Professional Documents
Culture Documents
Three-Phase Asynchronous Squirrel-Cage Motor Mod. M-4/EV: TEACHER/STUDENT Handbook
Three-Phase Asynchronous Squirrel-Cage Motor Mod. M-4/EV: TEACHER/STUDENT Handbook
THREE-PHASE ASYNCHRONOUS
SQUIRREL-CAGE MOTOR
mod. M-4/EV
TEACHER/STUDENT handbook
Carefully follow the instructions contained in this handbook as they supply important
indications on the safety of the installation, use and maintenance.
UNPACKING
After the packaging has been removed, set all accessories in order so that they are not lost and
check the equipment integrity. In particular, check that the equipment is integral and shows
no visible damage.
Before connecting the equipment, be sure that the rating correspond to the one of the
electrical distribution network. (the rating is fixed to the same equipment)
The power supply cables must be set so that they cannot be trodded upon or squeezed by
objects. In case of incompatibility between the socket and the plug of the equipment, the
socket must be changed with a suitable one by highly qualified personnel. The last must
check that the cable section of the socket is dimensioned according to the power absorbed by
the equipment. It is not suggested to use adapters or multiple sockets; when these are used
they must fit the actual safety regulations.
On the equipment, there are some slots or opening for the ventilation; to ensure a reliable
operation and to protect the equipment from overheating, they must not be blocked or
covered. This equipment must be in such a position to enable a proper aeration.
Do never set the equipment on trolleys, supports, tripods, stirrups o unstable tables. The
equipment could fall causing damages to the collided persons or it can damage itself Any
installation of the equipment must follow the instructions of the manufacturer and must be
carried out using recommended accessories.
This equipment must be employed only for the use it has been conceived, i.e. as educational
equipment, and must be used under the direct survey of expert personnel. Any other use is
unproper and so dangerous. The manufacturer cannot be considered responsible for eventual
damages due to unproper, wrong or unreasonable uses.
PRECAUTIONS!
y and the equipment operation, when using electrical
equipment some fundamental rules must be followed. In particular the following regulation
for use must be followed:
Ambient temperature: from 0 to 45°C.
Relative humidity: from 20 to 80 %.
Avoid any quick shift of temperature and humidity.
The system, included the power supply cable, must be used in a place without or distant from:
dust, humidity, high heat, objects radiating heat, liquids or corrosive substances.
To prevent contact against the electrical parts, do not open the equipment, in case of need,
only qualified personnel can do it. Before carrying out any maintenance operation, disconnect
the equipment from the power supply network.
In case of fault and/or bad operation, turn off the equipment and do not tamper it. In case of
reparation, ask the center for technical assistance or ask exclusively original spare parts. If
these conditions are not respected, the equipment can be compromised.
All the necessary connections to control an electrical motor must be carried out with
equipment off and using proper cables with 4mm-plug.
In case the protection fuses must be changed, first of all remove the power supply cables from
the network socket. To disconnect the cable, take it only from the plug. Do not pull the cable.
In case of penetration of objects or liquids inside the equipment, disconnect the power supply
cable and make it checked by qualified personnel before using again.
VIBRATIONS OR COLLISIONS
Be careful not to cause vibrations or collisions.
Stator and rotor are separated by an air gap of constant thickness which
has a relatively low value, with respect to that of alternators, as it is
required for a good operation of the machine. As in alternators, the
stator magnetic pack is laminated according to planes perpendicular to
the shaft of the machine and is provided with slots along the internal
periphery towards the air gap. Also the rotor is laminated and consists
of a pack of ring sheets. These sheets are centred and tightened by a
mechanical structure: one kind of bush, fixed to the shaft. Also the
rotor is provided with radial slots arranged along the external periphery
towards the air gap.
Both the stator and rotor slots are designed to contain the windings of
stator and rotor.
Like the other electrical machines, also the asynchronous machines can
operate both as asynchronous motors and as asynchronous generators.
These machines are called asynchronous because, differently from the
1
synchronous machines, they can never rotate at synchronous speed, but
at a speed which varies together with the load: starting from a value
very near the synchronous value in no-load operation, this speed
reaches a value different of some percent in full-load operation.
n0-n
where:
Moreover, the slip speed and the relative speed are positive or negative,
according to whether the asynchronous machine operates as motor or as
generator.
2
When operating as motor, the machine absorbs the necessary
magnetizing power from the mains and, at the same time, it also
absorbs the electric power which is transformed into mechanical power
(excluding the efficiency). On the contrary, when operating as
generator, the machine absorbs the magnetizing power for its excitation
from the mains and delivers the electric power transformed from the
mechanical power received by the driving motor, to the same mains.
DO IT YOURSELF
a) Using an ohmmeter or the instruments available in the laboratory,
identify the terminals corresponding to beginning and end of each
phase of the armature winding and check that there is no electrical
continuity between the phases.
b) Is there electrical continuity between the armature winding and the
metal frame of the machine ?
3
4.1 Measurement of the resistance of the machine windings
Connect the terminals of the d.c. line inserting a suitable ammeter and a
voltmeter, as well as a control rheostat, across the terminals
corresponding to the resistance to be measured.
Fig. 1 shows this connection with respect to the stator winding of the
asynchronous motor.
Close the switch of the d.c. line; then act on the variator and on the
rheostat to obtain the desired current value I1. This value must not
exceed the rated current capacity of the line and it must be lower than
the rated current of the winding under examination. Then, read the
voltage V11 on the voltmeter and calculate the resistance through the
ratio:
1
1
1
Repeat the measurement for the other two pairs of terminals obtaining
R12 and R13.
Remember that both in the case of star connection and delta connection
of the machine phases, the average resistance of an equivalent star
phase is determined through the sum of the three measured resistances,
divided by six, that is:
1 2 3
4
This result can be brought to 75°C:
where:
ta is the ambient temperature at which the test has been carried out; it
can be measured with a normal thermometer. In fact, as the test is quick
and the involved current very weak, with respect to the rated one, the
temperature of the windings would not be very different from the
ambient temperature; o is the temperature coefficient of the material
under examination (usually copper: o = 0,00426 1/°C).
Another formula is:
DO IT YOURSELF
a) Disconnect the terminals U2-V2-W2 and repeat the measurement
of resistance across the terminals U1-U2, V1-V2, W1-W2.
b) Are the three resistances measured across each phase of the
armature winding equal ?
c) Power supplying each phase with the voltage of 220V a.c., which
should be the generated current ?
d) Connect the terminals U1-W2, V1-U2, W1-V2 (delta connection)
and repeat the measurement of resistance across the terminals U1-
V1, V1-W1, W1-U1.
e) Compare the values measured with the star connection with those
measured with the delta connection.
5
4.2 No-load test of the three-phase asynchronous cage motor
The test consists in determining the values of the no-load losses Po and
of the no-load current Io, versus the voltage applied to the machine
(fig.2).
The power supply (obviously with variable voltage) can be given from
the three-phase variable line (0 to 430V a.c. - 3A). So, the motor can be
started with variable voltage. The three-phase starting rheostat is not
necessary.
Starting from a voltage approx. 20% higher than the rated one, measure
for various ever-decreasing values of the supply voltage, until the speed
of the machine is considerably decreased (usually, at approx. 20% of
the rated voltage).
6
fig. 3 Diagram for the measurement of the no-load characteristics of
the three-phase asynchronous cage motor
Moreover, the iron losses can easily be separated from the mechanical
losses thanks to a diagram representing the no-load losses (fig. 4.4)
versus the square of the voltage. Remember that the no-load losses can
be calculated through the algebraic sum of the values measured by the
two wattmeters:
Po = P13 P23
7
fig.4 Separation of the mechanical and iron losses in the no-load test
of the asynchronous motor
4.3 Test of short circuit, or with blocked rotor, of the three-phase asynchronous motor
Also the power supply can be given from the three-phase variable line
(0 to 430V a.c. - 3 A); the voltage and, consequently, the current can be
varied adjusting the three-phase voltage variator of this line.
8
Consequently, the test is carried out like the previous one. At first, a
current equal to the rated one (or even 20% higher) must cross the line
of the motor; measure the supply voltage and read the indications of the
wattmeters.
As the test must be carried out quickly to prevent the excessive heating
of the machine, take few other readings for gradually decreasing
currents. Four or five values are sufficient; in fact, the short-circuit
voltage vs the current is represented by a straight line and power has a
parabolic sketch. Therefore, it is not difficult to plot the other straight
line corresponding to the power vs the square of the current (fig.5 and
6).
9
As the power factor of the machine is generally equal to approx. 0,5, it
is better to use a wattmeter with low power factor, in position P23.
If the test is not carried out quickly and, consequently, the temperature
is not kept constant, it is better to measure the temperature immediately
after the end of the test, to know the starting point to bring the result to
75°C.
1 2 3
Then, starting from Tx, the values (and eventually the diagrams) can be
brought to 75°C.
Use the same instruments listed in the paragraph 4.2, except the
electronic digital counter which is not necessary in this test.
DO IT YOURSELF
10
4.4 Direct measurement of the main operating characteristics of the three-phase
asynchronous motor, through test with the dynamometer.
The test should be carried out once reached the operating temperature
of the machine under examination.
Fig. 7 shows the diagram of the test. The necessary instruments are an
ammeter, a voltmeter, a frequency meter (unnecessary, if the power
supply is given from the mains) and two Aron-connected wattmeters
(P13 and P23).
fig. 7 Diagram for the measurement of the load-operation characteristics of the three-phase
asynchronous cage motor
The ammeter and the voltmeter are connected to the supply circuit of
the dynamometer, to check that the rated values are not exceeded.
The measuring circuit of the motor can also include three voltmeters (to
check the symmetry of the supply voltage) and three ammeters (to
check the balance of the motor phases).
11
When the motor starts, the three-phase starting rheostat must be
inserted completely, to obtain the maximum starting torque and the
minimum absorbed current; then it is immediately disconnected.
However, before starting, the two machines are uncoupled and the
motor under examination, power supplied by the three-phase line with
rated (or nearly rated) voltage, is started in no-load condition; then, the
starting rheostat is short-circuited.
Then the motor stops and the initial balancing of the dynamometer
-
the scale of the measuring arm, to check that, with this system of
double rail (instead of the two arms coming out of the stator), the
balancing with counterweight is not necessary.
In fact, the zero of the scale is almost surely on the vertical axis
crossing the centre of gravity of the machine, that is, the locus of the
points where the application of a weight can never generate any torque.
Very small inclinations of the arm can eventually be corrected shifting
the smaller weight set on the upper part of the rail. But check that these
inclinations are not due to the indifference of balance of the system:
this is always possible for the passive frictions of brushes and bearings.
This condition can be checked through the index set on the generator.
In this condition, the generator (with load and field circuits open) is
coupled with the motor under test and driven to rotate at rated speed.
Fixing the speed at the rated value no (r.p.m.), the power Pa, lost for
friction in the bearings, can easily be calculated through the known
formula:
12
Pa is expressed in W.
As already explained, the ventilation losses are omitted in this
measurement.
On the other hand, considering the measuring circuit of the motor, the
- (Po + Pa)
These losses must be considered when they become remarkable and the
measuring circuit is sensitive enough to measure them.
These losses, transmitted from the motor to the dynamometer (but
absent in the torque generated by the stator balancing), must always be
summed to the losses which are progressively determined as the
generator load increases.
In this case, it is sufficient to put this weight on the zero of the scale
without stopping the machines and without counterweighing.
The test can also be carried out starting with small weights, for the
measurement of the lowest transmitted powers. Then, change the
weight acquiring higher measuring sensitivity, without stopping and
balancing the set at every change of weight.
The operator can choose the method which best meets his needs.
Starting from this moment, the speed must decrease as the load
increases and it can be checked through a stroboscopic lamp: this lamp
can be synchronized with the mains frequency. The speed can also be
measured with the electronic digital counter.
13
unbalancing the stator in the direction apposite to the motion.
The balancing is carried out closing the armature circuit of the
generator on the minimum load (load rheostat with maximum
resistance). Then, close the inductor circuit which is slowly excited to
regulate the torque, necessary to balance the structure again.
C = 9,81·p·b+Cv;
Pd = 1,027·p·b·n+Pv;
motor efficiency:
14
operation and with weak loads (in any case, for power factors of the
load lower than 0,5), the wattmeter P23 gives negative indications.
Consequently, the voltmetric coil of the wattmeter must be reversed, to
read the power indicated by the wattmeter, considered with its negative
sign. Once exceeded the cos 0,5, the wattmeter indication is positive,
so the voltmetric coil can be arranged in the right position again.
Also the power factor can be calculated with the wattmeters; for this,
calculate the value:
which is used to calculate the power factor through the known formula:
The power factor can also be calculated with the proper nomograph
included in any book of electrical measurements. But, as the load is
balanced, it is better to use this formula:
15
Instruments and equipment used in the test
Power supplies:
armature of the asynchronous motor: three-phase fixed line of 380 V
10 A; dynamometer field: fixed line of 220 V d.c. 3 A;
A: moving-iron ammeter 2-4 A;
V: moving-iron voltmeter 250-500 V;
W: electrodynamic wattmeter 2-4 A/250-500 V;
RA : motor-starting rheostat 3x(500 W 50 ohm);
RD : field rheostat of the dynamometer: (500 W 5000 ohm);
RC: load rheostat of the dynamometer mod. RL-1/EV;
IC : switch for the separation of the load;
Machine mod. M-4/EV;
Machine mod. M-12/EV
Electronic digital counter.
16