Lift

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1 2 3 4 5 6 7 8 9 10 11 12

Contravention will be prosecuted. Kone Elevator India Ltd.


permission and the contents thereof must not be imparted
to a third party nor be used for any unauthorised purpose.
This document must not be copied without our written Dwg Issue Date Change description Drawn by Checked by Appd. by

Work and Equipment Provided by Builder.


A

1.WELL
a) Lifting hooks having the lifting capacities and positions as shown.
b) Ventilation and heating, complying with the local building regulations, is
required to maintain the well air temperature between +5°C and +40°C.
B VALUES LIFT1 LIFT2
c) Verification that the wells are built to the dimensions and tolerances as **A 25A 32A
shown. **B 20A 25A
Fig. -1.

d) If necessary, pit access doors built to the dimensions shown and complying
with the local building regulations.
SINGLE LINE DIAGRAM
C
e) Landing door cut-outs to the dimensions shown.
f) Electrical sub-mains, fuses with neutral terminating at main switches near map CUSTOMER SCOPE KONE SCOPE
at top landing. The main switch unit should be with Lock out tag out Intercom wiring Twisted shielded pair/elevator
ELEVATOR INTERCOM
to master handset 2x0.75 SQmm
provision as shown in Fig. - 1.
g) Voltage between Earth & Neutral should be within 3V.
D

h) Safety barriers in front of all well openings during lift installation, to prevent
POWER SUPPLY
3Ø 415V±10%
50HZ
**A
MCB/RCB/RCCB/ELCB
CONTROLLER
**B
MCB
M
(300mA TYPE -A)
site personnel falling into well.
i) Pit access ladders to be provided if required or specified.
j) Permanent adequate shaft lighting to be given as mentioned in single line Car light Car light
E
10A SP MCB
diagram and same to be provided with two way switch connection in pit & 25A RCB 6A MCB
(30 mA)
POWER SUPPLY
mains panel. 1Ø 240V±10% Socket 16A
50HZ
***A
k) Where only one lift is erected in a common lift well, the builder must provide 25A
MCB 2W.SW 2W.SW
1 1

(FOR MIN.
adequate permanent protection for all openings left for future lifts.
2 2

SOCKET LOAD) #A MCB Near to PIT


F
shaft lighting
l) Provide dry pit adequately reinforced and waterproof. Pit should be designed MCB
Shaft & Pit lighting
to sustain the normal reaction on guides and buffer bases as indicated in this *** --> 2 WAY SW. Rating must be same as shaft lighting MCB Rating
#A --> For shaft height upto 70 Mtrs - 16A MCB to be used
#A --> For shaft height more than 70 Mtrs - 20A MCB to be used
drawing.
* Bulk head fitting 60 w/cfl-36w & plug point 16a-3 pin at every 3m in shaft
For intercom ordered jobs, communication cable specification is 2x0.75sqmm/ elevator,
m) A safety lockable covered and easily accessible storage space of atleast 40 Based on Intercom type additional power supply cable - 2X0.75sqmm/ elevator
G
sq.m area per lift must be made available, prior to delivery of materials to
site.
KONE ELEVATOR INDIA (P) LIMITED
n) The storage space must be reasonably near(within about 15 mts or so) the PLOT NO: A 28, SIPCOT INDUSTRIAL PARK, PILLAIPAKKAM,
SRIPERUMBUDUR TALUK, KANCHEEPURAM DISTRICT, TAMILNADU - 602105.

Date Customer NCC LIMITED


CUSTOMER'S APPROVAL
erection site and should be made available to our erection crew until the lift 31.07.2020

Prepared by
Name
Site IIT PATNA, BIHTA CAMPUS, BIHTA, PATNA, BIHAR-801106.
DV Address
H
is handed over. Checked by
KR
Drg. title GENERAL ARRANGEMENT DRAWING
Approved by KEN. no
VSK 44092760-61
Job/Enq. Lift1 - Drg. no KEI/6569224_1_40 Dwg Issue Page
Rev Lift2 - KEI/6569224_1_64 00 5(5)

A1