Shanta 6.6kV Realy Co-Ordination
Shanta 6.6kV Realy Co-Ordination
1.00
0 500 1000 1500 2000 2500 3000 3500 4000 45
Note
Incomer E/F should be 20% with TMS of 0.2
DW Feeder E/F should be 15% with a TMS of 0.15
Ilunga Feeder E/F should be 18% with TMS of 0.2
Crush Feeder E/F should be 20% with TMS of 0.25
Isec DW Isec Incomer I/In Ilunga Isec Ilunga I/In Crush Isec Crush
5.33 1.00 24.69 4.44 20.00 4 RELAY CO-ORDINATION F
6.93 1.30 32.10 5.78 26.00 5.2
10.67 2.00 49.38 8.89 40.00 8
16.00 3.00 74.07 13.33 60.00 12
21.33 4.00 98.77 17.78 80.00 16 10.00
26.67 5.00 123.46 22.22 100.00 20
32.00 6.00 148.15 26.67 120.00 24
37.33 7.00 172.84 31.11 140.00 28
42.67 8.00 197.53 35.56 160.00 32
48.00 9.00 222.22 40.00 180.00 36
53.33 10.00 246.91 44.44 200.00 40
58.67 11.00 271.60 48.89 220.00 44
64.00 12.00 296.30 53.33 240.00 48
69.33 13.00 320.99 57.78 260.00 52
74.67 14.00 345.68 62.22 280.00 56
80.00 15.00 370.37 66.67 300.00 60
85.33 16.00 395.06 71.11 320.00 64
90.67 17.00 419.75 75.56 340.00 68
96.00 18.00 444.44 80.00 360.00 72
I>/IN T.M.S
0.20 0.2
1.00
0 500
RELAY CO-ORDINATION FOR 6.6kV SHANTA SUBSTATION
10.00
1.00
0 500 1000 1500 2000 2500 3000 3500
Fault current (A)
Trip DW Trip Ilunga
3500