PROJECT GRANDLUCKY SUMBAWA Jakarta, 30 September 2022

FK21L-00XX PT. ANEKA FROZE TRIUTAMA


COLDROOM CHILLER
Evap.
Room Operating Cooling Capacity Cooling Capacity EVAP
Description Eksternal Dimension ( P x L x T ) m Temp Volume [m3] CDU - BITZER Evaporator Type safety factor ( % )
No Temp ( C ) required (watt) ( Watt)
(°C)
C1 Bahan Makanan Chiller 3.11 x 1.6 x 3.3 +5° -10 16.42 1,870 GACC RX 031.1/1-70.E-1846122M 2,700 44.4
C2 Meat Fish Chiller 3.1 x 2.5 x 3.3 -2° -10 25.58 2,799 GACC RX 031.1/2-70.E-1846007M 4,400 57.2
C3 Perishable Chiller 4.75 x 3.1 x 3.3 -2° -10 48.59 3,972 GACC RX 031.1/2-70.E-1846000M 5,400 36.0
C4 Vegetable Chiller 3.7 x 3.1 x 3.3 +5° -10 37.85 3,584 GACC RX 031.1/2-70.E-1846007M 4,400 22.8
C5 Fruit Chiller 3.7 x 2.4 x 3.3 +5° -10 29.3 3,037 GACC RX 031.1/2-70.E-1846007M 4,400 44.9

Total 15,262
SHOWCASE CHILLER 13,392 2560 15,952
Evap. Total Cooling
Case Size Operating
Description Brand Model Temp Cap. Required CDU - EMERSON CDU - BITZER Cooling Capacity CDU ( Watt) safety factor ( % )
No. (feet) temp. C
(C) (W)
1 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
2 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
3 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
4 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
5 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
6 Multideck Chiller Bonnet Rock L 12 0/+5° -10 4880 - -
7 SOC Meat Open Type Bonnet Melo RCA LS L250 -2 / +2 C -10 1280 - -
8 SOC Fish Open Type (SS) Bonnet Melo RCA LS L250 -2 / +2 C -10 1280 - -
9 Multideck Chiller Open Plug in Bonnet Offlip 6 0/+5° -10 - - -
10 Multideck Chiller Open Plug in Bonnet Offlip 6 0/+5° -10 - - -

Total 31,840

Cooling Cap. Calculation (S.CASE & CR) 47,102


Medium Temperature (R404a)
Total Cooling Capacity Required = 47,102 Watts
Bitzer Compressor selected = 3 x 4PES-12Y
Nominal Cooling Capacity at Evaporating Temp -10 C & Condensing Temp +45 C = 73,600 Watt
Excess Capacity = 26,498 Watts
Safety factor = 56.26 %
Condenser Type = GCHC RD 063.2/13-66-4242580M (SPECIAL COATING) (1 Unit)
Nominal Cooling Capacity at Condenser 136,300 Watt
COLDROOM FREEZER
Evap.
Room Operating Cooling Capacity Cooling Capacity EVAP
Description Eksternal Dimension ( P x L x T ) m Temp Volume [m3] CDU - BITZER Evaporator Type safety factor ( % )
No Temp ( C ) required (watt) ( Watt)
(°C)
F1 Meat Fish Freezer 3.7 x 2.1 x 3.3 -18/-25° -30 25.65 2,539 GACC RX 031.1/2-70.E-1846000M 3,900 53.6

Total 2,539

Cooling Cap. Calculation FREEZER 2,539


Low Temperature (R404a)
Total Cooling Capacity Required = 2,539 Watts
Bitzer Compressor selected = 1 x 2CES- 3Y
Nominal Cooling Capacity at Evaporating Temp -30 C & Condensing Temp +45 C = 3,320 Watt
Excess Capacity = 781 Watts 5,710 kW
Safety factor = 30.76 % SF 128
Condenser Type = G.030.1-N (SPECIAL COATING) (1 Unit)
Nominal Cooling Capacity at Condenser 13,000 Watt

COLDROOM FREEZER
Evap.
Room Operating Cooling Capacity Cooling Capacity EVAP
Description Eksternal Dimension ( P x L x T ) m Temp Volume [m3] CDU - BITZER Evaporator Type safety factor ( % )
No Temp ( C ) required (watt) ( Watt)
(°C)
F2 Perishable Freezer 4.3 x 3.7 x 3.3 -18/-25° -30 52.5 3,486 GACC RX 031.1/3-70.E-1845991M 5,200 49.2

Total 3,486

Cooling Cap. Calculation FREEZER 3,486


Low Temperature (R404a)
Total Cooling Capacity Required = 3,486 Watts
Bitzer Compressor selected = 1 x 4EES- 4Y
Nominal Cooling Capacity at Evaporating Temp -30 C & Condensing Temp +45 C = 4,540 Watt
Excess Capacity = 1,054 Watts 7,860 kW
Safety factor = 30.24 % SF 152
Condenser Type = G.050.2-N (SPECIAL COATING) (1 Unit)
Nominal Cooling Capacity at Condenser 19,800 Watt

COLDROOM FREEZER
Evap.
Room Operating Cooling Capacity Cooling Capacity EVAP
Description Eksternal Dimension ( P x L x T ) m Temp Volume [m3] CDU - BITZER Evaporator Type safety factor ( % )
No Temp ( C ) required (watt) ( Watt)
(°C)
F3 Bakery Freezer 2.2 x 3.36 x 3.3 -18/-25° -30 24.4 2,279 GACC RX 031.1/2-70.E-1846000M 3,900 71.1

Total 2,279

Cooling Cap. Calculation FREEZER 2,279


Low Temperature (R404a)
Total Cooling Capacity Required = 2,279 Watts
Bitzer Compressor selected = 1 x 2CES- 3Y
Nominal Cooling Capacity at Evaporating Temp -30 C & Condensing Temp +45 C = 3,320 Watt
Excess Capacity = 1,041 Watts 5,710 kW
Safety factor = 45.68 % SF 128
Condenser Type = G.030.1-N (SPECIAL COATING) (1 Unit)
Nominal Cooling Capacity at Condenser 13,000 Watt

SHOWCASE FROZEN
Evap. Total Cooling
Case Size Operating
Description Brand Model Temp Cap. Required CDU - EMERSON CDU - BITZER Cooling Capacity CDU ( Watt) safety factor ( % )
No. (feet) temp. C
(C) (W)
1 Frozen Glassdoor Bonnet Crystal 4D -18/-20° -30 2,020 - -
2 Frozen Glassdoor Bonnet Crystal 4D -18/-20° -30 2,020 - -
3 Frozen Glassdoor Bonnet Crystal 4D -18/-20° -30 2,020 - -

Total 6,060

Cooling Cap. Calculation FREEZER 6,060


Low Temperature (R404a)
Total Cooling Capacity Required = 6,060 Watts
Bitzer Compressor selected = 2 x 4CES- 6Y
Nominal Cooling Capacity at Evaporating Temp -30 C & Condensing Temp +45 C = 11,040 Watt
Excess Capacity = 4,980 Watts
Safety factor = 82.18 %
Condenser Type = G.100.2-N (SPECIAL COATING) (1 Unit)
Nominal Cooling Capacity at Condenser 38,000 Watt