www.qps.ca
QSD 34HL Rev 00
Certificate of Compliance
Certificate: 70169008 Master Contract: 161704 (023910_0_000)

Project: 70200289 Date Issued: 2018-10-25

Issued to: 12320 Cardinal Meadow Dr.

Suite 150 Sugar Land, Texas 77478


USA
Attention: Yanzhong Li

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Marin Banu
Issued by:
Marin Banu

U.S. STANDARDS

Class I, Div.1, Groups B, C & D, T2 or T3 or T4 (with purge controller, with back-up purge system)

• SOLA iQ Liquid, Liquid Trace, Vapor, Vapor Trace, Flare, Condensable Vapor (CV) Analyzer, rated 100-
240Vac, 50-60Hz, 18A. Ambient temperature range: 12°C to +40°C.

Class I, Div.2, Groups B, C & D, T2 or T3 or T4 (with back-up purge system)

• SOLA iQ Liquid, Liquid Trace, Vapor, Vapor Trace, Flare, Condensable Vapor (CV) Analyzer, rated 100-
240Vac, 50-60Hz, 18A. Ambient temperature range: 12°C to +40°C.

Notes:
1. Wiring shall be accordance with wiring method for Class I, Div. 1 and Div. 2, per the Canadian Electrical
Code (CEC) for installation in Canada and per the National Electrical Code (NFPA 70) for installation
within U.S.
2. Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection
authority.
3. Unused openings in the enclosure shall be plugged with suitable blanking plugs.

DQD 507 Rev. 2016-02-18 Page 1


Certificate: 70169008 Master Contract: 161704
Project: 70200289 Date Issued: 2018-10-25

4. To minimize the risk of electrostatic charge, provisions shall be made for adequate grounding.
Equipment shall be installed in such a manner so that accidental discharge shall not occur.

APPLICABLE REQUIREMENTS

CSA Std C22.2 No. 0-10 General Requirements – Canadian Electrical Code, Part II

CSA Std C22.2 No. 30-M1986 (R2012) Explosion-Proof Enclosures for Use in Class I Hazardous Locations
Non-Incendive Electrical Equipment for Use in Class I, Division 2
CSA Std. C22.2 No. 213-16
Hazardous Locations
Safety Requirements for Electrical Equipment for Measurement,
CSA C22.2 No. 61010-1-12 3rd Ed.
Control & Laboratory Use - Part 1: General Requirements
ANSI/NFPA 496-2013 Purged and Pressurized Enclosures for Electrical Equipment
Safety Requirements for Electrical Equipment for Measurement,
UL 61010-1 (3rd Ed.)
Control & Laboratory Use - Part 1: General Requirements
Non-incendive Electrical Equipment for Use in Class I and II, Division
ANSI/ISA-12.12.01-2016
2 and Class III, Division 1 and 2 Hazardous (Classified) Locations
Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
UL Std No. 1203 (6th Edition)
in Hazardous (Classified) Locations

MARKINGS

The manufacturer is required to apply the following markings:


• Products shall be marked with the markings specified by the particular product standard.
• Products certified for Canada shall have all Caution and Warning markings in both English and French.

Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.

The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.

- Submitter’s Name, or trademark;


- Catalogue or Model Designation;
- Month and Year of manufacture, or date code, or serial number traceable to the Month and Year of
Manufacture;
- Complete Electrical Rating;
- Ambient Temperature;
- Minimum purging flow rate (for initial purge);
- Minimum purging duration (for initial purge);
- Hazardous Location Designation;

DQD 507 Rev. 2016-02-18 Page 2


Certificate: 70169008 Master Contract: 161704
Project: 70200289 Date Issued: 2018-10-25

Class I, Division 1 or 2, Groups B, C, D, T2 or T3 or T4; Type X Purge


Class I, Division 2, Groups B, C, D, T2 or T3 or T4; Type Z Purge
Ta: +12°C <Tamb < +40°C

- The following Warnings (or equivalent):

“WARNING – PRESSURIZED ENCLOSURE”

“WARNING – ENCLOSURE SHALL NOT BE OPENED UNLESS THE AREA IS KNOWN TO BE


NONHAZARDOUS, OR UNLESS ALL DEVICES WITHIN THE ENCLOSURE HAVE BEEN
DEENERGIZED.”

“WARNING: PRESURISED ENCLOSURE SHALL NOT BE OPENED UNLESS THE AREA IS


KNOWN TO BE NON-HAZARDOUS. POWER SHALL NOT BE RESTORED AFTER AN
ENCLOSURE HAS BEEN OPENED, UNTIL ALL ENCLOSURES HAVE BEEN PRE-PURGED.
(BEEN PURGED FOR 30 MINUTES AT A FLOW RATE OF 120 L/MIN or 210 L/MIN for DIV 2
UNIT) ”

“WARNING: DO NOT OPEN ANY DOOR OR COVER FOR THE TEMPERATURE CODE
REQUIRED PURGE TIME AFTER REMOVING POWER.”

Temperature Code For Liquid Unit:


IN ORDER TO HAVE A (T) CLASS OF (T2) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
50 MINUTES. USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T3) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
80 MINUTES. USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG

For Flare/Vapor/CV Unit:


IN ORDER TO HAVE A (T) CLASS OF (T2) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
40 MINUTES USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T3) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
60 MINUTES USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T4) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
80 MINUTES.USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG

“WARNING – THE SAFETY OF THIS EQUIPMENT RELIES ON THE PROVISION OF PROPER


PURGING AND PRESSURIZING WHEN USED IN HAZARDOUS LOCATIONS. IT MUST NOT BE
PUT INTO USE WITHOUT “SPECIAL PERMISSION” FROM THE INSPECTION AUTHORITY
HAVING JURISDICTION.”

DQD 507 Rev. 2016-02-18 Page 3


Certificate: 70169008 Master Contract: 161704
Project: 70200289 Date Issued: 2018-10-25

Note - Jurisdictions in Canada may require these markings to also be provided in French language. It is the
responsibility of the manufacturer to provide bilingual marking, where applicable, in accordance with the
requirements of the Provincial Regulatory Authorities. It is the responsibility of the manufacturer to determine
this requirement and have bilingual wording added to the "Markings".

DQD 507 Rev. 2016-02-18 Page 4


Supplement to Certificate of Compliance

Certificate: 70163097 Master Contract: 185289 (104225_0_000)

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History


Project Date Description

70200289 2018-10-25 SOLA iQ Update to CSA Report 70169008 This quotation assumes that no
testing is required
70169008 2018-01-05 North America (CSA c-us) certification project. This is continuation of
project 70147328.

DQD 507 Rev. 2016-02-18 Page 1


Certificate of Compliance
Certificate: 70169008 Master Contract: 161704 (023910_0_000)

Project: 70169008 Date Issued: 2018-01-05

Issued to: Thermo Process Instruments L.P., a subs of Thermo Fisher Scientific
12320 Cardinal Meadow Dr.
Suite 150
Sugar Land, Texas 77478
USA
Attention: Yanzhong Li

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Marin Banu
Issued by:
Marin Banu

PRODUCTS
CLASS - C225802 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations-
CLASS - C225882 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations - Certified to US Standards

Class I, Div.1, Groups B, C & D, T2 or T3 or T4 (with purge controller, with back-up purge system)

• SOLA iQ Liquid, Liquid Trace, Vapor, Vapor Trace, Flare, Condensable Vapor (CV) Analyzer, rated 100-
240Vac, 50-60Hz, 18A. Ambient temperature range: 12°C to +40°C.

Class I, Div.2, Groups B, C & D, T2 or T3 or T4 (with back-up purge system)

• SOLA iQ Liquid, Liquid Trace, Vapor, Vapor Trace, Flare, Condensable Vapor (CV) Analyzer, rated 100-
240Vac, 50-60Hz, 18A. Ambient temperature range: 12°C to +40°C.

Notes:
1. Wiring shall be accordance with wiring method for Class I, Div. 1 and Div. 2, per the Canadian Electrical
Code (CEC) for installation in Canada and per the National Electrical Code (NFPA 70) for installation
within U.S.
2. Final acceptance of this equipment when installed is subject to the jurisdiction of the local inspection
authority.

DQD 507 Rev. 2016-02-18 Page 1


Certificate: 70169008 Master Contract: 161704
Project: 70169008 Date Issued: 2018-01-05

3. Unused openings in the enclosure shall be plugged with suitable blanking plugs.
4. To minimize the risk of electrostatic charge, provisions shall be made for adequate grounding.
Equipment shall be installed in such a manner so that accidental discharge shall not occur.

APPLICABLE REQUIREMENTS

CSA Std C22.2 No. 0-10 General Requirements – Canadian Electrical Code, Part II

CSA Std C22.2 No. 30-M1986 (R2012) Explosion-Proof Enclosures for Use in Class I Hazardous Locations
Non-Incendive Electrical Equipment for Use in Class I, Division 2
CSA Std. C22.2 No. 213-16
Hazardous Locations
Safety Requirements for Electrical Equipment for Measurement,
CSA C22.2 No. 61010-1-12 3rd Ed.
Control & Laboratory Use - Part 1: General Requirements
ANSI/NFPA 496-2013 Purged and Pressurized Enclosures for Electrical Equipment
Safety Requirements for Electrical Equipment for Measurement,
UL 61010-1 (3rd Ed.)
Control & Laboratory Use - Part 1: General Requirements
Non-incendive Electrical Equipment for Use in Class I and II, Division
ANSI/ISA-12.12.01-2016
2 and Class III, Division 1 and 2 Hazardous (Classified) Locations
Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
UL Std No. 1203 (6th Edition)
in Hazardous (Classified) Locations

MARKINGS

- Submitter’s Name, or trademark;


- Catalogue or Model Designation;
- Month and Year of manufacture, or date code, or serial number traceable to the Month and Year of
Manufacture;
- Complete Electrical Rating;
- Ambient Temperature;
- Minimum purging flow rate (for initial purge);
- Minimum purging duration (for initial purge);
- Hazardous Location Designation;
Class I, Division 1 or 2, Groups B, C, D, T2 or T3 or T4; Type X Purge
Class I, Division 2, Groups B, C, D, T2 or T3 or T4; Type Z Purge
Ta: +12°C <Tamb < +40°C

- The following Warnings (or equivalent):

“WARNING – PRESSURIZED ENCLOSURE”

“WARNING – ENCLOSURE SHALL NOT BE OPENED UNLESS THE AREA IS KNOWN TO BE


NONHAZARDOUS, OR UNLESS ALL DEVICES WITHIN THE ENCLOSURE HAVE BEEN
DEENERGIZED.”

DQD 507 Rev. 2016-02-18 Page 2


Certificate: 70169008 Master Contract: 161704
Project: 70169008 Date Issued: 2018-01-05

“WARNING: PRESURISED ENCLOSURE SHALL NOT BE OPENED UNLESS THE AREA IS


KNOWN TO BE NON-HAZARDOUS. POWER SHALL NOT BE RESTORED AFTER AN
ENCLOSURE HAS BEEN OPENED, UNTIL ALL ENCLOSURES HAVE BEEN PRE-PURGED.
(BEEN PURGED FOR 30 MINUTES AT A FLOW RATE OF 120 L/MIN or 210 L/MIN for DIV 2
UNIT) ”

“WARNING: DO NOT OPEN ANY DOOR OR COVER FOR THE TEMPERATURE CODE
REQUIRED PURGE TIME AFTER REMOVING POWER.”

Temperature Code For Liquid Unit:


IN ORDER TO HAVE A (T) CLASS OF (T2) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
50 MINUTES. USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T3) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
80 MINUTES. USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG

For Flare/Vapor/CV Unit:


IN ORDER TO HAVE A (T) CLASS OF (T2) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
40 MINUTES USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T3) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
60 MINUTES USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG
IN ORDER TO HAVE A (T) CLASS OF (T4) AFTER LOSS OF PURGE A SECONDARY PURGE
SYSTEM SHALL HOLD THE PRESSURE INSIDE THE UNIT ABOVE 0.5 mbar FOR A PERIOD OF
80 MINUTES.USING A MINIMUM SUPPLY PRESSURE OF 20 PSIG

“WARNING – THE SAFETY OF THIS EQUIPMENT RELIES ON THE PROVISION OF PROPER


PURGING AND PRESSURIZING WHEN USED IN HAZARDOUS LOCATIONS. IT MUST NOT BE
PUT INTO USE WITHOUT “SPECIAL PERMISSION” FROM THE INSPECTION AUTHORITY
HAVING JURISDICTION.”

DQD 507 Rev. 2016-02-18 Page 3


Supplement to Certificate of Compliance

Certificate: 70169008 Master Contract: 161704 (023910_0_000)

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History


Project Date Description

70169008 2018-01-05 North America (CSA c-us) certification of the SOLA iQ Liquid, Liquid
Trace, Vapor, Vapor Trace, Flare, condensable Vapor (CV) Analyzer for
hazardous locations.

DQD 507 Rev. 2016-02-18 Page 1


Certificate of Compliance
Certificate: 1105720 Master Contract: 204015

Project: 70125370 Date Issued: May 14, 2018

Issued to: ABB Automation GmbH


Stierstaedter Strasse 5
Frankfurt am Main,
60488
GERMANY

Attention: Matthias Guth

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Issued by:
Herbert Peters

PRODUCTS

CLASS C225802 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations-


CLASS C225882 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations - Certified to US Standards

Equipment Product code Ratings / Marking Ambient Temp.


Advance Optima / P/N 24041-x Class I, Div. 2, See analyzer
AO2000 Series" Groups A, B, C and D T4
Continuous Gas 100-240 Vac / 50-60Hz / 2.2A (single
Analyzers voltage range power supply installed),
Consisting of the following components:
Housing P/N 24341-x See analyzer
Electronic Module P/N 24441-x (relay contacts rated 30 V, 1A) See analyzer
Pneumatic Module P/N 24141-x See analyzer
Power supply 3KXG758003U0400 Type PSU-0261-12X See analyzer
3KXG758003U0300 Type PSU-0261-13X
758118 Rated 100 V to 240 Vac 50/60 Hz 4 A
Type MZP-Z159
Rated 100 V to 240 Vac 50/60 Hz, 4 A
HMI / Display unit 3KXG758009U0200 Rated Input HMI: DC 5V, 225 mA, See analyzer
Input Display unit:

DQD 507 Rev. 2016-02-18 Page 1


Certificate: 1105720 Master Contract: 204015
Project: 70125370 Date Issued: April 23, 2018

Logic: DC 3,3V 50mA


Backlight LED: DC 12V, 50 mA
Uras26 Module P/N 24541-x rated 24 Vdc, 75W +5 °C to +45 °C.
Magnos27 Module P/N 24642-x rated 24 Vdc, 35W +5 °C to +45 °C.
Magnos28 Module P/N 24644-x rated 24 Vdc, 55W +5 °C to +50 °C.
Magnos206 Module P/N 24641-x rated 24 Vdc, 55W +5 °C to +50 °C.
Caldos25 Module P/N 24741-x rated 24 Vdc, 35W +5 °C to +45 °C.
Caldos27 Module P/N 24742-x rated 24 Vdc, 35W +5 °C to +50 °C.
Limas21 UV Module P/N 24931-x rated 24 Vdc; max. 100 W +5 °C to +45 °C
Limas21 HW Module P/N 24931-x rated 24 Vdc; max. 100 W +15 °C to +35 °C
Limas11 UV Module P/N 24911-0-x rated 24 Vdc, 80W +5 °C to +45 °C.
Limas11 IR Module P/N 24921-0-x rated 24 Vdc, 80W +5 °C to +45 °C.
Limas11 HW Module P/N 24911-0-x rated 24 Vdc, 100W +5 °C to +35 °C.
LS25 Laser Stack P/N 24210-0-x rated 18-36 Vdc, 20W -20 °C to +55 °C.
Analyzer
LS25 Remote Power P/N 24210-0-x (Non-Hazardous Locations only, rated -20 °C to +55 °C.
Supply Unit 100-240Vac, 50/60Hz, 0.36 - 0.26A)
Separate products
SCC-C Cooler P/N 23070-x Class I, Div. 2, +5 °C to +50 °C
Groups A, B, C and D T4
input rated 120/240 Vac, 50/60 Hz, 200
VA; Relay contact rated 250Vac / 2A
SCC-F P/N 23212-x Class I, Div. 2, +5 °C to +50 °C
Sample Conditioning Groups A, B, C and D T4
Unit (Non-CAN Bus input rated 120/240 Vac, 50/60 Hz,
Version) 185VA; Relay contacts rated 250Vac /
2A
SCC-F P/N 23212-x Class I, Div. 2, +5 °C to +50 °C
Sample Conditioning Groups A, B, C and D T4
Unit (CAN Bus input rated 120/240 Vac, 50/60 Hz, 185
Version) VA; Relay contacts rated 30V/1A
(General Purpose) and B300 Pilot Duty
(360VA max at 240Vac)

Notes:
1. "x" in the P/N's may be a 12 digit number representing specific features and options such as wall mount or
rack mount versions.
2. The AO2000 Analyzer Series consists of the AO2020 rack mount version and the AO2040 wall mount
version.
3. Rack mount versions and wall mount versions not equipped with conduit entries must be installed in a
suitable enclosure, cabinet or rack with provision for connection of Division 2 wiring methods, acceptable to
the local inspection authority having jurisdiction.
4. I/O connectors must only be connected to Class 2 circuits.

DQD 507 Rev. 2016-02-18 Page 2


Certificate: 1105720 Master Contract: 204015
Project: 70125370 Date Issued: April 23, 2018

APPLICABLE REQUIREMENTS

CAN/CSA C22.2 No. 0-M91 (R2001) - General Requirements - Canadian Electrical


Code, Part II
CSA Std. C22.2 No. 142-M1987 - Process Control Equipment
CSA Std. C22.2 No. 213-M1987 - Non-Incendive Electrical Equipment for Use in Class I, Division
2 Hazardous Locations
UL Std. No. 916-2007 - Energy Management Equipment
ANSI/ISA-12.12.01-2010 - Non incendive Electrical Equipment for Use in Class I and II,
Division 2 and Class III, Divisions 1 and 2 Hazardous
(Classified) Locations

MARKINGS

The manufacturer is required to apply the following markings:


• Products shall be marked with the markings specified by the particular product standard.
• Products certified for Canada shall have all Caution and Warning markings in both English and French.

Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.

The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.

1. Submittor's identification (company name and/or file number and/or registered tradename);
2. Factory identifier; [if required]
3. Model designation;
4. Serial Number
5. Date Code or Month and Year of Manufacture(can be included in the serial number)
6. Electrical rating;
7. Class I, Div. 2, Groups A, B, C and D T4
8. The CSA Monogram with C/US subscript;
9. Range of the ambient temperature
10. Warnings in English and French

DQD 507 Rev. 2016-02-18 Page 3


EU Declaration of Conformity
No: RAD 1124 Rev. B
5081-G

We,

Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA

declare under our sole responsibility that the product,

Rosemount™ Oxygen Gas Transmitter model 5081-AA-BB-CC

manufactured by,

Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA

to which this declaration relates, is in conformity with the provisions of the European Union
Directives, including the latest amendments, as shown in the attached schedule.

Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Union notified body certification, as shown in the attached
schedule.

Vice President of Global Quality


(signature) (function)

Chris LaPoint 1-Feb-19; Shakopee, MN USA


(name) (date of issue & place)

Page 1 of 2
EU Declaration of Conformity
No: RAD 1124 Rev. B
Rosemount™ Oxygen Gas Transmitter model 5081-AA-BB-CC

Where
AA is: CC is:
G Oxygen Gas measurement 60 CSA, Intrinsically Safe, NonIncendive
67 FM, Intrinsically Safe, NonIncendive
BB is: 69 CSA, Intrinsically Safe, NonIncendive
HT Analog/HART communications 73 ATEX / IECEx, Intrinsically Safe
FF Fieldbus communications

to which this declaration relates, is in conformity with relevant Union harmonization legislation:

EMC Directive (2014/30/EU)


Harmonized Standards:
EN 61326-1:2013

ATEX Directive (2014/34/EU) (The ATEX Directive is only valid if option 73 is selected)

Baseefa04ATEX0052X – Intrinsically Safe


Equipment Group II, Category 1 G Ex ia IIC T4 Ga ( -20°C ≤ Ta ≤ +65°C)
Special Condition for use:
The equipment enclosure may contain light metals. The apparatus must
be installed in such a manner as to minimize the risk of impact or friction
with other metal surfaces.

Harmonized Standards:
EN 60079-0:2012+A11:2013
EN 60079-11:2012

ATEX Notified Body for EC Type Examination Certificate & Quality Assurance
SGS FIMKO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland

Page 2 of 2
CERTIFICATE OF CONFORMITY

1. HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT PER US REQUIREMENTS


2. Certificate No: FM20US0047
3. Equipment: Mobrey Squing 2 Explosionproof Liquid Level Switch/
(Type Reference and Name) Rosemount 2100 series Liquid Level Swtich

4. Name of Listing Company: Rosemount Tank Radar AB

5. Address of Listing Company: Layoutvägen 1,


43533 Mölnlycke,
Sweden

6. The examination and test results are recorded in confidential report number:

3012658 dated 12th August 2002


7. FM Approvals LLC, certifies that the equipment described has been found to comply with the following Approval
standards and other documents:

FM3600:2018, FM3615:2018, FM3810:2005, ANSI/NEMA 250:1991

8. If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to specific
conditions of use specified in the schedule to this certificate.

9. This certificate relates to the design, examination and testing of the products specified herein. The FM
Approvals surveillance audit program has further determined that the manufacturing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.

10. Equipment Ratings:

Explosionproof for Class I, Division 1, Groups A, B, C and D hazardous (classified) locations, indoors and
outdoors (Type 4X).

Certificate issued by:

4 June 2020
J. E. Marquedant Date
VP, Manager - Electrical Systems

To verify the availability of the Approved product, please refer to www.approvalguide.com

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 347 (Mar 16) Page 1 of 4


SCHEDULE
US Certificate Of Conformity No: FM20US0047

11. The marking of the equipment shall include:

Explosionproof for Class I, Division 1, Groups A, B, C, D, T6 with a Ta= -40°C to 75°C; T4 with a Ta=-40°C to
65°C; T3 with a Ta=-40°C to 50°C; Type 4X (-40°C to +150°C process)

Explosionproof for Class I, Division 1, Groups A, B, C, D, T6 with a Ta= -40°C to 75°C; T4 with a Ta=-40°C to
65°C; T3 with a Ta=-40°C to 50°C; Type 4X (-40°C to +180°C process)

Explosionproof for Class I, Division 1, Groups A, B, C, D, T6 with a Ta= -40°C to 75°C; T4 with a Ta=-40°C to
73°C; T3 with a Ta=-40°C to 69°C; T2 with a Ta=-40°C to 65°C; Type 4X (-70°C to +260°C process)

12. Description of Equipment:

General – The Squing 2 and Rosemount 2100 series Transmitters are a vibrating fork liquid level switch. As the
tuning forks vibrate, they send a signal of the amount of liquid. As liquid comes into contact, it dampens the
tuning fork, which alters the output to match the amount of liquid.

Construction – The Squing 2 and Rosemount 2100 series Transmitters areconstructed from Aluminium ally
ASTM B26 356-T6 and is in two parts, a main body and lid. Te Body and lid are fixed together via a threaded
joint, which then has a lid retention bracket. The body has two M20 x 1.5 cable entries and a ¾ NPT thread for
a connection point for the vibrating fork probe. The probe that enters the material is 315 Stainless Steel and is
of welded construction

Ratings - The Squing 2 and Rosemount 2100 series Transmitters operate at 20-60 Vdc (2W) or 20 – 264 VAC.
The transmitters are rated for use in an ambient temperature range of -40°C of up to +150°C. The transmitter
probes are rated for use in a process temperature range of -70°C to +260°C. The max rated pressure is
100bar.

Tabcdefghj. Mobrey Squing 2 Explosionproof Liquid Level Switch (-40°C to +150°C process
temperature).
XP/ I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 65°C; T3 Ta = 50°C; Type 4X
a = Material process connection/fork (Stainless Steel 316; D, E, F, G: Alloy C & C-276; C, H).
b = Process connection size (0 to 9).
c = Fitting (A to Z).
d = Electronic type B, C, R, S, T, G, V, K or H.
e = Finish (0-9).
f = Approval FM Explosionproof: D or F
g = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; Y: Stainless; T).
h = Length: A, H, B, C, D, E or L.
j = Any combination of up to 6 alphanumeric characters which do not affect safety compliance.

Mabcdefghj. Mobrey Squing 2 Explosionproof Liquid Level Switch (-40°C to +180°C process
temperature).
XP / I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 65°C; T3 Ta = 50°C; Type 4X
a = Material process connection/fork (Stainless Steel 316; D, E, F, G: Alloy C & C-276; C, H)
b = Process connection size (0 to 9).
c = Fitting (A to Z).
d = Electronic Type N, L, P, D or M.
e = Finish (0-9).
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 347 (Mar 16) Page 2 of 4


SCHEDULE
US Certificate Of Conformity No: FM20US0047

f = Approval FM Explosionproof: D or F
g = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; Y: Stainless; T).
h = Length A, H, B, C, D, E or L.
j = Any combination of up to 6 alphanumeric characters which do not affect safety compliance.

Habcdefghj. Mobrey Squing 2 Explosionproof Liquid Level Switch (-70°C to +260°C process
temperature).
XP / I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 73°C; T3 Ta = 69°C; T2 Ta = 65°C; Type 4X
a = Material process connection/fork (Stainless Steel 316; D, E, F, G: Alloy C & C-276; C, H).
b = Process connection size (0 to 9).
c = Fitting (A to Z).
d = Electronic type N, L, P, D or M.
e = Finish (0-9).
f = Approval FM Explosionproof: D or F
g = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; Y: Stainless; T).
h = Length A, H, B, C, D, E or L.
j = Any combination of up to 6 alphanumeric characters which do not affect safety compliance.

2120abcdeE5fghj. Rosemount 2120 Explosionproof Liquid Level Switch (-40°C to +150°C


process temperature).
XP / I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 65°C; T3 Ta = 50°C; Type 4X
a = Material process connection/fork (Stainless Steel 316; D, N, F: Alloy C & C-276; C, K)
b = Process connection size (0 to 9 or X ).
c = Fitting ( A to Z ).
d = Electronic Type B, C, E, R, S, T, G, V, K, H, F, W or X.
e = Finish ( 0 to 9 ).
f = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; Y: Stainless; T).
g = Length: A0000, H0000 or (E, M with 4 numeric characters to indicate actual length).
h = Up to 12 of alphanumeric characters may be added to represent options not affecting certification.
j = Low Power option (R2257, R2258).

2130abMcdefE5g. Rosemount 2130 Explosionproof Liquid Level Switch (-40°C to +180°C


process temperature).
XP / I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 73°C; T3 Ta = 69°C; T2 Ta = 65°C; Type 4X
a = Electronic Type N, L, P, D, M, F, W or X.
b = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; A9: Stainless; S9).
c = Material (Stainless Steel 316; S, F: Alloy C & C-276; H, K)
d = Process connection size & fitting: 4 alphanumeric characters.
e = Length A0000, H0000 or (E, M with 4 numeric characters to indicate actual length).
f = Finish (0-9).
g = Up to 12 alphanumeric characters may be added to represent options not affecting certification.

2130abEcdefE5g. Rosemount 2130 Explosionproof Liquid Level Switch (-70°C to +260°C


process temperature).
XP / I / 1 / ABCD / T6 Ta = 75°C; T4 Ta = 73°C; T3 Ta = 69°C; T2 Ta= 65°C; Type 4X
a = Electronic Type N, L, P, D, M, F, W or X.
b = Housing, 3⁄4 inch NPT Conduit Entry, (Aluminum; A9: Stainless; S9).
c = Material (Stainless Steel 316; S, F: Alloy C & C-276; H, K)
d = Process connection size & fitting: 4 alphanumeric characters.
e = Length A0000, H0000 or (E, M with 4 numeric characters to indicate actual length).
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 347 (Mar 16) Page 3 of 4


SCHEDULE
US Certificate Of Conformity No: FM20US0047

f = Finish (0-9).
g = Up to 12 alphanumeric characters may be added to represent options not affecting certification.

13. Specific Conditions of Use:

None

14. Test and Assessment Procedure and Conditions:

This Certificate has been issued in accordance with FM Approvals US Certification Requirements.

15. Schedule Drawings

A copy of the technical documentation has been kept by FM Approvals.

16. Certificate History

Details of the supplements to this certificate are described below:

Date Description

12th August 2002 Original Issue.


Supplement 1 to 7:
17th April 2016
See Certificate dated 17th April 2016.
Supplement 8:
Report Reference: RR223449 Dated 4th June 2020.
4th June 2020 Description of the Change: Transfer of certificate from previous holder Rosemount
Measurement Limited to Rosemount Tank Radar AB. No changes made to function,
form, or fit of the equipment.

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 347 (Mar 16) Page 4 of 4


CERTIFICATE OF COMPLIANCE
Certificate Number 20190805-E10449
Report Reference E10449-19830920
Issue Date 2019-AUGUST-05

Issued to: APPLETON GROUP


9377 W HIGGINS RD
ROSEMONT IL 60018

This certificate confirms that AUXILIARY DEVICES FOR USE IN HAZARDOUS


representative samples of LOCATIONS
See Addendum Page

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical


Equipment for Use in Hazardous (Classified) Locations
CAN/CSA C22.2 No. 25-1966, Enclosures for Use in Class
II Groups E, F, and G Hazardous Locations
CAN/CSA C22.2 No. 30-M1986, General Instruction No.
2:1988-11, Explosion-Proof Enclosures for Use in Class I
Hazardous Locations

Additional Information: See the UL Online Certifications Directory at


https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number 20190805-E10449
Report Reference E10449-19830920
Issue Date 2019-AUGUST-05

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Open type auxiliary devices for use in Class I, Division 1, Groups B, C and D; Class II, Division 1,
Groups E, F and G; and Class III hazardous locations.

Pilot Lights: Cat. No. EPL, may be followed by G, followed by 1, 2, 3, 4, 5, 6, 7, 8 or 9, followed by A, B,


C, G, R or O, may be followed by L, may be followed by LED. The catalog number may include prefix
A, C or N.

Single and Dual Push Button Switches: Cat. No. EP may be followed D, M or MC, followed by B, R or
G, may be followed by B, R or G, followed by A, B, C, D, E or F, may be followed L. The catalog
number may include prefix A, C or N.

Selector Switches: Cat. Nos. ESS, followed by 2 or 3, followed by 1, 2 or 4, followed by M, S, KM or


KS, followed by G, H, L, M, N, R, S or Q, may be followed by L. The catalog number may include prefix
A, C or N.

Illuminated Push Button Operators: Cat. No. EPT, followed by A, B, C, G, R or O, followed by A, B, C,


D, E or F, may be followed by L. The catalog number may include prefix A, C or N.

Reset Button: Cat. No. EPRS, may be followed by L or M. The catalog number may include prefix A, C
or N.

Potentiometer Operator: Cat. Nos. PO, followed by 1 or 2. The catalog number may include
prefix A, C or N.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 2
CERTIFICATE OF CONFORMITY

1. HAZARDOUS LOCATION ELECTRICAL EQUIPMENT PER CANADIAN REQUIREMENTS


2. Certificate No: FM18CA0010X
3. Equipment: TC-Standard X2; TC-Standard+ X2; TC-MIDI X2; TC MIDI+
(Type Reference and Name) X2; TC-Double X2 & TC-Double+ X2
Sample Gas Cooler
4. Name of Listing Company: Bühler Technologies GmbH

5. Address of Listing Company: Harkortstrasse 29


Ratingen, D-40880
Germany

6. The examination and test results are recorded in confidential report number:

3062014 dated 4th October 2018

7. FM Approvals LLC, certifies that the equipment described has been found to comply with the following Approval
standards and other documents:

CSA-C22.2 No. 213-15, CAN/CSA-C22.2 No. 61010-1:2012

8. If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to specific
conditions of use specified in the schedule to this certificate.
9. This certificate relates to the design, examination and testing of the products specified herein. The FM
Approvals surveillance audit program has further determined that the manufacturing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.

10. Equipment Ratings:

TC-Standard Models:

Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous locations with an ambient
temperature rating of 0°C of up to 50°C.

Certificate issued by:

4 October 2018
J. E. Marquedant Date
VP, Manager, Electrical Systems

To verify the availability of the Approved product, please refer to www.approvalguide.com

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 348 (Mar 16) Page 1 of 4


SCHEDULE
Canadian Certificate Of Conformity No: FM18CA0010X

TC-MIDI and TC-Double Models:

Non-incendive for Class I, Division 2, Groups A, B, C and D; T4 hazardous (classified) locations with an
ambient temperature rating of 0°C of up to 60°C.

11. The marking of the equipment shall include:

TC-Standard Models:

Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 50°C

TC-MIDI and TC-Double Models:

Class I Division 2, Groups A, B, C, D; T4 Ta = 0°C to 60°C

12. Description of Equipment:

General - The TC-6 sample gas chillers are intended to cool and dry the sample gas before going into the
gas analysers. Sample gases contain vapour which has to be withdrawn before it reaches the gas analyser.
The Gas flows through a heat exchanger (impinger) inserted into a cooling block. The latter then is cooled
to a preset temperature (5°C mostly).
Depending on the required cooling capacity the size of the heat exchanger and therefore chiller is chosen
and depending on the kind of gas to be cooled different heat exchanger materials are provided (stainless
steel, glass or PVDF).
A gas cooler (chiller) might be prepared for more than one heat exchanger. The cooling block is cooled by
different combinations of Peltier-elements. The temperature is sensed by an RTD.

Construction – The equipment is housed in a brushed stainsteel IP20 enclosure.

Ratings - TC-Standard operate at 24VDC, 115 VAC or 230 VAC, selectable by ordering, with an ambient
temperature rating of 0°C of up to 50°C. and TC-MIDI and TC-Double Models operate at 115 VAC or 230 VAC,
selectable by ordering, with an ambient temperature rating of 0°C of up to 60°C.

4496 211b2d1fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 1 heat exchangers)
b = Gas cooler model: 1 or 2
d, = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 1, 3
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1

4496 212b2d2fgh0jkl0n0 TC-Standard X2 - Sample Gas Cooler (fitted with 2 heat exchangers)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 10, 15, 20, 25, 30, or 35
h = Peristaltic Pumps; 0, 2, or 4
j & k = Moisture detector / Filter; 00, 01,02, 10, 11, 20, 21, 22
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 348 (Mar 16) Page 2 of 4


SCHEDULE
Canadian Certificate Of Conformity No: FM18CA0010X

l = Status Outputs; 0 or 1
n = Delta T control; 0 or 1

4496 212b2d2fgh0jkl0n0 TC-Standard+ X2 - Sample Gas Cooler (with 2 heat exchangers in


series)
b = Gas cooler model: 1 or 2
d = Supply voltage; 1, 2 or 4
f & g = Heat exchanger; 22, 27, 32 & 37
h = Peristaltic Pumps; 0, 2, 4
j & k = Moisture detector / Filter; 00, 01,10, or 11
l = Status Outputs; 0 or 1
n = no value assigned.

4496 311 b2defghijklmno Thermoelectric Cooler, TC-MIDI + X2(fitted with 1 heat exchangers)
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
e = Gas paths; 1or 2
f,g = Heat exchangers; 60,61, 65, 66, 70, 75, 80 or 85
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, 11, 20 21, or 22
l,m = Status output; 00 or 10
n,o = Delta T control; 00 or 10

4496 312 b2d1fghijklm00 Thermoelectric Cooler, TC-MIDI + X2(fitted with 2 heat exchangers)
b = Gas cooler types 1 or 2
d = Supply Voltage; 1 or 2
f,g = Heat exchangers; 22, 27, 32, or 37
h = Peristaltic pumps; 0, 2, or 4
i = Sample gas pumps; 0, 1, 2, 6, or 7
j,k = Moisture detector / Filter; 00, 01, 02, 10, or 11
l,m = Status output; 00 or 10

4496 611a2c1efghijkl000 Thermoelectric Cooler, TC-Double X2


a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 10,15, 20,25,30, or 35
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
k,l = Status output; 00 or 10

4496 611a2c1efghijkl000 Thermoelectric Cooler, TC-Double+ X2


a = Gas cooler types 1 or 2
c = Voltage; 1 or 2
e,f = Heat exchangers; 22, 27, 32, or 37
g = Peristaltic pumps; 0, 2, or 4
h = Sample gas pumps; 0, 1, or 2
i,j = Moisture Detector/Filter; 00, 01, 10, or 11
k,l = Status output; 00 or 10
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 348 (Mar 16) Page 3 of 4


SCHEDULE
Canadian Certificate Of Conformity No: FM18CA0010X

13. Specific Conditions of Use:

1. When installed as Class I Division 2 equipment, the thermoelectric cooler shall be mounted within a
tool-secured IP54 enclosure.

14. Test and Assessment Procedure and Conditions:

This Certificate has been issued in accordance with FM Approvals Canadian Certification Scheme.

15. Schedule Drawings

A copy of the technical documentation has been kept by FM Approvals.

16. Certificate History

Details of the supplements to this certificate are described below:

Date Description

4th October 2018 Original Issue.

THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: information@fmapprovals.com www.fmapprovals.com

F 348 (Mar 16) Page 4 of 4


Certificate of Compliance
Certificate: 1728394 Master Contract: 231516

Project: 70008788 Date Issued: October 15, 2014


Issued to: Bühler Technologies GmbH
Harkortstr. 29
Ratingen, D-40880
Germany
Attention: Christopher Sundergeld

The products listed below are eligible to bear the CSA


Mark shown with adjacent indicators 'C' and 'US' for
Canada and US or with adjacent indicator 'US' for
US only or without either indicator for Canada only.

Joe da Silva
Issued by: Joe da Silva, C.E.T.

PRODUCTS
CLASS 2252 81 - PROCESS CONTROL EQUIPMENT - Certified to US Standards
CLASS 2252 01 - PROCESS CONTROL EQUIPMENT

- Series GAS222.XX sample gas probes, Models GAS222.11ANSI/CSA, GAS222.30ANSI/CSA,


GAS222.35UANSI/CSA, GAS222.15ANSI/CSA, GAS222.17ANSI/CSA, GAS222.20ANSI/CSA,
GAS222.21ANSI/CSA, GAS222.31ANSI/CSA and GAS222.35ANSI/CSA, rated 115/230Vac, 50/60Hz, 440W,
max. Ambient 70°C max.
- Series AHF 22 heated sample gas filters, models AHF- 22-S-K and AHF-22-yyy-R-K, where yyy means the
mains voltage, 115 or 230V.

CLASS 2258 02 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations


CLASS 2258 82 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations - CERTIFIED TO U.S.
STANDARDS
Class I, Div 2, Groups B, C and D:
- Series GAS222.XX sample gas probes, Models GAS222.20 AMEX, GAS222.21 AMEX, GAS222.31AMEX,
GAS222.35 AMEX, GAS222.11ANSI/CSA, GAS222.30ANSI/CSA, GAS222.35UANSI/CSA, rated
115V/230V, 50/60Hz, 360W max, Ambient 80°C max., Temp code T3 or T4.

DQD 507 Rev. 2012-05-22 Page: 1


Certificate: 1728394 Master Contract: 231516

Project: 70008788 Date Issued: October 15, 2014

APPLICABLE REQUIREMENTS
CAN/CSA C22.2 No. 0-M91 (R2001) - General Requirements - Canadian Electrical Code, Part II
CSA Std C22.2 No. 142-M1987 - Process Control Equipment
CSA Std C22.2 No. 213-M1987 - Non-Incendive Electrical Equipment for Use in Class I, Division 2
Hazardous Locations
ANSI/ISA – 12.12.01-2012 - Nonincendive Electrical Equipment for Use in Class I and II,
Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations
UL Std No.916, Fourth Ed. 2007 - Energy Management Equipment

DQD 507 Rev. 2012-05-22 Page: 2


CERTIFICATE OF COMPLIANCE
Certificate Number 20140903-E258346
Report Reference E258346-20051214
Issue Date 2014-September-03

Issued to: HAMMOND POWER SOLUTIONS INC


595 SOUTHGATE DR
GUELPH, ON N1G 3W6 CANADA

This is to certify that TRANSFORMERS, GENERAL PURPOSE FOR USE IN


representative samples of HAZARDOUS LOCATIONS
USL, CNL Transformers for use in Class I, Division 2
Hazardous Locations Groups A, B, C and D:
Type HZQ - Single phase, compound filled, 0-50 kVA,
Type HZQT - Three phase, compound filled, 0-150 kVA.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: Standard No. ANSI/ISA 12.12.01-2013, Approved 2013-06-03,


Nonincendive Electrical Equipment for Use in Class I and II, Division 2
and Class III, Divisions 1 and 2 Hazardous (Classified) Locations
CSA C22.2 NO. 213-M1987 NON-INCENDIVE ELECTRICAL
EQUIPMENT FOR USE IN CLASS I, DIVISION 2 HAZARDOUS
LOCATIONS.
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Listing Mark for the US and Canada should be considered as
being covered by UL's Listing and Follow-Up Service meeting the appropriate requirements for US
and Canada.
The UL Listing Mark for the US and Canada generally includes: the UL in a circle symbol with “C” and
“US” identifiers: the word “LISTED”; a control number (may be alphanumeric) assigned by UL;
and the product category name (product identifier) as indicated in the appropriate UL Directory.

Look for the UL Listing Mark on the product.

William R. Carney, Director, North American Certification Programs

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1
Certificate of Compliance
Certificate: 70212106 Master Contract: 164460 (065182_0_000)

Project: 70212106 Date Issued: 2019-03-29

Issued to: Appleton Group Ltd.


9377 W Higgins Rd
Rosemont, Illinois 60018
USA
Attention: Steve Blais

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Steven Simkevitz
Issued by:
Steven Simkevitz

PRODUCTS
CLASS - C342883 - FIXTURES AND FITTINGS-For Hazardous Locations-Certified to U.S. Standards
CLASS - C342803 - FIXTURES AND FITTINGS-For Hazardous Locations

Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III; T-coded per
table below; Type 3R, 4, 4X; IP66; Marine Outside Type (Salt Water) for USA only;

Rigmaster Linear LED luminaires for use in hazardous locations; ceiling surface or wall surface mounted; rated
input voltage 120-277 VAC 50/60 Hz, 125-300 VDC or 347-480 VAC 50/60 Hz, 60 Watts max; Tambient -40 C to
+65 C per table below.
Catalogue number RM may be followed by A, B, L or N, followed by 2 or 4, may be followed by 1, 2 or 3,
followed by C, N or W, followed by D or P, followed by L, followed by BU or BH, followed by N, followed by
G, followed by W or T.

Class I,
Min Max Max Class I Class II, Zone
Class I, Division 2
Supply Driver Ambient Division 2 Division 22,
Series Number Wire Current Temp. Groups A,
Zone 2,
2, Groups Group
&
Group IIC Class II,
(C°) (mA) (C°) B, C and D F and G IIIC
Division 2
40 T6 T6 T6 T6 T5
RM*2***LB*NG* 90 600
55 T5 T5 T5 T5 T4A

DQD 507 Rev. 2018-11-12 Page 1


Certificate: 70212106 Master Contract: 164460
Project: 70212106 Date Issued: 2019-03-29

65 T4A T4 T4A T4 T4A


40 T5 T5 T6 T6 T5
RM*4***LB*NG* 90 1040 55 T4A T4 T5 T5 T4A
65 T4A T4 T5 T5 T4A

Notes:
1. *** Series model RM is followed with alphanumeric suffixes to denote electrical and mechanical
variations. Refer to nomenclature for details.
2. Marine Outside Type (Salt Water) rating applies to installation in the USA only.
3. Luminaire for marine application in the US is intended to be installed in accordance with CG-259
American Bureau of Shipping and Coast Guard requirements.
4. May be additionally marked Class I, Zone 2, IIC; Zone 22;

APPLICABLE REQUIREMENTS

CAN/CSA C22.2 No. 0-10 - General requirements — Canadian Electrical Code, Part II
CAN/CSA C22.2 No. 94.2-15 - Enclosures for electrical equipment, environmental considerations
CAN/CSA C22.2 No. 137-18 - Electric Luminaires for Use in Hazardous Locations
CAN/CSA C22.2 No. 250.0-18 - Luminaires
CAN/CSA C22.2 No. 250.13-17 - Light emitting diode (LED) equipment for lighting applications
CAN/CSA C22.2 No. 60529:16 - Luminaires — Part 1: General requirements and tests
UL 50E, Second Edition - Enclosures for electrical equipment, environmental considerations
UL 844, Thirteenth Edition - Luminaires for Use in Hazardous (Classified) Locations
UL 1598, Fourth Edition - Luminaires
UL 8750, Second Edition - Light Emitting Diode (LED) Equipment for Use in Lighting
Products

DQD 507 Rev. 2018-11-12 Page 2


Supplement to Certificate of Compliance

Certificate: 70212106 Master Contract: 164460 (065182_0_000)

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History


Project Date Description

70212106 2019-03-29 Original Hazardous Locations Certification for North America, for the
Rigmaster Linear LED Luminaire for the following ratings: Class I, Division
2, Groups A, B, C, D; Class II, Division 2, Groups F, G; Class III; Type 3R,
4, 4X; IP 66.

DQD 507 Rev. 2018-11-12 Page 1


2020/12/9 WSQX.E10523 - Snap Switches for Use in Hazardous Locations | UL Product iQ

WSQX.E10523 - Snap Switches for Use in Hazardous Locations


Snap Switches for Use in Hazardous Locations
See General Information for Snap Switches for Use in Hazardous Locations

APPLETON GROUP E10523


9377 W HIGGINS RD
ROSEMONT, IL 60018 USA

Trademark and/or Tradename: "E10523" , , , , , , , ,

, ,

Class I, Division 2, Groups B, C and D; Class II, Division 2, Groups F and G; Class III; ssemblies with snap switches, Type 3, 3R, 4, 4X aluminum assemblies only, 12, Model(s) FD2
or FD2C, followed by -110, -150 or -175, may be followed by L, followed by F1, -F2 or -F3W, may be followed by A.

Class I, Groups B, C and D, "LAB Series", Model(s) LAB-21, LAB-21L, LAB-22, LAB-22L, LAB-23, LAB-23W, LAB-23WL

Class I, Groups B, C and D; Class II, Groups E, F and G, "EDS Series", Model(s) EDS-150, or -175, with suffix -F1, -F2, -F3W, -F4W, -F13, -F23, -F3W3, -R1, -R2, -R3W, -R4W, -R13, -R23
or R3W3, may be followed by suffix A; EDS series provided with factory seals of conductors entering the switch enclosure.

Class I, Groups B, C and D; Class II, Groups E, F and G, "EDSC Series", Model(s) EDSC-150 or -175, with suffix -F1, -F2, -F3W, -F4W, -F13, -F23, -F3W3, -R1, -R2, -R3W, -R4W, -R13, -
R23, or -R3W3, may be followed by suffix A.

Class I, Groups C and D, "EHSF Series", Model(s) EHSF-1275, provided with factory seals of conductors entering the switch enclosure.

Class I, Groups C and D, suitable for use only in the specific atmospheres indicated in the manufacturer's installation instruction sheet No. 501550 supplied with device, "N1D
Series", Model(s) N1D75-F1, N1D75-F13, N1D75-F2, N1D75-F23, N1D75-F3W, N1D75-F3W3, N1D75-F4W, N1DC75-F1, N1DC75-F13, N1DC75-F2, N1DC75-F23, N1DC75-F3W, N1DC75-
F3W3, N1DC75-F4W

Class I, Groups C and D; Class I, Division 2, Group B; Class II, Groups E, F and G, snap switches w/LAB Series factory sealed switch, "EDS Series", Model(s) EDS or EDSC, may have
prefix N, followed by 118, 128, 218, 228, 318, 328, 1129, 1130, 1229, 1230, 2129, 2130, 2229, 2230, 3129, 3130, 3229 or 3230, may be followed by -SA.

Class I, Groups C and D; Class II, Groups E, F and G, "EDS, EDSC Series", Model(s) EDS- or EDSC-110, with suffix -F1, -F2, -F13, -F23, F3W, -F3W3, -F4W, -R1, -R2, -R13, -R23, -R3W, -
R3W3, -R4W, may be followed by suffix A.

https://iq.ulprospector.com/en/profile?e=164479 1/2
2020/12/9 WSQX.E10523 - Snap Switches for Use in Hazardous Locations | UL Product iQ

Class I, Groups C and D; Class II, Groups E, F and G, "EDS, EDSC Series", Model(s) EDS- or EDSC-210, -250, -275, with suffix -F1, -F2, -F3W, -F4W, -R1, -R2, -R3W, -R4W, -R13, -R23, -
R3W3, -F13, -F23 or -F3W3.

Class I, Groups C and D; Class II, Groups E, F and G, snap switches w/sealing chamber, "EDS Series", Model(s) EDS or EDSC, may have prefix N, followed by 118, 128, 218, 228, 318,
328, 1129, 1130, 1140, 1229, 1230, 1240, 2129, 2130, 2140, 2229, 2230, 2240, 3129, 3130, 3140, 3229, 3230, 3240, 3591, 3593 or 3594, with or without suffix -SA; EDS series are provided
with factory seals of conductors entering the switch enclosure.

Class I, Groups C and D; Class II, Groups E, F and G, Types EFS, EFSC, "EFS Series", Model(s) EFS150-F1, EFS150-F1A, EFS150-F3W, EFS150-F3WA, EFS150-F4W, EFS150-F4WA, EFS150-
R1, EFS150-R1A, EFS150-R3W, EFS150-R3WA, EFS150-R4W, EFS150-R4WA, EFS175-F1, EFS175-F13, EFS175-F13A, EFS175-F1A, EFS175-F2, EFS175-F23, EFS175-F23A, EFS175-F2A,
EFS175-F3W, EFS175-F3WA, EFS175-F4W, EFS175-F4WA, EFS175-R1, EFS175-R1A, EFS175-R2, EFS175-R2A, EFS175-R3W, EFS175-R3WA, EFS175-R4W, EFS175-R4WA, EFS210-F2, EFS210-
F23, EFS210-F3W, EFS210-F4W, EFS210-R2, EFS210-R3W, EFS210-R4W, EFS250-F1, EFS250-F1A, EFS250-R1, EFS250-R1A, EFS275-F1, EFS275-F13, EFS275-R1, EFSC150-F1, EFSC150-F1A,
EFSC150-F2, EFSC150-F2A, EFSC150-F3W, EFSC150-F3WA, EFSC150-F4W, EFSC150-F4WA, EFSC150-R1, EFSC150-R1A, EFSC150-R2, EFSC150-R2A, EFSC150-R3W, EFSC150-R3WA,
EFSC150-R4W, EFSC150-R4WA, EFSC175-F1, EFSC175-F13, EFSC175-F13A, EFSC175-F1A, EFSC175-F2, EFSC175-F23, EFSC175-F23A, EFSC175-F2A, EFSC175-F3W, EFSC175-F3WA,
EFSC175-F4W, EFSC175-F4WA, EFSC175-R1, EFSC175-R1A, EFSC175-R2, EFSC175-R2A, EFSC175-R3W, EFSC175-R3WA, EFSC175-R4W, EFSC175-R4WA, EFSC250-F1, EFSC250-F2,
EFSC250-F3W, EFSC250-F4W, EFSC250-R1, EFSC250-R2, EFSC250-R3W, EFSC250-R4W, EFSC275-F1, EFSC275-F13, EFSC275-F2, EFSC275-F23, EFSC275-F3W, EFSC275-F4W, EFSC275-R1,
EFSC275-R2, EFSC275-R3W, EFSC275-R4W

Click here to view the Colombia Market Access Certification

Last Updated on 2019-06-20

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those
products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions,
Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement
"Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright
notice in the following format: "© 2020 UL LLC"

https://iq.ulprospector.com/en/profile?e=164479 2/2
Certificate of Compliance
Certificate: 1538493 (013017_0_000) Master Contract: 150241

Project: 70167791 Date Issued: 2018-03-14

Issued to: EGS Electrical Group Canada Ltd.


99 Union St
Elmira, Ontario N3B 3L7
CANADA
Attention: Randall Kennedy

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Don Verbeem
Issued by:
Don Verbeem

PRODUCTS
CLASS - C441802 - OUTLET BOXES AND FITTINGS-Boxes - For Hazardous Locations
CLASS - C441882 - OUTLET BOXES AND FITTINGS-Boxes - For Hazardous Locations - Certified to US
Standards

Part A:

Ex e II, T5 or T6; IP 66; Type 4x (with approved breather)


Class I, Zone 1, AEx e II, T5 or T6; IP 66; Type 4x (with approved breather)

 Junction Boxes with or without window, Under Catalog series:


SJB or LJB or CJB or
JBES,or JBEL, or JBEC or
JBESG, JBELG, and JBECG followed by alphanumeric suffixes denoting window, dimensions of the junction
box, number of gland opening(s), and optional suffixes denoting optional mounting pan, and size and number of
terminal blocks installed. Rated 600 V max, 400 A Max. Maximum Dissipated power 927W.
.

DQD 507 Rev. 2012-05-22 Page 1


Certificate: 1538493 Master Contract: 150241
Project: 70167791 Date Issued: 2018-03-14

Enclosure Depth Depth Depth Depth Depth Depth Max. Dissipated Power / Encl.
Size 95 mm 150 mm 200 mm 300 mm 400 mm 500 mm for Ta 40°C max. T6
120 X 120 X 14 W
120 X 180 X 28 W
180 X 180 X 32 W
260 X 220 X 55 W
220 X 370 X 80 W
370 X 260 X 87 W
370 X 370 X X 106 W / 133 W
560 X 370 X X 145 W/ 175 W
750 X 370 X X 169 W / 220 W
560 X 560 X X 192 W / 232 W
750 X 560 X X 242 W / 288 W
1130 X 750 X X 412W/476 W
1500 X 750 X X 603 W/ 689W
1500 X 1000 X X X 758W/842 W/927W

Note:

1. Temperature Class T5 = The number of authorized terminal increases (max. dissipated power increased
1.17 times max dissipated power for T6)
2. Ta 55 °C or Ta 70 °C = The number of authorized terminals decreases
3. De-rating coefficients: 0.5 for Ta 55 °C and 0.25 for Ta 70 °C
4. Important parameters for selecting stainless steel boxes and enclosures equipped with terminals are given
under Tables 1 to 4 (attached under Ills. 4, 5 & 6)
5. The overall IP rating of the enclosure is governed by the lowest IP rating of any devices which are
interfaced with the enclosure
6. Enclosure Type 4X rating is governed by the lowest IP rating of any devices which are interfaced with the
enclosure
7. Above listing represents a partial range of potential junction boxes available ranging from 120 x 120 x 95 to
1500x1000x500. Additional dissipation readings to be established using supplied calculator file.

Part B:

Class I Div 2, Groups A, B, C, and D, T5 or T6; (with dual listed UL/CSA approved terminal blocks)
Class II, Division 1, Groups F and G; Class III
Ex e II, T5 or T6; IP 66; Type 4x (with approved breather and Ex e rated terminal blocks)
Class I, Zone 1, AEx e II, T5 or T6; IP 66; Type 4x (with approved breather and Ex e rated terminal
blocks)

• Junction Boxes, Catalog series SJB, LJB, or CJB or alternately known as Catalog series JBES, JBEL, and JBEC
followed by alphanumeric suffixes denoting dimensions of the junction box and construction features as specified
in the Ambient temperature range: -40°C to + 70°C. Suitable for outdoor use.

DQD 507 Rev. 2012-05-22 Page 2


Certificate: 1538493 Master Contract: 150241
Project: 70167791 Date Issued: 2018-03-14

The following junction box sizes are Certified (H x W x D in mm): 120 x 120 x 95, 120 x 180 x 95, 180 x 180 x
95, 260 x 220 x 150, 220 x 370 x 200, 370 x 260 x 200, 370 x 370 x 200 or 300, 560 x 370 x 200 or 300, 750 x
370 x 200 or 300, 560 x 560 x 200 or 300, 750 x 560 x 200 or 300, 1130 x 750 x 300, 1500 x 750 x 200 or 300,
and 1500 x 1000 x 300 ,1500 x 1000 x 400, or 1500 x 1000 x 500.

Note:

1. Junction boxes are furnished with NPT conduit hubs. The conduit hubs are CSA / UL Certified for Class II,
Division 1, Groups F and G hazardous locations and are at least Type 3 rated.
2. Junction boxes may or may not be furnished with CSA / UL Certified terminal blocks.
3. Above listing represents a partial range of potential junction boxes available ranging from 120 x 120 x 95 to
1500x1000x500.

APPLICABLE REQUIREMENTS

CAN/CSA C22.2 No 0- 10 - General Requirements - Canadian Electrical Code Part II


CAN/CSA C22.2 No 94.1 -07 - Enclosures for Electrical Equipment
CAN/CSA C22.2 No 213- M1987 - Non Incendive Equipment For Use in Class I Division 2 Hazardous
Locations
CSA C22.2 No. 25-1966 - Enclosures for Use in Class II Groups E, F, and G Hazardous Locations
CAN/CSA E60079-0-02 - Electrical apparatus for explosive gas atmospheres.
PART 0: General requirements.
CAN/CSA E60079-7-03 - Electrical apparatus for explosive gas atmospheres.
PART 7: Increased safety “e”
ANSI/UL 60079-0, 4th Ed. - Electrical apparatus for explosive gas atmospheres.
PART 0: General requirements
ANSI/UL60079-7, 1st Ed. - Electrical apparatus for explosive gas atmospheres.
PART 7: Increased safety “e”
ANSI/ISA-12.12.01-2013 - Nonincendive Electrical Equipment for Use in Class I and II, Division 2
and Class III, Divisions 1 and 2 Hazardous (Classified) Locations
UL 1203 - Fourth Edition - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
in Hazardous (Classified) Locations
UL 50E - Fourth Edition - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use
in Hazardous (Classified) Locations

MARKINGS

The manufacturer is required to apply the following markings:


 Products shall be marked with the markings specified by the particular product standard.
 Products certified for Canada shall have all Caution and Warning markings in both English and French.

Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.

DQD 507 Rev. 2012-05-22 Page 3


Certificate: 1538493 Master Contract: 150241
Project: 70167791 Date Issued: 2018-03-14

The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.

Nameplate adhesive label material approval information:

VENDOR: MOORE CANADA (INT)


MATERIAL TYPE: 3M Thermal Transfer Polyester
Listing :
UL FILE: MH16411
CSA File 99316:
Class Numbers 7922-xx and 7924-xx suitable for Class I Div 2 application only

The following markings shall be permanently marked on a CSA/UL certified self-adhesive label: (Refer to Ill.
10):

1. For junction boxes Certified as Ex e II / AEx e II for Class I, Zone 1 hazardous locations (Certified in “Part
A” above) and Class I Division 2 Groups A,B,C,D(Certified in “Part B” above):
 Manufacturers’ Name, Trade Mark, Master Contract Number “150241”, or File No. “LR 13017”;
 Catalogue Number designation;
 Hazardous Location Designation;
 Ambient Temperature range (-40°C to + 70°C);
 Temperature Code (T5 or T6);
 The rated maximum dissipated power;
 Rated voltage;
 Enclosure degree of protection: IP66; Type 4X
 “ CAUTION – DISCONNECT SUPPLY POWER BEFORE OPENING”;
 CSA monogram with the c us designator, followed with year of certification and certificate number
followed with suffix X;
 Serial Number or Date Code;
 Reference to Installation Instruction Sheets;

2. For junction boxes Certified for Class II, Division 1, Groups F and G hazardous locations (Certified in “Part
B” above):

 Manufacturers’ Name, Trade Mark, Master Contract Number “150241”, or File No. “LR 13017”;
 Catalogue Number designation;
 Hazardous Location Designation;
 Ambient Temperature range (-40°C to + 70°C);
 “ CAUTION – DISCONNECT SUPPLY POWER BEFORE OPENING”;
 “SUITABLE FOR OUTDOOR USE”;
 CSA monogram with the c us designator;
 Serial Number or Date Code;

DQD 507 Rev. 2012-05-22 Page 4


Certificate: 1538493 Master Contract: 150241
Project: 70167791 Date Issued: 2018-03-14

 Reference to Installation Instruction Sheets;


Installation Instructions

Installation Instructions shall include at least the following information:


 Assigned torque values;
 Instructions to indicate clearly any rearrangement or adjustment that is necessary to adapt to various sizes
of conductors;
 Instructions for proper installation of the conductors for the terminal constructions where the wiring
method is not obvious;
 Conductors insulating stripping requirements

DQD 507 Rev. 2012-05-22 Page 5


Supplement to Certificate of Compliance

Certificate: 1538493 (013017_0_000) Master Contract: 150241

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History


Project Date Description

70167791 2018-03-14 Update report 1538493 to include alternate Material (CRS) BOQ • Delivery
based on receipt of samples • Testing performed at CSA • Client to supply 2
identical sized fully assembled samples (1 for each material) • Temperature
test to compare CRS enclosure heat dissipation = SS enclosure Heat
Dissipation • Test for gasket adhesion
70117039 2017-02-06 Update report to include alternate enclosure construction
70045072 2015-10-20 Update report 1538493 to include alternate 304SS material
70035277 2015-07-22 Update report 1538493 to include maximum enclosure size 1500mm x
1000mm x 500mm, as well as clarify Class 1 Div 2 rating (when terminal
blocks are provided), and revise nomenclature to coincide
70011305 2014-09-24 Update to report 1538493 to evaluate the new SJB (or JBES) stainless steel
junction box construction with latch design
2645809 2013-11-29 Update report 1538493 to include Type 4X enclosure rating and larger
enclosure size.
2533051 2013-03-18 Certification of ten sizes of Catalog SJB (alternate Catalog designation
JBES) junction boxes for Class II, Division 1, Groups F and G and Class III
hazardous locations. Sizes Certified are specified in the Certificate of
Compliance.
2367404 2011-01-18 Update of report 1538493 to cover addition of Stainless Steel Enclosure with
window, Cat SJB-W and aluminum enclosures Cat LJB.
1538493 2005-02-02 Stainless steel outlet boxes, Series SJB; Rated 600 V max, 400 A max,
maximum Dessipated Power 489 W, Class I, Zone 1, AEx e II; T5 or T6; Ex
e II; T5 or T6; IP66 (Legacy no. LR13017)

DQD 507 Rev. 2012-05-22 Page 1


Certificate of Compliance
Certificate: 2238701 Master Contract: 153896

Project: 80063611 Date Issued: 2021-05-04

Issued To: Thermon, Inc


100 Thermon Dr
San Marcos, Texas, 78667
United States

Attention: Jason Anderson

Issued by: Amir Kianimanesh


Amir Kianimanesh

PRODUCTS
CLASS - C287201 - HEATERS Cable and Cable Sets
CLASS - C287281 - HEATERS Cable and Cable Sets - Certified to US Standards
CLASS - C287801 - HEATERS Cable and Cable Sets - For Hazardous Locations
CLASS - C287881 - HEATERS-Cable and Cable Sets For Hazardous Locations-Certified to U.S. Standards

For All CLASSES:

Trace heater sets, comprised of trace heater cable and kits as follows:

Electrical resistance parallel trace heater cable, Type HTSX, for indoor or outdoor applications for heating metal
or non-metallic pipes or vessels, usages -G, -W, with PFA insulation, tinned or nickel-plated copper braid, and
PFA overjacket (a construction option includes suffix “-BN” which denotes a nickel-plated copper braid without
an overjacket); rated 480V ac maximum, maximum withstand temperature rating of 250°C (482°F) (for 380-
480Vac is limited to 204℃) , maximum maintain temperature of 150°C (302°F) (for 380-480Vac is limited to
121℃), minimum recommended installation temperature -60°C, and maximum nominal power output of 66 W/m
(20 W/ft).

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 1
Certificate: 2238701 Master Contract: 153896
Project: 80063611 Date Issued: 2021-05-04

Type HTSX trace heaters are supplied with field connection and termination kits and accessories as detailed in
CSA Report 153896-2238691 (LR 79539/LR 79540) in order to create a trace heater set.

Electrical resistance parallel trace heater cable, Type KSX, for indoor or outdoor applications for heating metal or
non-metallic pipes or vessels, usages -G, -W, with PFA insulation, tinned or nickel-plated copper braid, and FEP
or PFA overjacket (a construction option includes suffix “-BN” which denotes a nickel-plated copper braid
without an overjacket); rated at 277V ac maximum, maximum de-energized temperature rating 200°C (392°F),
maximum maintenance temperature rating of 121°C (250°F), minimum recommended installation temperature -
60°C, and maximum power output of 77 W/m (23.5 W/ft).

Type KSX trace heater cable are supplied with field connection and termination kits and accessories as detailed in
CSA Report 153896-2238691 (LR 79539/LR 79540) in order to create a trace heater set.

Electrical resistance parallel trace heater cable, Type USX, for indoor or outdoor applications for heating metal or
non-metallic pipes or vessels, usages -G, -W, with PFA primary jacket (insulation) , tinned or nickel-plated copper
braid, and PFA overjacket (a construction option includes suffix “-BN” which denotes a nickel-plated copper braid
without an overjacket); rated 277V ac maximum, maximum intermittent energized/de-energized temperature rating
of 250°C (482°F), maximum maintenance temperature of 240°C (464°F), minimum recommended installation
temperature -60°C, and maximum nominal power output of 66 W/m (20 W/ft).

Type USX trace heaters are supplied with field connection and termination kits and accessories as detailed in CSA
Report 153896-2238691 (LR 79539/LR 79540) in order to create a trace heater set.

Additional Requirements for Classes:

CLASS 2872 01 – HEATERS – Cable and Cable Sets – For Ordinary Locations
CLASS 2872 81 – HEATERS – Cable and Cable Sets – For Ordinary Locations – Certified to US
Standards

Ordinary Location – HTSX, KSX and USX trace heater sets, usages –G and -W.

CLASS 2878 01 – HEATERS – Cable and Cable Sets – For Hazardous Locations
CLASS 2878 81 – HEATERS – Cable and Cable Sets – For Hazardous Locations – Certified to US
Standards

Hazardous location – HTSX trace heater sets, usages –G and -W:

For Canada:
Class I, Div. 1 & 2, Groups A, B, C, D; Class II, Div. 1 & 2, Groups E, F, and G; Class III
Type 4X

For US:

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 2
Certificate: 2238701 Master Contract: 153896
Project: 80063611 Date Issued: 2021-05-04

Class I, Div. 2, Groups B, C, D; Class II, Div. 2, Groups F and G; Class III
Type 4X

T3 - HTSX 3-1, HTSX 3-2, HTSX 6-1, HTSX 6-2, HTSX 9-1, HTSX 9-2, HTSX 10-4, HTSX
12-1, HTSX 12-2, HTSX 15-2 and HTSX 15-4
T2D - HTSX 15-1, HTSX 20-1
T2C - HTSX 20-2, HTSX 20-4

Ex eb IIC; Class I Zone 1 AEx eb IIC; Type 4X IP66

T3 - HTSX 3-1, HTSX 3-2, HTSX 6-1, HTSX 6-2, HTSX 9-1, HTSX 9-2, HTSX 9-2, HTSX 10-
4, HTSX 12-1, HTSX 12-2, and HTSX 15-2
215 °C (T2) - HTSX 15-1, HTSX 20-1
230 °C (T2) - HTSX 20-2, HTSX 20-4

Hazardous location – KSX trace heater sets, usages –G and -W:

For Canada:
Class I, Div. 1 & 2, Groups A, B, C, D; Class II, Div. 1 & 2, Groups E, F, and G; Class III
Type 4X IP66

For US:
Class I, Div. 2, Groups B, C, D; Class II, Div. 2, Groups F and G; Class III;

*T6…T3 - KSX 5-2, KSX 10-2, KSX 15-2, KSX 20-2, KSX 15-1, and KSX 20-1.

Ex eb IIC; Class I Zone I AEx eb IIC; Type 4X IP66

*T6…T3 - KSX 5-2, KSX 10-2, KSX 15-2, KSX 20-2, KSX 15-1, and KSX 20-1.

* Note: T-rating based on stabilized design.

Hazardous location – USX trace heater sets, usages –G and -W:

For Canada:
Class I, Div. 1 & 2, Groups A, B, C, D; Class II, Div. 1 & 2, Groups E, F, and G; Class III
Type 4X

For US:
Class I, Div. 2, Groups B, C, D; Class II, Div. 2, Groups F and G; Class III
Type 4X

T3 - USX 3-1, USX 3-2, USX 6-1, USX 6-2, USX 9-1, USX 9-2, USX 12-1,
USX 12-2, and USX 15-2

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 3
Certificate: 2238701 Master Contract: 153896
Project: 80063611 Date Issued: 2021-05-04

T2D - USX 15-1, USX 20-1


T2C - USX 20-2

Ex eb IIC; Class I Zone 1 AEx eb IIC; Type 4X IP66

T3 - USX 3-1, USX 3-2, USX 6-1, USX 6-2, USX 9-1, USX 9-2, USX 12-1,
USX 12-2, and USX 15-2
215 °C (T2) - USX 15-1, USX 20-1
230 °C (T2) - USX 20-2

Note:
1. Installation in accordance with the Canadian Electrical Code Part I (CEC Part I) or National Electrical
Code (NEC) as applicable.
2. Type HTSX and KSX trace heater cables are supplied with field connection and termination kits and
accessories as detailed in CSA Report 153896-2238691 (LR 79539/LR 79540) in order to create a HTSX,
USX or KSX trace heater set.
3. The hazardous location marking for the HTSX, KSX and USX electrical trace heater sets are limited by the
rating of the connection kits and accessories.
4. Type HTSX rated 480Vac, maximum withstand temperature rating of 250°C (482°F) (limited to 204℃ for
380-480Vac).
5. Type HTSX rated 480Vac, maximum maintain temperature of 150°C (302°F) (limited to 121℃ for 380-
480Vac)

APPLICABLE REQUIREMENTS

CAN/CSA-C22.2 No 130-16* Requirements for electrical resistance trace heating and heating
device sets
CAN/CSA-C22.2 No. 213 - 2016 (Ed. 2)** Nonincendive electrical equipment for use in Class I and II, Division
2, and Class III, Divisions 1 and 2 hazardous (classified) locations
(reference only)
CAN/CSA-C22.2 No.60079-0:2015(Ed. 6)* Explosive atmospheres - Part 0: Equipment - General requirements
CAN/CSA-C22.2 No. 60079-7:12* Explosive atmospheres - Part 7: Equipment protection by increased
safety “e”
CAN/CSA-C22.2 No. 60079-30-1:2014* Explosive atmospheres - Part 30-1: Electrical resistance trace
heating - General and testing requirements

IEEE 515: 2011* IEEE Standard for the Testing, Design, Installation, and
Maintenance of Electrical Resistance Trace Heating for Industrial
Applications
ANSI/ISA 12.12.01-1: 2016 (Ed. 7)** Nonincendive electrical equipment for use in Class I and II, Division
2, and Class III, Divisions 1 and 2 hazardous (classified) locations
(reference only)
ANSI/UL 60079-0: 2012 (Ed. 6)* Explosive atmospheres - Part 0: Equipment - General Requirements

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 4
Certificate: 2238701 Master Contract: 153896
Project: 80063611 Date Issued: 2021-05-04

ANSI/UL 60079-7: 2008 (Ed. 4)* Explosive atmospheres - Part 31: Equipment dust ignition protection
by enclosure “t”
ANSI/UL 60079-30-1:2017* Explosive Atmospheres – Part 30-1: Electrical Resistance Trace
Heating – General and Testing Requirements
CAN/CSA-C22.2 No. 25:1966 (R2014)* Enclosures for Use in Class II Groups E, F and G Hazardous
Locations
CAN/CSA-C22.2 No. 30:1986 (R2016)* Explosion-Proof Enclosures for Use in Class I Hazardous Locations

CAN/CSA-C22.2 No. 60529:16* Degrees of protection provided by enclosures (IP Code)

IEC 60529:1989+AMD1:1999+AMD2:2013* Degrees of protection provided by enclosures (IP Code)

CAN/CSA-C22.2 No. 61010-1-12* Safety requirements for electrical equipment for measurement,
control, and laboratory use - Part 1: General requirements
[Applies to ECM kit only]

ANSI/UL 61010-1 (Ed. 3)* Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use - Part 1: General Requirements
[Applies to ECM kit only]

CAN/CSA C22.2 No. 94.1-07* Enclosures for electrical equipment, non-environmental


considerations
CAN/CSA C22.2 No. 94.2-07* Enclosures for electrical equipment, environmental considerations

ANSI/UL 50: 2007 (Ed. 13)* Enclosures for Electrical Equipment, Non-Environmental
Considerations
ANSI/UL 50E: 2007 (Ed. 2)* Enclosures for Electrical Equipment, Environmental Considerations

* Applicable for Kits detailed in CSA Report 153896-2238691 (LR 79539/LR 79540)
** Kits applicable to HTSX/KSX in CSA report 153896-2238691. All testing requirements for integral
connections were met with test requirements in both IEEE 515 (2011) and CAN/CSA-C22.2 No. 130-16.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 5
Supplement to Certificate of Compliance

Certificate: 2238701 Master Contract: 153896

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History

Project Date Description

80063611 2021-05-04 Update CSA report 2238701to include 480VAC option for following HTSX
self-regulating models

80034609 2020-06-22 Update report number 2238701 to add USX Self-Regulating Heating Cable
as an additional model

000070126268 2017-06-20 UPDATE HTSX/KSX REPORT 2238701 TO CSA STD. 130-16.

0002247913 2010-07-22 Report Revision to a) add Div I rating, and b) include the specific T-code.

0002238701 2009-11-12 Update to 130-03 (Wiring Devices 37A) for HTSX/KSX Heating Cable.

DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 1
Certificate of Compliance
Certificate: 2238704 (LR 79539-29, LR Master Contract: 153896
79540-31)

Project: 2461611 Date Issued: September 17, 2012


Issued to: Thermon Manufacturing Company
100 Thermon Dr
San Marcos, TX 78667
USA
Attention: Roy Barth
The products listed below are eligible to bear the CSA Mark shown

D. Hawkes
Issued by: D. Hawkes

PRODUCTS
CLASS 2872 01 - HEATERS - Cable and Cable Sets
CLASS 2878 01 - HEATERS - Cable and Cable Sets - For Hazardous Locations

CLASS 2872 01 - HEATERS - Cable and Cable Sets – For Ordinary Locations

Heating cable sets as follows:

Electric parallel heating cable Type "BSX" for indoor or outdoor applications requiring a usage marking
Type -G, and Type -W for heating metal or non-metallic pipes or vessels. The BSX cables are insulated with
crosslinked polyolefin (XLPE), maximum de-energized temperature rating 185°F (85°C), maximum energized
temperature rating 150oF (65.5oC), nominal power rating up to 10 W/ft (33 W/m) at 50 °F (10 °C). BSX cables
have a voltage range of 110 – 130V ac or 208 – 277V ac. The BSX cables are supplied with a tinned copper
braid and a thermoplastic elastomer (TPE) over-jacket and can be optionally supplied with a tinned copper braid
and a fluoropolymer over-jacket (ECTFE or FEP). As an additional option, the tinned copper braid may be
substituted with a nickel-plated copper braid (-BN) without an over jacket.

Ordinary Location markings for BSX are as follows: -G, -W (all BSX Types)

DQD 507 Rev. 2012-05-22 Page: 1


Certificate: 2238704 (LR 79539-29, LR Master Contract: 153896
79540-31)

Project: 2461611 Date Issued: September 17, 2012

Notes:
1. The usage marking Type for the BSX electrical heat tracing cable sets may be additionally limited by the
rating of the connection kits and accessories.
2. Type BSX heating cable are supplied with field connection and termination kits and accessories as detailed in
CSA Report 2238691 (Thermon File No. 79539-30).

CLASS 2878 01 - HEATERS - Cable and Cable Sets - For Hazardous Locations

Class I, Div. 1 & 2, Groups A, B, C and D; Class II, Div. 1 & 2, Groups E, F and G; Ex e II; T*; -G, -W

Heating cable sets as follows:

Electric parallel heating cable Type "BSX" for indoor or outdoor applications requiring a usage marking
Type -G, and Type -W for heating metal or non-metallic pipes or vessels. The BSX cables are insulated with
crosslinked polyolefin (XLPE), maximum de-energized temperature rating 185°F (85°C) , maximum energized
temperature rating 150oF (65.5oC), nominal power rating up to 10 W/ft (33 W/m) at 50 °F (10 °C). BSX cables
have a voltage range of 110 – 130V ac or 208 – 277V ac. The BSX cables are supplied with a tinned copper
braid and a thermoplastic elastomer (TPE) over-jacket and can be optionally supplied with a tinned copper braid
and a fluoropolymer over-jacket (ECTFE or FEP). As an additional option, the tinned copper braid may be
substituted with a nickel-plated copper braid (-BN) without an over jacket.

* Hazardous location markings for BSX are as follows:

Class I, Divisions 1 and 2, Groups A, B, C, D; Class II, Divisions 1 and 2, Groups E, F, and G
T6-BSX 3-1, BSX 3-2, BSX 5-1, BSX 5-2, BSX 8-1, BSX 8-2
T5-BSX 10-1, BSX 10-2
Ex e II
T6-BSX 3-1, BSX 3-2, BSX 5-1, BSX 5-2, BSX 8-1, BSX 8-2
T5-BSX 10-1, BSX 10-2

DQD 507 Rev. 2012-05-22 Page: 2


Certificate: 2238704 (LR 79539-29, LR Master Contract: 153896
79540-31)

Project: 2461611 Date Issued: September 17, 2012

-G, -W All BSX Types

Notes:
1. The usage marking Type for the BSX electrical heat tracing cable sets may be additionally limited by the
rating of the connection kits and accessories.
2. Type BSX heating cable are supplied with field connection and termination kits and accessories as detailed in
CSA report 2238691 (Thermon File No. 79540-32).

APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No 130-03 - Requirements for Resistance Heating Cables and Heating Device Sets
Additional Requirements for Hazardous Locations:
CAN/CSA 60079-0-07 - Electrical Apparatus for Explosive Gas Atmospheres – Part 0: General Requirements
CAN/CSA E60079-7:03 - Electrical Apparatus for Explosive Gas Atmospheres – Part 7: Increased Safety “e”
IEC 62086-1 (1st Edition) - Electrical Apparatus for Explosive Gas Atmospheres- Electrical Resistance Trace
Heating; Part 1: General and Testing Requirements (reference Only)

DQD 507 Rev. 2012-05-22 Page: 3


Certificate of Compliance
Certificate: 2709489 Master Contract: 153896

Project: 70199536 Date Issued: June 12, 2019

Issued to: Thermon Inc.


100 Thermon Drive
San Marcos,
Texas 78666

Attention: Jason Anderson

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US (indicating that
products have been manufactured to the requirements of both Canadian
and US Standards) or with adjacent indicator 'US' for US only or without
either indicator for Canada only

Issued by:
B J Allen

PRODUCTS

CLASS C2258 02 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations


CLASS C2258 82 - PROCESS CONTROL EQUIPMENT-For Hazardous Locations - Certified to US Standards

Hazardous Locations rating in Canada (except mounting option OS):

Class I Div 2 Groups ABCD, Class II Div. 2 Groups FG, Class III, T4
Ex eb mb [ib] IIC T4, Ex tb IIIC T135°C

Hazardous Locations rating in U.S.A. (except mounting option OS):


Class I Div 2 Groups ABCD, Class II Div. 2 Groups FG, Class III, T4
Class 1, Zone 1, AEx eb mb [ib] IIC T4; Zone 21 AEx tb IIIC T135°C

Hazardous Locations rating in Canada (OS option):


Ex eb mb [ib] IIC T4 (see Note 4)

FF0 002

DQD 507 Rev 2018-11-12 © 2018 CSA Group. All rights reserved. Page 1
Certificate: 2709489 Master Contract: 153896
Project: 70199536 Date Issued: June 12, 2019

Hazardous Locations rating in U.S.A. (OS option):


Class 1, Zone 1, AEx eb mb [ib] IIC T4 (see Note 4)
Model: TraceNet ECM
Rated input 120 Vac (102-132 Vac), 208 Vac (188-228 Vac), or 240 Vac (204-264 Vac), 50/60 Hz
Output relay contacts rated 30 A maximum
Alarm relay contact rated 2 A, 120, 208, or 240 Vac nominal
Ambient -60 to 55°C
Enclosure Type 4X, IP66
Comm RS485/4-20 mA/CAN

Notes:
1. The TraceNet ECM catalogue number contains suffixes to denote construction options.
2. Installation in accordance with the CEC Part I or the NEC as applicable.
3. For use with Thermon Heating Cable Sets CSA Certified under LR 79539 and LR 79540.
4. The OS option has Class/Divisions equivalency (Class I Div 2 Groups ABCD, Class II Div. 2 Groups FG,
Class III, T4) according to NEC 501.5 and CEC Part I J1.2, based on the Zones Certification.

Special Conditions of Use:

1. Under certain extreme circumstances, the non-metallic enclosure of this equipment may generate an ignition-
capable level of electrostatic charge. Therefore the equipment shall not be installed in a location where the
external conditions are conducive to the build-up of electrostatic charge on such surfaces. In addition, the
equipment shall only be cleaned with a damp cloth. The manufacturer provides this information in the
installation instructions and includes a reference to the instructions on the product label.
2. The maximum wire size to the comms and alarm terminals is 1.5 mm².
3. The trace heater relay, the alarm relay, and the comms circuits have no internal fuse or any other components
that will guarantee suitability for connection to mains supply with a prospective short circuit current of
1500A. Such components must be provided in the external equipment to which the TraceNet ECM is to be
connected. The manufacturer specifies the requirement for a circuit breaker in the installation instructions.
4. The power rating of the section of trace heater within the enclosure must not exceed 20W per foot/65.6W per
meter; Installation of trace heater in accordance with Thermon instructions.

APPLICABLE REQUIREMENTS

CAN/CSA C22.2 No. 0-10 - General requirements - Canadian electrical code, part II
CAN/CSA C22.2 No. 0.4-04 (R2013) - Bonding of Electrical Equipment
C22.2 No. 25-1966 (R2009) - Enclosures for Use in Class II Groups E, F and G Hazardous
Locations
CSA C22.2 No. 94.1-07 - Enclosures for Electrical Equipment, Non-Environmental
Considerations
CSA C22.2 No. 94.2-07 - Enclosures for Electrical Equipment, Environmental
Considerations
CAN/CSA C22.2 No. 130-03 (R2013) - Requirements for Resistance Heating Cables and Heating Device
Sets
CSA C22.2 No. 213-M1987 (R2013) - Non-Incendive Electrical Equipment for Use in Class I,
Division 2 Hazardous Locations

DQD 507 Rev 2018-11-12 © 2018 CSA Group. All rights reserved. Page 2
Certificate: 2709489 Master Contract: 153896
Project: 70199536 Date Issued: June 12, 2019

CAN/CSA C22.2 No. 60079-0:11 - Explosive atmospheres - Part 0: Equipment – General


requirements
CAN/CSA C22.2 No. 60079-7:12 - Explosive atmospheres - Part 7: Equipment protection
by increased safety "e"
CAN/CSA C22.2 No. E60079-11:02 - Electrical apparatus for explosive gas atmospheres - Part 11:
Intrinsic safety “i”
CAN/CSA C22.2 No. 60079-18:16 - Explosive atmospheres - Part 18: Equipment protection by
encapsulation "m"
CAN/CSA C22.2 No. 60079-31: 15 - Explosive atmospheres - Part 31: Equipment dust ignition
protection by enclosure “t”
CAN/CSA C22.2 No. 60529-05 (R2010)- Degrees of Protection Provided by Enclosures (IP Code)
CAN/CSA C22.2 No. 61010-1-12 - Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use, Part 1: General Requirements
IEC 60529: 2013 - Degrees of protection provided by enclosures (IP Code)
ANSI/ISA 12.12.01-1: 2012 - Nonincendive Electrical Equipment for Use in Class I and II,
Div. 2, and Class III, Div. 1 and 2 Hazardous (Classified)
Locations
NEMA 250: 2008 - Enclosures for Electrical Equipment (1000 Volts Maximum)
ANSI/UL 50 (12th Ed.) - Enclosures for Electrical Equipment, Non-Environmental
Considerations
ANSI/UL 50E (1st Ed.) - Enclosures for Electrical Equipment, Environmental
Considerations
ANSI/UL 60079-0 (6th Ed.) - Explosive atmospheres - Part 0: Equipment – General
Requirements
ANSI/UL 60079-7 (4th Ed.) - Explosive atmospheres - Part 7: Equipment protection by
increased safety 'e'
ANSI/UL 60079-11 (6th Ed.) - Explosive atmospheres - Part 11: Equipment protection by
intrinsic safety “i”
ANSI/ISA/UL 60079-18: 2015 (4th Ed.) - Explosive atmospheres - Part 18: Equipment protection by
encapsulation
ANSI/ISA/UL 60079-31:2015 (2nd Ed) - Explosive atmospheres – Part 31: Equipment dust ignition
protection by enclosure “t”
ANSI/UL 61010-1 (3rd Ed.) - Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use - Part 1: General Requirements

DQD 507 Rev 2018-11-12 © 2018 CSA Group. All rights reserved. Page 3
Certificate of Compliance
Certificate: 70088957 Master Contract: 160062

Project: 70088957 Date Issued: 2016-11-23

Issued to: WEG Equipamentos Eletricos S.A.


Av Prefeito Waldemar Grubba 3000
Caixa Postal 420
Jaragua Do Sul, Santa Catarina 89256-900
BRAZIL
Attention: Daniel Garcia Peres

The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.

Ezio Migliozi
Issued by:
Ezio Migliozi

PRODUCTS
CLASS - C422801 - MOTORS AND GENERATORS-For Hazardous Locations
CLASS - C422881 - MOTORS AND GENERATORS-For Hazardous Locations - Certified to US Standards

Class I, Div. 2, Groups A, B, C and D; Class II, Div. 2, Group F and G; Temperature Coded:

Squirrel cage induction motors, three phase, Rolled steel Series, Models W01 Series, TEFC, TENV or TEAO,
random wound, 25hp max. at 60Hz or 20hp max. at 50Hz, 575V max, 70A maximum, SF 1.75 max, 2 to 8 poles,
Class B, F or H insulation, 40°C maximum ambient, , NEMA frame 48 to 256 (IEC frame 90 to 160).

The motors can be available as or with:


1. Multiple Voltages. 50Hz motors with Insulation class F and Temperature Rise 80K.
2. Inverter and/or Vector Duty, max. SF 1.00, 1000:1VT and 2:1CT.
3. Optional up to 50 or 60°C ambient:
4. TEAO Construction (“Minimum Airflow Nameplate Mandatory”).
5. Brake motor.
6. The Temperature Code is given under Tables A and B.
7. Shaft grounding ring inside motor for Class II, Division 2.

APPLICABLE REQUIREMENTS

DQD 507 Rev. 2016-02-18 Page 1


Certificate: 70088957 Master Contract: 160062
Project: 70088957 Date Issued: 2016-11-23

-CAN/CSA C22.2 No 0-10 - General Requirements - Canadian Electrical Code Part II


-CAN/CSA C22.2 No. 25-1966 - Enclosures for Use in Class II, Groups E, F and G Hazardous
Locations (Guidance)
-CAN/CSA C22.2 No. 145-11 - Electric Motors and Generators for Use in Division 1 Hazardous
Locations (Guidance)
-CAN/CSA C22.2 No 100-14 - Motors and Generators
-CAN/CSA C22.2 No 213 - M1987 - Non-Incendive Electrical Equipment for Use in Class I, Div 2 Hazardous
Locations
-NFPA 70 - US National Electric Code
-ANSI/UL 674 5th Ed. - Electric Motors and Generators for Use in Division 1 Hazardous
Locations (Guidance)
-ANSI/UL 1604 3rd Ed - Electric Equipment for Use in Class I and II, Division 2 and Class III
Hazardous Location
-ANSI/UL 1004-1: 2011 - Motors and Generators
-ANSI/UL 1836: 2014 - Outline of Investigation for Electric Motors and Generators for
Use in Class I, Division 2 and Class II, Division 2 Hazardous
(Classified) Locations.

MARKINGS

The manufacturer is required to apply the following markings:


 Products shall be marked with the markings specified by the particular product standard.
 Products certified for Canada shall have all Caution and Warning markings in both English and French.

Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.

The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.

Nameplate adhesive label material approval information:

Manufacture: 3M (ULMH16411, CSA 99316)


Label type: 7871 and 7350
Material: Polyester
Printing Method: Thermal Transfer

The following shall be marked on each motor on an adhesive label as above or a riveted metal plate in a permanent,
legible manner and located where readily visible after assembly:

- Submitter’s name, Master Contract or Trade Mark;


- Type or (model) designation (as applicable);

DQD 507 Rev. 2016-02-18 Page 2


Certificate: 70088957 Master Contract: 160062
Project: 70088957 Date Issued: 2016-11-23

- Hazardous Location designation: Class I, Div. 2, Groups A, B, C and D (and additionally optional
Class I, Zone 2, Groups IIC, IIB, IIA) and Class II, Div. 2, Groups F and G);
- Temperature Code or Maximum Operating Temperature;
- Complete electrical rating in horsepower, volts, amperes, hertz;
- Class insulation;
- Ambient temperature;
- Rated speed;
- Number of phase;
- Service factor (if greater than 1.0);
- Enclosure designation;
- Space heater nameplate (when applicable) shall be marked with voltage and watts ratings.
- CSA Monogram with the C US indicator.
- Machine application (e.g. inverter-duty motor), (where applicable);
- Speed range over which the machine is designed to operate, or if marked with a nominal speed at a
nominal frequency, the frequency range for which the machine is designed to operate; (where
applicable);
- Type(s) of torque application for which the machine is designed (e.g. VT (variable torque), CT
(constant torque), CHP (constant horsepower); (where applicable);
- Types of inverter with which the machine is intended to be used (e.g. VPWM (voltage source pulse
width modulated) (where applicable);

DQD 507 Rev. 2016-02-18 Page 3


Supplement to Certificate of Compliance

Certificate: 70088957 Master Contract: 160062 (050962_C_000)

The products listed, including the latest revision described below,


are eligible to be marked in accordance with the referenced Certificate.

Product Certification History


Project Date Description

70088957 2016-11-23 Original certification to cover Model W01 rated 25hp max., 60Hz, 575V
max, 70A maximum, SF 1.75 max, 2 to 8 poles, Class B, F or H insulation,
40°C maximum ambient, , NEMA frame 48 to 256 (IEC frame 90 to 160) for
Class I, Div 2, Groups A, B, C and D; Class II, Div 2, Groups F and G
hazardous locations.

DQD 507 Rev. 2016-02-18 Page 1


QPS Evaluation Services Inc
Testing, Certification and Field Evaluation Body
Accredited in Canada, the USA, and Internationally
Page 1 of 2

File
LR1380

CERTIFICATE OF COMPLIANCE
(ISO TYPE 3 CERTIFICATION SYSTEM)

Issued to Thompson Valves Ltd.

Address 17 Balena Close


Creekmoor, Poole
Dorset, BH17 7EF
UK

Project Number LR1380-2R7

Product Electrically Operated Valves

Model Number ICO3S (Explosion-Proof), ICO3S (Intrinsically Safe), ICO4S, ICO4E and
Maxseal POV

Ratings ICO3S (Explosion-Proof):


Class I, Division 1, Groups B, C, D; Temperature Code T4/T6
Class I, Zone 1, AEx d IIC T4/T6
Zone 1, Ex d IIC T4/T6 Gb
Ta = -60/20° to +40/50/90°C
24-240Vac, 40-60 Hz or 12 – 240 Vdc and up to 14 W
Max. pressure 350 bar (5076 psi), Dual Seal, Type 4X / IP66/X8

ICO3S (Intrinsically Safe):


Class I, Division 1, Groups A, B, C, D; Temperature Code T4/T6
Class I, Zone 0, AEx ia IIC T4/T6
Zone 0, Ex ia IIC T4/T6 Gb
T6 = -**ºC to +50ºC
T4 = -**ºC to +69ºC
“**” = either -60ºC or -50ºC or -40ºC or -30ºC dependant on O-ring gasket
materials
maximum operating pressure is 350 bar (5076 psi), Dual Seal

Rated Ui = 28Vdc, Ii = 300mA, Ci = 0, Li = 0 Pi = 1.3 W.

ICO4S:
Class I, Division 1, Groups B, C, D; Temperature Code T4/T6
Class I, Zone 1, AEx d IIC T4/T6
Zone 1, Ex d IIC T4/T6 Gb
Ta = -60/30° to +48/90°C
110-440Vac, 40-60 Hz or 12 – 240 Vdc and up to 18 W
Max. pressure 300 bar (4351 psi), Dual Seal, Type 4X / IP66/X8

Maxseal POV
24-240Vac, 40-60 Hz or 12 – 240 Vdc and up to 14 W
110-440Vac, 40-60 Hz or 12 – 240 Vdc and up to 18 W
Max. pressure 82 bar, Media temperature range (0°C to 150°C)

81 Kelfield St., Units 7-9, Toronto, ON M9W 5A3 Tel: 416-241-8857; Fax: 416-241-0682
www.qps.ca
QSD 34HL Rev 00
QPS Evaluation Services Inc
Testing, Certification and Field Evaluation Body
Accredited in Canada, the USA, and Internationally
Page 2 of 2

File
LR1380

ICO4E:
Class I, Division 1, Groups A, B, C, D; Temperature Code T4/T6
Class I, Zone 1, AEx d IIC T4/T6
Ex d IIC T4/T6 Gb
-60 /-55/-50/-40/-35/-30°C to +43/79/90 ºC
110-440Vac, 40-60 Hz or 12 – 240 Vdc and up to 20 W.
Maximum operating pressure is 300 bar (4351 psi), Dual Seal.
Type 4X / IP66/X8

Applicable Standards ICO3S(Explosion-Proof), ICO4S, Maxseal POV


CSA C22.2 No. 30-M1986 (R2007), C22.2 No 139-2013,
CSA C22.2 No. 142-1987 (R2014), CSA C22.2 No. 60079-0-11,
CSA C22.2 No. 60079-1-11, ANSI/ISA – 12.27.01:2011
UL 429 7th ed., UL 1002 7th ed, UL1203-5th ed., FM 3600-2011, FM3615-
2006, FM3810-2005, ANSI/ISA-60079-0-2013, ANSI/ISA-60079-1-2013,
ANSI/NEMA 250-1991, ANSI/IEC 60529-2004

ICO4E
CSA C22.2 No. 30-M1986 (R2007), C22.2 No 139-2013,
CSA C22.2 No. 60079-0-11, CSA C22.2 No. 60079-1-11,
ANSI/ISA – 12.27.01:2011, UL 429 7th ed., UL 1002 7th ed.,
FM 3600-2011, FM3615-2006, FM3810-2005, ANSI/ISA-60079-0-2013,
ANSI/ISA-60079-1-2013, ANSI/NEMA 250-1991, ANSI/IEC 60529-2004

ICO3S (Intrinsically Safe)


C22.2 No. 157-92 (R2016), C22.2 No 139-2013, C22.2 No. 60079-0-11, C22.2
No. 60079-11-14, ANSI/ISA – 12.27.01:2011, UL 429 7th Edition, UL 1002 7th
Edition, FM 3600-2011, FM 3610-2015, FM 3810-2005, ANSI/ISA-60079-0-
2013, ANSI/ISA 60079-11-2014, ANSI/NEMA 250-1991, ANSI/IEC 60529-2004

Factory/Manufacturing Location Same as Applicant

Statement of Compliance: The product(s) identified in this Certificate and described in the Report covered under the
above referenced project number have been investigated and found to be in compliance with the relevant requirements of
the above referenced standard(s). As such, they are eligible to bear the QPS Certification Mark shown below, in accordance
with the provisions of QPS’s Service Agreement.

Issued By: Dave Adams, P.Eng.


Manager, Hazardous Locations Dept. [Ex Equipment]

Signature: Date: July 16, 2018

81 Kelfield St., Units 7-9, Toronto, ON M9W 5A3 Tel: 416-241-8857; Fax: 416-241-0682
www.qps.ca
QSD 34HL Rev 00
CERTIFICATE OF COMPLIANCE
Certificate Number E312544
Report Reference E312544-20091202
Issue Date 2020-JUNE-25

Issued to: MOXA Inc


4th Fl 135 Lane 235 Baoqiao Rd
Xindian District
New Taipei City
231 TAIWAN

This certificate confirms that PROGRAMMABLE CONTROLLERS FOR USE IN


representative samples of HAZARDOUS LOCATIONS
See Next Page

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: Standard No. ANSI/ISA 12.12.01-2013, Nonincendive


Electrical Equipment for Use in Class I and II, Division 2
and Class III, Divisions 1 and 2 Hazardous (Classified)
Locations
Standard No. CAN/CSA C22.2 No. 213-M1987, Non-
incendive Electrical Equipment for Use in Class I, Division 2
Hazardous Locations
Additional Information: See the UL Online Certifications Directory at
https://iq.ulprospector.com for additional information.

This Certificate of Compliance does not provide authorization to apply the UL Mark. Only the UL Follow-Up
Services Procedure provides authorization to apply the UL Mark.

Only those products bearing the UL Mark should be considered as being UL Certified and covered under UL’s
Follow-Up Services.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 2
CERTIFICATE OF COMPLIANCE
Certificate Number E312544
Report Reference E312544-20091202
Issue Date 2020-JUNE-25

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

Models/Product

USL, CNL – Class I, Division 2, Groups A, B, C, and D Hazardous Locations

Programmable Controller Communication Interface Units, Models EDS-205A, EDS-205A-T, EDS-205A-


M-SC, EDS-205A-M-SC-T, EDS-205A-M-ST, EDS-205A-M-ST-T, EDS-205A-S-SC, EDS-205A-S-SC-T.
Models EDS-208A, may be followed by –M-SC, -M-ST, -MM-ST, –MM-SC, -S-SC, -SS-SC, may be
followed by –T.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 2
QQPX8.E317914 - Power Supplies for Use in Hazardous Locations Certified for Cana... Page 1 of 1

QQPX8.E317914
Power Supplies for Use in Hazardous Locations Certified for Canada - Component
Page Bottom

Power Supplies for Use in Hazardous Locations Certified for Canada - Component

See General Information for Power Supplies for Use in Hazardous Locations Certified for Canada - Component

ABB STOTZ-KONTAKT GMBH E317914


HAUPTSTRASSE 14-16
78132 HORNBERG, GERMANY

Class 2 power supplies, Model(s) CP-E12/1.5, CP-E15/1.2, CP-E24/0.75, CP-E5/3.0

Class I, Division 2, Groups A, B, C and D, Model(s) CP-E 12/10.0, CP-E 24/10.0, CP-E 24/20.0, CP-E 24/5.0, CP-E 48/10.0, CP-E 48/5.0, CP-T
24/10.0, CP-T 24/20.0, CP-T 24/40.0, CP-T 24/5.0, CP-T 48/10.0, CP-T 48/20.0, CP-T 48/5.0

Class I, Division 2, Groups A, B, C and D (switching), Model(s) CP-E12/2, CP-E12/5.0, CP-E24/1.25, CP-E24/2.5, CP-E48/0.62, CP-E48/1.25,
CP-E5/6.0

Marking: Company name, model designation and Recognized Component Mark for Canada, .
Last Updated on 2009-10-26

Questions? Notice of Disclaimer Page Top

Copyright © 2009 Underwriters Laboratories Inc.®

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the
data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright ©
2009 Underwriters Laboratories Inc.®"

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?nam... 10/27/2009