ERROECODE: 01 (B)
CAUSE: 1) One of the two poles of the 24Vdc power supply (24R or 0V on the BG15) is connected
to earth (PE).
REMEDY: 1) Check the 24volt circuits (door limit switch, photo cell, inspection box, display, gong,
push button, button lamps…) proceed disconnecting all wires involved and check one by
one until the fault is found.
2) With a voltmeter measure the voltage between 0V and earth and between earth and
24V, in a normal condition they should be exactly the half of the voltage measured, if
between 0V and earth is lower means that the wires conducting the 0V could have some
short circuit to earth, if it is lower between earth and 24V than the problem comes from the
wires conducting the 24V.
CAUSE: 1) The car does not reach, running in slow speed, the landing floor in the programmed
standard time (14 seconds) or time programmed at PAR 0B.
2) Increase the low speed time, programmed at address PAR 0B (write 1E= 30sec).
3) With Tapehead: The stopping Zone are set 0, the cabin does not stop at required floor
continuing at slow speed until “02” error is shown. Check Stopping Zone at address D2
and D3.
4) With Tapehead: The unlocking Zone are set at 0, the cabin does not stop at required
floor continuing at slow speed till “02” error is shown. Check Unlocking Zone and write
02 at D4 and 24 at D5.
5) With Tapehead, the slow-down distances are not correctly programmed and the cabin
travels for a too long distance at V0. Check distance D0-D1 for V2.
ERROR CODE: 03 (D)
CAUSE: 1) In inspection mode, the upward or downward push button is pushed for a time longer
than the one programmed at address 0D.
CAUSE: 1) The safety chain is interrupted before X4-6 terminal. One or more of the car safety
contact (stop, slack rope, safety gear, etc….) in the hoistway (final limit switch,
stop switch in pit, etc…) in the machine room (speed governor,etc).
2) Because of a short circuit in the safety chaine the automatic valve DI is switched
off.
3) For hydraulic elevator or with advanced door opening ( door zone control by
REED switch) the time relay KC operates.
5) The tension rods of the ropes are too close to the slack ropes plate opening the
safety contact.
2) For hydraulic elevators or with advanced door opening, check the good operation
of N.O. REED in the door zone and the right position of magnets.
5) If voltage of safety chain is present at “6” of BG15, the board may be faulty.
ERROR CODE: 05 (D)
CAUSE: 1) During the RESET operation after 3 staring attempts, the safety chain does not
close between X4-8 and X4-10 terminals.
REMEDY: 1) Check the contacts of the landing door locks and the wiring
2) For installation with swing doors, check also the contacts of the car doors.
3) The door contact may bounce and filtering time is not enough to solve the
problem. Write 14 (0, 2 sec) at AD PAR 1E.
4) If voltage of safety chain is present at “10” of BG15, the board may be faulty.
CAUSE: 1) 7 Function can be programmed on 4 outputs. One output cannot be used for two
functions.
REMEDY: 1) Check if two functions are programmed on the same output at AD PAR 78-79-
7A-7B, they should not have the same segments lighted and then modify the
program.
STATE CODE: 08 (D)
This is not an error but a function. If activated the car cannot start, if calls are registered they will be
answered when “NO START” is no more active. This function is used to start the cabins of a car group
in a row in order not to overload the supply.
CAUSE: 1) The maximum operation temperature, 110oC for the motor, or 70oC for
oil has been exceeded.
REMEDY: 1) Stop the lift until the running conditions are restored and search the
overheating causes.
2) Check if thermo contact or PTC are OK. In any case, shunting 0V and
“STH” the error must disappear, if not replace BG15.
REMEDY: 1) Check that with an up call actually the car goes up, and vice versa.
2) Check the right position of the magnets in the hoistway and check that the
connection A and B of REED Switches (ILS) are not inverted. Check on
main board BG15 the LEDs CA, corresponding to sensor A, and CB
corresponding to B, light up in the right order.
3) For traction rope elevator check phase sequence on traction motor. Check
also the balancing between car and counterweight if the fall of the cabin is
too much at starting when an up call is given.
4) If a phase is missing, the motor may be not able to keep the ordered
direction.
ERROR CODE: 11 (A)
AT STOPPING
2) Check the operation of the command circuit or/ and the control circuit of
contactors (see wiring diagram). Check the auxiliary contacts on the
contactors command circuit.
3) Check the voltage supply through the safety chain: the resistance of the
safety chain could be too high causing a drop of the voltage. Try to add
where it is possible an auxiliary contact in parallel to the existing one
on the contactors command circuit.
4) Check that the jumper SW7 is placed on TRAC for a traction lift and
HYDR for hydraulic.
CAUSE: 1) A limit switch should operate, when in inspection, to prevent the car
going beyond 1.5m from the roof of the hoistway.
CAUSE: 1) The Phase relay (KDF) does not switch on because one or more phases
are lost.
REMEDY: 1) Check the right power supply to the controller, terminal L1, L2, L3.
Exchange the phases if necessary. Always check the correct rotation of the
motor of the hydraulic power unit or the traction machine. This defect
might also came out at starting when the main power supply is not enough
or the temporary site supply is too feeble.
2) Check if the fault is the main board BG15: shunt 0V and “STH” on
BG15; if error disappears the board is OK.
ERROR CODE: 18 (A)
TERMINAL X4-8
CAUSE: 1) Opening of the safety circuit between terminals X4-6 and X4-8 (car door)
during the run.
2) For lift with swing doors, the opening of one of the preliminary contact of the
landing door.
2) For installation with swing doors check the contacts of the landing doors.
4) On VVVF the electrical noise generated by the motor can cause this error.
Hoistway harness must pass at 300mm, at least, from motor wires and 1m
from motor.
ERROR CODE: 20 (B)
EXCEEDS 700 C
CAUSE: 1) Only for hydraulic lifts, the oil temperature in the power unit exceeds 700C.
REMEDY: 1) Stop the lift until the optimal conditions are restored and search the
overheating causes.
TERMINAL
CAUSE: 1) One of the landing doors lock does not close at start. The fault is definitive
after 5 attempts
2) For installation with swing doors, car doors don’t close at starting.
REMEDY: 1) Check the contacts and wiring of the landing doors locks.
2) For installation with swing doors check the car doors contacts.
3) The door contact may bounce and filtering time is not enough to solve the
problem. Write 14 (0.2 sec) at AD PAR 1E.
4) If everything seems OK and “10” arrives on the main board, the latter is
faulty.
ERROR CODE: 22 (A)
CAUSE: 1) The REED switches or the Tapehead do not send any signal during
the reset standard time (20 second).
2) Check the right operation of sensors: REED A and B and the correct
magnets arrangement in the hoistway; the tapehead is correctly mounted at
the center of the tape and nothing hamper the reading.
4) Check any mechanical failure that may block the car, if the brake actually
opens or if the lift is stuck because of the safety gear.
CAUSE: 1) Safety chain interrupted before X4-6 terminal. Because of opening of one of
the safety contacts in the car (stop,slack ropes,safety gear, etc….), in the
hoistway (final limit switch, stop switch in the pit, etc…) or in the machine
room (slack ropes, speed governor, etc…).
3) For hydraulic elevators or with advanced door opening (door zone controlled
by REED switches) the time relay KC operated.
2) For hydraulic elevators or with advanced door opening, check the correct
operation of N.O. REED in the door zone and the right position of
magnets.
CAUSE: 1) REED “A” remains closed for a longer time than standard programmed
(standard 7 second high speed, 14 seconds low speed). AD PAR 0E for
high speed, AD PAR 0F for low speed.
REMEDY: 1) Check the right REED “A” operation and its connections.
2) Check other possible causes the car does not move. (See error 22).
CAUSE: 1) REED “B” remains closed for a longer time than standard programmed
(standard 7 seconds low speed). AD PAR 0E for high speed, AD PAR 0F
for low speed.
AT THE STARTING
CAUSE: 1) The supply voltage of the main board BG15 must be 19Vdc,
between 16 and 22 Vdc, measured on KT2 connector.
2) Check if the supply voltage L1, L2, L3 is the one required by the
controller 370-420V.
3) Check the 19V output of the transformer (T). Change the primary
winding, from 19V to 21V and vice versa, of the transformer to
suit site condition if possible.
4) Check the operation of the diode bridge rectifier PR1 (see wiring
diagram).
CAUSE: 1) The car doors contacts don’t close properly at the starting. For
installation with swing doors, contacts of the landing doors do not
close properly.
REMEDY: 1) Check the right operation of the car door contacts, or for installation
with swing doors, the landing doors contacts.
4) The door contact may bounce and filtering time is not enough to solve
the problem.
CAUSE: 1) One of the landing doors lock contact does not close at starting. For
installation with swing doors, the car door contacts do not close.
REMEDY: 1) Check the landing doors lock contacts and, for installation with swing
doors, the car door contacts. Check wiring of locks.
2) For installation with swing doors check the car doors contacts too.
3) The door contact may bounce and filtering time is not enough to solve the
problem.
4) Check adjustment and working of the close limit switch of door operator.
AT THE OPENING
CAUSE: 1) The opening of the door limit switch FCA is not detected in the standard
programmed time (10 seconds, AD PAR 47). 3 attempts are allowed than
the fault becomes permanent.
REMEDY: 1) Check there are no mechanical obstacles that stop door opening.
2) Check that the door limit switches are properly connected and positioned. Be
sure that the switches work properly check at AD RAM 0F segment 0 and
1, when the door is closed SEG1 is lightened ON and SEG0 ON.
AT THE OPENING
CAUSE: 1) The opening of the door limit switch FCA is not detected in the standard
programmed time (10 seconds, AD PAR 67).3 attempts are allowed than
the fault becomes permanent.
AT THE CLOSING
CAUSE: 1) The opening of the door limit switch FCC is not detected in the standard
programmed time (10 seconds AD PAR 47). 3 attempts are allowed than
the fault becomes permanent.
2) Check that there are no mechanical obstacles that stop door closing.
AT THE CLOSING
CAUSE: 1) The opening of the door limit switch FCC is not detected in the standard
programmed time (10 seconds AD PAR 67). 3 attempts are allowed than
the fault becomes permanent.
The function is used to put, by means of a contact, the elevator out of service. At AD PAR 43 is
programmed the parking floor. Parking can be with door open or closed.
This code shows us that by means of a contact the lift will accept only the car calls.
ERROR CODE: 52 (B)
CAUSE: 1) Opening of one of the landing doors locks while the car is running.
2) For installations with swing doors, opening of the car door contacts.
2) For installations with swing doors, check the car door contacts.
4) On VVVF the electrical noise generated by the motor can cause this
error. Hoistway harness must pass at 1 meter, at least, from motor
wires.
CAUSE: 1) During anti creep levelling the KRIP relay does not switch off (hydraulic).
CAUSE: 1) During anti creep levelling the KRIP relay does not switch on. Only for
hydraulic.
2) For traction lifts with N62 board: relevelling contactor is stuck and does not
switch on.
REMEDY: 1) Check the operation of door zone REED switches and, only for hydraulic,
the operation of relay KA and KB.
CAUSE: 1) During anti creep levelling the car exceeds the door zone (up or down).
3) If Tapehead is used: steps of relevelling are too wide and distance run
in relevelling is too long. Write 03 at AD PAR 1C (6mm).
5) The brake operates with delay. Check the brake command circuit.
CAUSE: 1) During anti creep levelling the car exceeds the relevelling zone (up or
down)
EXCEEDED
CAUSE: 1) During anti creep levelling the car did not reach the floor within the
maximum time of 12 seconds (AD PAR 19).
REMEDY: 1) Check the good operation of the traction machine and verify that there
are not any obstacles to car movement.
3) The brake does not open sufficiently. Check the brake command circuit.
(with TAPEHEAD)
2) At starting the microprocessor detects that floor height parameters are not
coherent.
CAUSE: 1) The sequence of signals of the tapehead is: 0-A-AB-B-0-A…If one pulse
is missing, the error is recorded and when total is 62, error is shown and
elevator stops.
REMEDY: 1) Check the slotted tape is correctly pulled, centred and without any
deformations, check also that nothing obstructs the slots and the magnets
and the brackets are fixed outside the slotted zone.
3) Electrical noise influence Tapehead: keep its cables separated from other
wires.
CAUSE: 1) With ILS contacts CED and CEM are simultaneously open.
Both with ILS contacts or 003 tapehead the contacts ED (CED) and EM CEM must be:
- Below the bottom slow down point: ED (CED) opened, EM (CEM) closed.
- Over the top slow down point: ED (CED) closed, EM (CEM) opened.
- Between bottom and top slow down point ED (CED) and EM (CEM) closed.
REMEDY: 1) Check the mechanical state of CEM and CED contacts and their wiring.
4) Bistable switch on the tapehead EM and/or ED are not coherent with the
position.
5) If everything is OK, the board BG23 for ILS contacts or the board N70 for
tapehead could be faulty.
CONTEMPORANEOUSLY ACTIVATED
CAUSE: 1) If two panels, inspection and recall, are provided, the inspection and recall
pushbutton panels are operating at the same time.
2) If only one inspection box is provided the shunt on BG15 card on the
KM12 connector is missing.
2) When in normal operation, check if on the BG15 card, the shunt has been
placed on the KM12 connector between terminals 1 and 2. (0V-MAN or
set AD PAR 07 SEG 4 OFF.
ERROR CODE: 65
ONLY FOR CONTROLLER WITH VVVF DRIVE
After 3 starting attempts a definitive fault of VVVF drive is detected. See VVVF manual.
ERROR CODE: 66
ONLY FOR CONTROLLER WITH VVVF DRIVE
Order to move has been given by the operation board, but the VVVF drive does not start because
of an error. See VVVF manual.
CAUSE: 1) When the car goes up in over travel, because of a creep, it leaves the over
travel zone and goes down to the lowest floor. Doors are open and
elevator is out of order.
REMEDY: 1) RESET (turn off and on supply) to restore the lift and check the causes of
the car over travel.
CAUSE: 1) For hydraulic lifts with probe to measure the oil level (optional). Oil has gone
down under the minimum level.
2) This error might came out after restoring the automatic valve DI.
CAUSE: 1) Possible sticking of one of the contactors. 3 attempts are made if AD PAR
07 SEG 6 ON.
2) 24R is missing.
2) Check the connection between KRIP relay terminals 1 and 3 on the controller.
ERROR CODE: 77 (C)
CAUSE: 1) The maximum oil operation temperature in the power unit has been
exceeded.
REMEDY: 1) Stop the lift until the optimal condition are restored and search the
overheating causes.
2) If the lift is without thermal probe for slow-down distance adjustment, check
the presence of shunt on the board BG15 connector KM17 between
terminals 1 and 3.