DS1311 Engineered Dry Chemical

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Dry Chemical

Engineered Fire Suppression System


The Janus Fire Systems® Engineered Dry Chemical Fire Suppression System utilizes ABC dry
chemical as the extinguishing medium. ABC or Multi-Purpose dry chemical is a specially fluidized
and siliconized mono-ammonium phosphate. It chemically insulates Class A fires by melting at
approximately 350°F and coating surfaces to which it is applied. It smothers and breaks the chain
reaction of Class B fire and will not conduct electricity. Each system consists of the following com-
ponents and their associated accessories:

1. Agent Storage Components - Storage components consist of the cylinder assembly(s), which
contains the ABC dry chemical and the cylinder bracket(s), which holds the cylinder assembly
securely in place.
2. Agent Distribution Components - Distribution components consist of the discharge nozzles
used to introduce the ABC dry chemical into a protected hazard along with the associated pip-
ing system used to connect the nozzles to the cylinder assembly.
3. Trim Components - Trim components complete the installation of the suppression system and
consist of connection fittings, pressure gauge, low-pressure supervisory switch, electric valve
actuator, and manual valve actuator.
4. Multi-Cylinder Arrangement Components - Multi-cylinder arrangement components consist
of the pneumatic valve actuator(s), actuation check valve, vent check, actuation hose, and fit-
tings required for a multiple cylinder arrangement.
5. Supplemental Components - Supplemental components include the discharge pressure
switch and manifold check valve. They supplement the core equipment or complete a specific
multi-cylinder configuration.
6. Control Panel - This device monitors the condition of the electric actuator, detectors, warning
devices, cylinder pressure, and any manual release and abort stations. All electric or electronic
devices must connect to the control panel in order to function.
7. Detection and Alarm Devices - Detection devices coupled with manual release and abort
stations maximize system efficiency while audible and visual alarm devices alert staff of alarm
conditions.

Typical Large Dry Chemical System Layout

Alarm
Warning Sign

Electric
Valve
Actuator

Smoke Detector Cylinder Valve


Discharge Nozzle
Control Panel

Manual Release
& Abort

Cylinder Bracket
Agent Storage Cylinder

DS1311 Revised: 18-Feb-2022 © 2016 Janus Fire Systems. All rights reserved (2/2016) Janus Design Suite® and Janus Fire Systems® are registered trademarks of Janus Fire Systems.
EQUIPMENT DESCRIPTION
The ABC dry chemical is stored in cylinder assemblies designed specifically for the application. To
ensure optimal performance, each cylinder is superpressurized with dry nitrogen to 500 psi (34.48
bar) at 70°F (21°C). An identification label is affixed to the cylinder body indicating the fill quantity
of ABC dry chemical, charging pressure, date of fill, and fill station.

The cylinder assembly is composed of a cylinder, dip tube, cylinder valve, pressure vent port, agent
fill port, and (in the 1000 lb cylinder) a rupture disc. Cylinders are available in three capacities and
are filled in 50 pound (22.7 kg) increments in the fill ranges as indicated below.

Nominal Fill H1 H2 H3 D1 D2 Empty


Cylinder P/N Range Weight
Capacity (lbs) in mm in mm in mm in mm in mm lb kg
200 lb 26301 50 - 200 42.8 1086 38.7 982 19.8 503 16.0 406 17.9 454 160 72.6
600 lb 25147 200 - 500 50.8 1290 44.5 1130 21.5 546 24.0 610 25.9 657 346 157.0
1000 lb 25148 200 - 900 61.4 1559 53.7 1365 30.0 762 30.0 762 31.9 810 471 213.6

Cylinder Valve: The automatic release of ABC dry


chemical is controlled by a forged brass, differential
pressure operated cylinder valve connected to the
neck of the cylinder. The valve assembly is shipped
Agent Fill with an anti-recoil safety device installed in the dis-
Port charge outlet and chained to the cylinder valve.
Rupture Disc
Dip Tube: A threaded, rigid dip tube extends from the
(1000 lb only)
cylinder neck down to its bottom.
Cylinder: The light walled, welded seam cylinder
is manufactured according to the requirements of
the U.S. Department of Transportation (USDOT) for
H2 compressed gas for compressed gas. Internal neck
threads allow connection of the cylinder valve. The
H1 cylinder is designed for mounting in a vertical position
only.
Pressure Vent Port: The pressure vent port is lo-
D2 cated on the cylinder body. It is used to release nitro-
gen from a filled cylinder in the event the agent fill port
H3
must be opened.
Agent Fill Port: The agent fill port is located at the top
of the cylinder. It is used to fill the cylinder with ABC
dry chemical agent.
Rupture Disc (1000 lb Cylinder Only): A frangible
D1 rupture disc is fitted to the cylinder body. It functions
as an emergency relief device in the event of exces-
sive pressure within the cylinder. Its rupture point is
between 850 psi (58.6 bar) and 1000 psi (68.9 bar).

Wall Mount Cylinder Bracket Assembly


Cylinder (P/N See Chart)
Bracket P/N
Capacity
200 lb 18535 Cylinder stability is ensured by the cylinder bracket as-
sembly, consisting of one strap and rail with accompa-
600 lb 18536 nying bolts, nuts, and washers. The rail is slotted for
1000 lb 18537 ease of mounting with fasteners provided by the installer.

DS1311 Revised: 18-Feb-2022 Page 2 of 14


Valve Actuation
Connection

Discharge
Outlet

Each cylinder valve has the following features:

Pressure Gauge
Connection Valve Actuation Connection: A threaded connection
1000 lb Valve - Side View located on top of the cylinder valve serves as the at-
Safety tachment point for the electric (primary) or pneumatic
Pressure Gauge Cap (secondary) valve actuator.
Anti-Recoil
Connection Safety Device

Pressure Gauge Connection: A female connec-


tion serves as the attachment point for the pressure
gauge. It is fitted with an internal check valve to allow
removal of the gauge while the cylinder is pressurized.

Low-Pressure Supervisory Switch Connection: A


Low-Pressure female connection serves as the attachment point for
Auxiliary
Port Plug
Supervisory Switch the low-pressure supervisory switch. An internal check
Connection
valve allows for removal of the pressure switch while
the cylinder is pressurized.
1000 lb Valve - Top View
Valve Actuation
Connection Discharge Outlet (1000 lb only): A 3 in (80 mm)
grooved connection serves as the attachment point
for discharge piping.

Discharge Discharge Outlet (200, 600 lb only): A 2 in (50 mm)


Outlet
grooved connection serves as the connection point for
discharge piping.

Auxiliary Port: A 1/4 in (8 mm) FNPT port on the side


of the valve (shipped with a pipe plug) is not currently
utilized in the dry chemical system. The pipe plug shall
Pressure Gauge
Connection
remain in place at all times. DO NOT REMOVE THE
PIPE PLUG.
200, 600 lb Valve - Side View
Rupture Disc (not on 1000 lb valve): A frangible rup-
Pressure Gauge
Connection
Safety ture disc is fitted to the cylinder valve body. It functions
Cap Anti-Recoil
Safety Device
as an emergency relief device in the event of exces-
sive pressure within the cylinder. Its rupture point is
between 850 psi (58.6 bar) and 1000 psi (68.9 bar).
Rupture
Disc

Auxiliary Low-Pressure
Port Plug Supervisory Switch
Connection
200, 600 lb Valve - Top View

DS1311 Revised: 18-Feb-2022 Page 3 of 14


TRIM COMPONENTS
Trim components are required to operate the clean agent cylinder(s).
2” Grooved to NPT
Adapter Nipple
(50 mm)
Grooved Coupling
(P/N 18474)
(200, 600 lb Cylinders - P/N 18555)
200, 600 lb Cylinders Only
(1000 lb Cylinders - P/N 18554)

Manual Valve
Actuator
(P/N 17001)

Grooved Elbow
(200, 600 lb Cylinders - P/N 18551)
Electric Valve Actuator
(1000 lb Cylinders - P/N 18550)
w/ Supervisory Limit Switch
(P/N 20722)
Low-Pressure Supervisory Switch
Pressure Assembly
Vent Port (P/N 22946)
Grooved Coupling
Shipped with Affixed to
Cylinder Valve Cylinder

Discharge
Outlet
Anti-Recoil
Safety Cap
Shipped with Rupture Disc
Cylinder Valve Affixed to
as part of Cylinder Valve
Anti-Recoil Safety Device Except on 1000 lb
Cylinders

Pressure
Gauge
Assembly
(P/N 25804)

Agent Fill Port


Affixed to
Cylinder

Discharge Connection Fitting


A 2 in (50 mm) grooved elbow and NPT adaptor connects to the grooved cylinder outlet adapter for
200 and 600 lb capacity valves utilizing the coupling factory installed to retain the anti-recoil safety
device. A 3 in (80 mm) grooved elbow is used for the 1000 lb valve. All other pipe and fittings be-
yond the 3 in (80 mm) and 2 in (50 mm) elbow are to be supplied by the installer.

Low-Pressure Supervisory Switch Assembly


(P/N 22946)
36” The low-pressure supervisory switch continuously moni-
(914 mm)
Leads tors the pressure of the cylinder. The contact configura-
tion is single pole, single throw (SPST) with contacts rated
1.5 Amps at 24 VDC. Should the cylinder pressure drop
to approximately 440 psi (30.34 bar), the switch contacts
will close transmitting an abnormal signal to the system
control panel.

Pressure Gauge Assembly (P/N 25804)

A pressure gauge for each cylinder allow for visually moni-


toring the internal pressure condition of the cylinder assem-
bly.

DS1311 Revised: 18-Feb-2022 Page 4 of 14


Electric Valve Actuator
w/ Supervisory Limit Switch (P/N 20722)
The electric valve actuator attaches to a single cylinder valve
or to the Remote Pneumatic Actuation/Bracket Kit in multi-
DIN Connector cylinder systems at the actuation connection and is utilized to
with 1/2” (15 mm) NPS
Female Conduit Hub
automatically open the cylinder valve upon receipt of a signal
with 40” (1016 mm) leads from the control panel or other source. It operates between
17 and 30 VDC and consumes 500 mA (.5 Amps) at 24 VDC
nominal with a maximum supervisory current of 30 mA (0.03
Amps).
The electric valve actuator body is steel construction with a
Knurled brass knurled swivel nut and a stainless steel actuation pin
Swivel Nut that depresses the valve core when energized. In the model
with supervisory limit switch, the switch contacts are normally
Emergency closed when the actuator is not installed onto the cylinder
Release Button valve and open when the actuator is fully installed onto the
valve actuation connection at the top of the cylinder valve.

Manual Valve Actuator (P/N 17001)


A manual valve actuator attaches to the top of the electric
valve actuator and provides a means to manually open the
Ring Pin cylinder valve. The manual valve actuator consists of a brass
body, stainless steel actuation pin, and steel safety ring pin.
To discharge the primary cylinder manually, the ring pin is re-
moved and the emergency release button is depressed forc-
ing the pin in the electric valve actuator to depress the valve
core of the cylinder valve. All other connected cylinders will
Knurled Nut be opened pneumatically.

MULTI-CYLINDER ARRANGEMENT COMPONENTS


Up to 16 cylinders may be installed in a single arrangement, piloted from a remote nitrogen actuation
cylinder with a maximum length of 160 ft (48.76 m) of pilot actuation hose or tubing extending from
the primary cylinder in either direction. A typical arrangement is shown below.

40” Flex Hose


(1016 mm) Discharge Manifold
Pilot Actuation 2” (50 mm) (P/N 18651) (Provided By Installer)
Discharge Mid Line Tee Manifold Pneumatic Male NPT
Pressure (P/N 18622) Check Valve Valve Actuator Adapter Pilot
Switch (P/N 18546) (P/N 17019) (P/N 18625) Actuation
(P/N 97428) Manual
Valve End Line
Actuator Tee
(P/N 17001) (P/N 18611)

Male NPT
Adapter
Vent Check
(P/N 18625)
(P/N 10173)
Electric
Valve Actuator
(P/N 20722)

Remote
Pneumatic
Actuation/Bracket
Kit
(P/N 97643)

Remote Nitrogen Actuation Cylinder


(26311 - w/o Supervisory Port)
(26310 - w/ Supervisory Port)

Typical Primary and Secondary Cylinder Arrangement


DS1311 Revised: 18-Feb-2022 Page 5 of 14
Remote Nitrogen Actuation Cylinder
(P/N 26311)
Actuation
Connection Port / The remote nitrogen actuation cylinder is pressurized
Discharge Outlet
with nitrogen to 500 psi (34.47 bar). A pressure gauge
is permanently affixed to the base of the cylinder. The
actuation port of the cylinder is fitted with an internal
Schrader valve that is upset when the remote pneumatic
Pressure actuation/bracket kit is actuated, causing the cylinder to
open. An optional model (P/N 26310) can be fitted with a
Gauge

supervisory pressure switch.


Actuation
Connection Port
Shipped with Cap Remote Pneumatic Actuation/Bracket Kit
(P/N 97643)
Outlet Port
Shipped
A remote pneumatic actuation/bracket kit is installed with
with Plug the remote nitrogen actuation cylinder to both support the
Outlet Port
Shipped with cylinder and to allow the actuation of the cylinder through
Male NPT
Actuation Adapter
the electric or manual pneumatic actuators. The remote
Connection
Port
pneumatic actuation/bracket kit includes back channel
Cylinder for installing the assembly.
Strap

1/4” (8 mm) FNPT Pneumatic Valve Actuator (P/N 17019)

On multiple cylinder systems the electric valve actua-


tor will actuate the remote nitrogen cylinder and then,
in a rapidly occurring sequence, the pneumatic valve
actuator(s) will open all other cylinders using pressure
from the nitrogen cylinder.

A pneumatic valve actuator attaches to the valve actu-


ation connection of each secondary cylinder. It receives
pressure from the remote nitrogen cylinder via the out-
let port of the remote pneumatic actuation/bracket kit. It
is brass with a brass piston and pin.
Knurled Nut
Vent Check (P/N 10173)
The vent check is a safety device with 1/4 in (8 mm)
MNPT threads that is to be installed in the pilot actua-
tion line downstream of the final cylinder. It is used to
bleed off pressure that may accumulate in the pilot actua-
tion hose or piping minimizing the chance of inadvertent
pressurization of the pneumatic actuators or discharge
1/4” (8 mm)
MNPT pressure switch.
Male NPT Adapter (P/N 18625)
A 1/4 in (8 mm) 37° male JIC by MNPT adapter fits into
the pilot actuation end line tee of the final secondary cyl-
inder to facilitate the attachment of the pilot actuation
line. It also may be utilized to allow the attachment of flex
1/4” (8 mm) 1/4” (8 mm)
MNPT 37° Male JIC
hose to the discharge pressure switch.

Pilot Actuation Mid Line Tee (P/N 18622)


A 1/4 in (8 mm) 37° male JIC by MNPT brass branch tee
is utilized to attach the pilot actuation line to the pneu-
1/4” (8 mm) matic valve actuator.
37° Male JIC 1/4” (8 mm)
MNPT

DS1311 Revised: 18-Feb-2022 Page 6 of 14


Pilot Actuation End Line Tee (P/N 18611)
A 1/4 in (8 mm) FNPT by MNPT brass branch tee mounts
to the final pneumatic valve actuator to facilitate attach-
ment of the vent check to the pilot actuation line.
1/4” (8 mm) 1/4” (8 mm)
FNPT MNPT

Flex Hose (P/N See Chart)


Flex hoses are 3/16 in (7 mm) Teflon® lined stainless
steel wire braided hoses of varying lengths with 1/4 in
(8 mm) 37° female JIC flare fittings. They are utilized to
interconnect cylinders when a secondary arrangement is
L required. A 1/4 in (8 mm) 37° male JIC flare x male JIC
flare adapter (P/N 18777) is available to connect lengths
of flex hose together.

P/N Hose Length (L)


18648 16 in (406 mm)
18649 24 in (610 mm)
18650 34 in (864 mm)
18651 40 in (1016 mm)

Manifold Check Valve (P/N See Chart)


In a multiple cylinder arrangement where the secondary
and primary cylinders share a common manifold or in a
main / reserve arrangement, a manifold check valve must
be placed between the discharge outlet of each cylinder
and the discharge manifold to prevent back flow from the
manifold should the system be inadvertently discharged
L when one or more cylinders are disconnected for main-
tenance. The check valve required are indicated in the
chart below.

Manifold Check Check Valve


Cylinder Size Length (L)
Valve P/N Outlet Size
200 lb, 500 lb 18546 5.625 in (143 mm) 2 in NPT
1000 lb 18538 11.5 in (292 mm) 3 in Grooved

DS1311 Revised: 18-Feb-2022 Page 7 of 14


GENERAL PURPOSE AND INDUSTRIAL HAZARDS
Typically, general purpose and industrial hazards are protected by either total flooding an en-
closure with dry chemical or locally applying the dry chemical to the hazard directly. Depending
on the type of hazard being protected the following nozzles can be used in applications that
meet the classification for general purpose and industrial hazards:

a. Local Application – Overhead: This system is used for applying agent on a hazard
from above and uses the Local Application, Overhead (LAOH) Nozzle. Typical applications in-
clude dip tanks, power generators, and transformers. The maximum nozzle height for overhead
protection is 10 ft (3048 mm).

Local Application, Overhead


(LAOH) Nozzle
(P/N 16216)

b. Local Application – Tankside: This system is used for applying agent across a hazard
area from the side of the area and uses the Local Application, Tankside (TS) Nozzle. Typical
applications include, but are not limited to, dip tanks, quench tanks, and solvent tanks where
overhead obstructions are present.

Local Application, Tankside


(TS) Nozzle
(P/N 16170) Local Application Tank Side Nozzle Placement and Coverage
(shown in feet)

c. Total Flooding: This system is used to fill a volume with agent to protect any hazard
within that volume. Typical applications include hazardous storage containers and warehouses.
Total flooding systems require a fixed enclosure to be present around the hazard area to allow
the system to build up the proper concentration of agent within the hazard area. It uses the JSH
Nozzles, Total Flood (TF) Nozzle, Total Flood Perimeter (TFP) Nozzle, Duct and Plenum (D/P)
Nozzle, Three-Way Nozzle, or Screening (SCR) Nozzle as appropriate for the hazard.

DS1311 Revised: 18-Feb-2022 Page 8 of 14


Total Flood - JSH Nozzles
The JSH-360 and JSH-180 Discharge Nozzles are Total Flooding nozzles with varying orifice
sizes as determined by the Janus Design Suite® Flow Calculation Software. JSH-360 nozzles
are designed for 360° (8 port) radial or center room placement. JSH-180 are designed for 180°
(6 port) sidewall placement. Both are available in Brass or Stainless Steel. The nozzles are
designed for Total Flooding Application of Dry Chemical Agent into an enclosure with no more
than 2.25% total unclosable openings. Each nozzle is stamped with the nozzle part number and
orifice diameter. Blow-Off Cap MUST be ordered separately (see chart). The maximum height
for a single tier of nozzles is 18 ft 4 in (5.588 m) from floor to ceiling. NOTE: JSH-360 and JSH-
180 Discharge Nozzles have not been evaluated for use in Vehicle Paint Spray Booth or Open
Front Spray Booth15'applications. 15'
[4.572m] [4.572m]

10.605'
[3.23m]
MAXIMUM

16.77'
15' 15' [5.11m]
[4.572m] [4.572m] MAXIMUM

1' [305mm]
MAXIMUM

1' [305mm]
180° Sidewall Nozzle (6 Port)
MAXIMUM

0.5' [152mm]
MAXIMUM

180° Sidewall Nozzle Maximum Coverage Area


(Single Nozzle)
15'
[4.572m]
24'
[7.32m]

10.605'
[3.23m]
MAXIMUM
33.94'
[10.34m]
MAXIMUM
24'
[7.32m]

15' 15'
[4.572m] [4.572m]

1' [305mm]
MAXIMUM

360° Center Room Nozzle (8 Port)


1' [305mm]
MAXIMUM

360° Center Room Nozzle Maximum Coverage Area

JSH Discharge Nozzles


Nozzle Part Number
Nominal
Blow-Off Cap
Brass Stainless Steel Pipe
Part Number
Size
360° 180° 360° 180°
19529 19522 20445 20438 3/8 in (10mm) 97146
19530 19523 20446 20439 1/2 in (15 mm) 97145
19531 19524 20447 20440 3/4 in (20 mm) 97144
19532 19525 20448 20441 1 in (25 mm) 97143
19533 19526 20449 20442 1 1/4 in (32 mm) 97142
19534 19527 20450 20443 1 1/2 in (40 mm) 97141
19535 19528 20451 20444 2 in (50 mm) 97140
DS1311 Revised: 18-Feb-2022 Page 9 of 14
Total Flood (TF) Nozzle - Fixed Orifice (P/N 16172)
This nozzle is designed for Total Flooding Application of Dry
Chemical Agent into an enclosure with no more than 5% total
unclosable openings. It is suited for and recognized by UL for
use in General Purpose and Industrial Hazards, Vehicle Paint
Spray Booth, Open Front Spray Booth, and Duct and Plenum
applications. It has a 3/4” (20 mm) MNPT pipe connection. The
TF Nozzle ships with a blow-off cap (P/N 14988). The maximum
nozzle height above the cylinder is 20 ft. Total Flood (TF) Nozzle
(P/N 16172)

Maximum Standard Coverage Per TF Nozzle


Hazard Height Longest Area Volume
ft (mm) Side ft (mm) ft² (m²) ft³ (m³)
12 or less
15 (4572) 120 (11.14) 1440 (40.77)
(3658 or less)
13 (3962) 15 (4572) 110.7 (10.28) 1440 (40.77)
14 (4267) 15 (4572) 102.8 (9.55) 1440 (40.77)
15 (4572) 15 (4572) 96 (8.91) 1440 (40.77)
16 (4877) 15 (4572) 90 (8.36) 1440 (40.77)
17 (5181) 15 (4572) 84.7 (7.86) 1440 (40.77)
18 (5486) 15 (4572) 80 (7.43) 1440 (40.77)
19 (5791) 15 (4572) 75.8 (7.04) 1440 (40.77)
20 (6096) 15 (4572) 72 (6.68) 1440 (40.77)

Nozzle Placement for Fixed Orifice Total


Flood Application
Total Flood Perimeter (TFP) Nozzle (P/N 17809)
This nozzle is designed to protect the Work Area in a Vehicle Paint
Spray Booth. It is also used in Total Flood applications. It is to be
installed at the upper perimeter of the module being protected. The
TFP Nozzle has a 1” (25 mm) FNPT. The TFP Nozzle ships with a
blow-off cap (P/N 17810). The nozzle must be properly oriented at the
upper perimeter of the module being protected. The tip of the nozzle
must be within 6” of its entry point and installed vertically with orifices
pointing downward.
Maximum Module Volume: 2,720 ft³ per nozzle
Maximum Module Area: 217.6 ft² per nozzle at 12.5 ft nozzle height Total Flood, Perimeter
Maximum Module Height: 12.5 ft. (TFP) Nozzle
(P/N 17809)
Maximum Module Side length: 16 ft. (either dimension)

LOCATE NOZZLE AT MIDPOINT 6 in (152 mm) MAXIMUM


OF ADJACENT MODULE EDGE FROM ENTRY POINT

TFP NOZZLE AS VIEWED DIRECTLY FROM BELOW:


8 ft (2438 mm)
MAXIMUM
TO LATERAL
MODULE
EDGE

HEIGHT

LENGTH
WIDTH

DS1311 Revised: 18-Feb-2022 Page 10 of 14


Duct and Plenum (D/P) Nozzle (P/N 16190)
This nozzle is designed to protect exhaust ducts and certain plenums
in Vehicle and Open Front Spray Booths. It can also be used in general
purpose and industrial hazards if the hazard criteria and the nozzle
spacing and coverage parameters are the same as outlined in the de-
sign manual. It has a 3/4” (20 mm) MNPT pipe connection. The D/P
Nozzle ships with a blow-off cap (P/N 14988).

It will protect either round or rectangular ducts up to 28 feet in length.


Any change in duct direction or additional length requires an additional
Duct/Plenum Nozzle. The nozzle must be centered at the duct entrance,
pointed in the direction of air flow. For Vehicle Paint Spray Booths, the Duct and Plenum (D/P) Nozzle
tip of the duct nozzle must be within 6” of the duct entrance. The Maxi- (P/N 16190)
mum diameter for Round Ducts is 46 inches. For Rectangular Ducts,
the Maximum Perimeter is 144.5 inches and the Maximum Diagonal 46
inches.

Three-Way Nozzle (P/N 16174)


This nozzle is specifically tailored for certain Vehicle Paint Spray Booth
and Open Front Spray Booth Plenum hazards. It can also be used in
general purpose and industrial hazards if the hazard criteria and the
nozzle spacing and coverage parameters are the same as outlined in
the design manual. It has a 3/4” (20 mm) MNPT pipe connection. The
Three-Way Nozzle ships with a blow-off cap (P/N 14988).
Three-Way Nozzle
(P/N 16174)

Screening (SCR) Nozzle (P/N 16192)


This nozzle is designed to be used to protect the unclosable openings
of General Purpose and Industrial Hazards and Vehicle Paint Spray
Booth Hazards when the opening has greater than the allowable to-
tal unclosable opening percentage. It can also be used to protect the
opening of the work area in an Open Front Spray Booth. It has a 3/4”
(20 mm) MNPT pipe connection. The SCR Nozzle is provided with a
blow-off cap (P/N 14988).

The screening nozzle can protect a maximum width of 8 ft (2438 mm)


and a maximum height of 18 ft (5486 mm). It has no depth of protec-
tion capability for dry chemical coverage. When providing a screening Screening (SCR)
nozzle(s) in conjunction with total flooding nozzles (Total Flooding ap- Nozzle
plications, Open Front Spray Booths), the total flooding nozzles must (P/N 16192)
be designed to protect up to the edge of the unclosable opening(s) that
are protected by the screening nozzle. Screening nozzles cannot be
tiered vertically.

DS1311 Revised: 18-Feb-2022 Page 11 of 14


VEHICLE PAINT SPRAY BOOTH HAZARDS
Vehicle paint spray booths are enclosures designed for the purpose of spraying combustible or
flammable paints (or other Class B materials) and conducting or directing the excess materials
into a forced ventilation exhaust system. Vapors, mists and residues produced from the spray-
ing operation are also conveyed through the exhaust system.

Vehicle paint spray booth hazards are protected with a combination of total flooding, screening,
duct and/or plenum nozzles. The physical structure of the enclosure and the arrangement of
the plenum and ductwork will normally determine what nozzles will perform best for the applica-
tion. The following nozzles can be used for the protection of vehicle paint spray booths:

Total Flood (TF) Nozzle Three-Way Nozzle Screening (SCR) Nozzle


(P/N 16172) (P/N 16174) (P/N 16192)
Total Flood, Perimeter (TFP) Nozzle Duct and Plenum (D/P) Nozzle
(P/N 17809) (P/N 16190)

OPEN FRONT PAINT SPRAY BOOTH HAZARDS


Open front paint spray booths are enclosures with one side (or face) of the enclosure generally
open. As with vehicle paint spray booths the enclosures are designed for the purpose of spray-
ing combustible or flammable paints (or other Class B materials) and conducting or directing
the excess materials into a forced ventilation exhaust system. Vapors, mists and residues pro-
duced from the spraying operation are also conveyed through the exhaust system.

Open front paint spray booth hazards are protected with a combination of total flooding, screen-
ing, duct and/or plenum nozzles. The physical structure of the enclosure and the arrangement
of the plenum and ductwork will normally determine what nozzles will perform best for the ap-
plication. The following nozzles can be used for the protection of open front paint spray booths:

Total Flood (TF) Nozzle Three-Way Nozzle Screening (SCR) Nozzle


(P/N 16172) (P/N 16174) (P/N 16192)
Total Flood, Perimeter (TFP) Nozzle Duct and Plenum (D/P) Nozzle
(P/N 17809) (P/N 16190)

DS1311 Revised: 18-Feb-2022 Page 12 of 14


SUPPLEMENTAL COMPONENTS
Supplemental components complete various system arrangements.

Discharge Pressure Switch (P/N 97428)


A discharge pressure switch is used in the system to
send a signal confirming agent discharge to the control
panel or to initiate the shut down of equipment that may
deplete agent concentration. It is a single pole, double
throw (SPDT) switch with contacts rated 15 Amps at
125/250/480 VAC and 0.5 Amps at 125 VDC. It has a
NEMA 4X enclosure.

XP Discharge Pressure Switch (P/N 97430)


A self-restoring NEMA 4X, 7, 9 and IP 67 Explosion-Proof
Discharge Pressure Switch can be used in potentially
72” (1829 mm)
explosive atmospheres to send indication of agent dis-
Leads charge to a releasing panel and/or initiate the shut down
of equipment that may deplete agent concentration. It is
a self-restoring double pole, double throw (DPDT) switch
with contacts rated 5 Amps at 125/250 VAC and 28 VDC
1/2” (15 mm) MNPT
Conduit Connection resistive. It is factory set at 50 psig (3.44 bar) rise.

Explosion-Proof Ratings:
Class I Div 1 Groups A, B, C, & D
1/4” (8 mm) MNPT Class II Div 1 Groups E, F, & G
Process Connection T5 or T6
II 2GD
Ex d IIC T6/T5 Gb
Ex tb IIIC T85°C/100°C Db

CHEMICAL PROPERTIES OF ABC DRY CHEMICAL AGENT


ABC or Multi-Purpose dry chemical is a specially fluidized and siliconized mono-ammonium phos-
phate. It chemically insulates Class A fires by melting at approximately 350°F and coating surfaces
to which it is applied. It smothers and breaks the chain reaction of Class B fire and will not conduct
electricity.

SAFETY CONSIDERATIONS
The discharge of dry chemical into a hazard may reduce visibility for a brief period.
The discharge of dry chemical systems to extinguish a fire can result in a potential hazard to per-
sonnel from the natural form of the powder or from the products of combustion that result from
exposure of the agent to the fire or hot surfaces. Unnecessary exposure of personnel either to the
natural agent or to the products of decomposition shall be avoided.
The Safety Data Sheet (SDS) on ABC Dry Chemical should be read and understood prior to working
with the agent.
A cylinder containing ABC Dry Chemical should be handled carefully. The anti-recoil safety de-
vice must be in place at all times when the cylinder is not connected to the discharge piping
and restrained.

DS1311 Revised: 18-Feb-2022 Page 13 of 14


Order Review List

P/N Description

26301 Cylinder Assembly, Dry Chemical 200lb Agent Capacity, 500 PSI
25147 Cylinder Assembly, Dry Chemical 600lb Agent Capacity, 500 PSI
25148 Cylinder Assembly, Dry Chemical 1000lb Agent Capacity, 500 PSI
18535 Bracket Assembly, Cylinder (200 lb cylinder)
18536 Bracket Assembly, Cylinder (600 / 1000 lb cylinder)
20722 Electric Valve Actuator w/ Supervisory Limit Switch
17001 Manual Valve Actuator
25804 Gauge Assembly, Pressure, Dry Chemical
Switch Assembly, Low-Pressure Supervisory
22946
(recommended all cylinders)
18554 Coupling, Grooved, 3” (80 mm) - 1000 lb Cylinders Only
18550 Elbow, Grooved, 3” (80 mm) - 1000 lb Cylinders Only
18555 Coupling, Grooved, 2” (50 mm) - 200, 600 lb Cylinders Only
18551 Elbow, Grooved, 2” (50 mm) - 200, 600 lb Cylinders Only
18474 Nipple, Grooved x MNPT, 2” (50 mm) - 200, 600 lb Cylinders Only
26311 Cylinder, Remote Nitrogen Actuation
26310 Cylinder, Remote Nitrogen Actuation, w Supervisory Switch Port
97643 Remote Pneumatic Actuation/Bracket Kit
17019 Pneumatic Valve Actuator (secondary cylinder)
18622 Tee, 1/4” JIC Male x 1/4” MNPT, Brass Pilot Actuation Mid Line Tee
10173 Vent Check (connects to Pilot Actuation End Line Tee)
Adapter, 1/4” MNPT x 1/4” JIC Male, Brass
18625
Male NPT Adapter (connects to Pilot Actuation End Line Tee)
18611 Tee, 1/4” FNPT x 1/4” MNPT, Brass Pilot Actuation End Line Tee
97428 Switch, Discharge Pressure
97430 Switch, Discharge Pressure, XP
18538 Manifold Check Valve, 3” (80 mm) - 1000 lb Cylinders Only
18546 Manifold Check Valve, 2” (50 mm) - 200, 600 lb Cylinders Only
18648 Hose, Flex, 3/16”, 1/4” JIC Female, 16” long
18649 Hose, Flex, 3/16”, 1/4” JIC Female, 24” long
18650 Hose, Flex, 3/16”, 1/4” JIC Female, 34” long
18651 Hose, Flex, 3/16”, 1/4” JIC Female, 40” long
18777 Adapter, 1/4” JIC Male x 1/4” JIC Male, Brass Flex Hose Adapter
16172 Total Flood Nozzle, Fixed Orifice, Dry Chemical
17809 Total Flood Perimeter Nozzle, Dry Chemical
16126 Local Application Overhead Nozzle, Dry Chemical
16170 Local Application Tankside Nozzle, Dry Chemical
16190 Duct and Plenum Nozzle, Dry Chemical
16174 Three-Way Nozzle, Dry Chemical
16192 Screening Nozzle, Dry Chemical
VARIABLE Total Flood Nozzle, JSH
The seller makes no warranties, express or implied, including, but not limited to, the implied warranties of merchantability and
fitness for a particular purpose, except as expressly stated in the seller’s sales contract or sales acknowledgment form. Every
attempt is made to keep our product information up-to-date and accurate. All specific applications cannot be covered, nor can
all requirements be anticipated. All specifications are subject to change without notice.

1102 Rupcich Drive


Millennium Park
Crown Point, IN 46307
TEL: (219) 663-1600 FAX: (219) 663-4562
e-mail: info@janusfiresystems.com
www.janusfiresystems.com
DS1311 Revised: 18-Feb-2022 Page 14 of 14