STATION :

CIRCUIT :
BAY ID :
P (MVA) RATING = 30000000 SEC. FULL LOAD CURR IN = 1574.63783329834
V RATING = 11000 PRIMARY FAULT CURR IFP = 23619.5674994751
MAIN CT RATIO = 1600 SEC. FAULT CURR IFS = 14.762229687172
Vk MAX = 110 SEC. FAULT VOLTAGE VF = IFS X (RCT MAX + RL MAX)
CLASS = PX VF = 81.9303747638043
NEUTRAL CT RATIO = 1600 VF (LIMIT) = 82
Vk MAX = 230 Ir (RELAY SETTING) = 0.2
RCT A = 5.3 RELAY BURDEN (VA) = 1
RCT B = 5.3 RS REQUIRED = (Vf/Ir - (VA/(IrXIr))
RCT C = 5.3 RS REQUIRED = 385
RCT N = 5.3
RCT MAX = 5.3
RL A1 = 0.25
RL B1 = 0.25
RL C1 = 0.25
RL A2 = 0
RL B2 = 0
RL C2 = 0
RL MAX = 0.25
783329834 TX rating /(1.732 x V rating)
674994751 Sec full load current x 15 %
229687172 Primary fault current / main CT ratio
MAX + RL MAX)
747638043 calculated voltage level
82 relay voltage setting
0.2 relay current setting
1 relay burden
VA/(IrXIr)) VF/ RELAY SETTING - ( RELAY BURDEN/ RELAY SETTING X RELAY SETTING)
385