Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

FUNCTIONAL LOGIC DIAGRAM

WATER INJECTION PUMP (P-131001)

SHEET NO :001

_
FUNCTIONAL LOGIC DIAGRAM

LEGENDS

TRANSFER
INDICATOR OF
13-LAL- 13-LAL- DCS ALARM
SIGNALS TO
AND LOGIC 10022 10022
AND ANOTHER
FUNCTION SHEET 13-LAL-10022
SHEET :001 SHEET :008

ON DELAY
TON TIMER
HW 13-LT-10022 H> TIMER
A PHYSICAL T#60S
OR LOGIC INPUT
OR FUNCTION I Diff level
IPS Transmitter

START 13-PMST-10022 V HW
Diff level PHYSICAL
LESS THAN OR
Transmitter W MCC OUTPUT
<= EQUAL TO
LOGIC
FUNCTION

13-KMXZ-13103
S SK
O
OUTPUT
TRIP LO/WO F
COOLER FAN K- IPS SERIAL LINK
GREATER T
THAN OR 13103 MOTOR
>= EQUAL TO
LOGIC
FUNCTION
SK S 13-EMRN-10031C
O INPUT
F LO/WO COOLER FAN SERIAL LINK
IPS T RUNNING FB
S Q
SR FLIP FLOP
SR LOGIC
FUNCTION
R

SHEET NO :002
_
INPUT OUTPUT
FIELD
13-PT-10085 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD

HW 13-PT-10085 L Alarm Setpoint


A = 8637 KPag
I PUMP P-131001 ANALOG INPUT
SEAL SYSTEM L <=
DCS PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
20000 KPag & SCALING
13-PAL-10085
13-PAL- 13-PAL-
LOW LIMIT = 10085
0 KPag LL Alarm Setpoint 10085
= 8100 KPag SHEET :003 SHEET :027
<=

13-PALL-10085
13-PALL- 13-PALL-
10085 10085
DCS TAGS
SHEET :003 SHEET :027 NORMAL = 0
ALARM = 1

13-PT-10087 - PUMP P-131001 SEAL SYSTEM PRESS (NDE SEAL)

HW 13-PT-10087 L Alarm Setpoint


A = 8637 KPag
I PUMP P-131001 ANALOG INPUT <=
DCS SEAL SYSTEM L SIGNAL PROCESSING
PRESS (NDE SEAL) HIGH LIMIT =
20000 KPag & SCALING
13-PAL-10087
13-PAL- 13-PAL-
LOW LIMIT = 10087
0 KPag LL Alarm Setpoint 10087
= 8100 KPag SHEET :003 SHEET :028
<=

13-PALL-10087
13-PALL- 13-PALL-
10087 10087
SHEET :003 SHEET :028

DCS TAGS
NORMAL = 0
ALARM = 1

SHEET NO :003
INPUT OUTPUT
FIELD
13-PZT-10086 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD

HW 13-PZT-10086 LL Alarm Setpoint


A = 7920 KPag
I PUMP P-131001 ANALOG INPUT
SEAL SYSTEM L <=
IPS PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
20000 KPag & SCALING
13-PALL-10086
13-PALL- 13-PALL-
LOW LIMIT = 10086
0 KPag 10086
SHEET :004 SHEET :023 IPS TAGS
SHEET :027 NORMAL = 1
SHEET :028 TRIP/ALARM = 0

13-PZT-10088 - PUMP P-131001 SEAL SYSTEM PRESS (NDE SEAL)

HW 13-PZT-10088 LL Alarm Setpoint


A = 7920 KPag
I PUMP P-131001 ANALOG INPUT
SEAL SYSTEM L <=
IPS HIGH LIMIT = SIGNAL PROCESSING
PRESS (NDE SEAL)
20000 KPag & SCALING
13-PALL-10088
13-PALL- 13-PALL-
LOW LIMIT = 10088
0 KPag 10088
SHEET :004 SHEET :023
SHEET :027
IPS TAGS
SHEET :028
NORMAL = 1
TRIP/ALARM = 0

SHEET NO :004
INPUT OUTPUT
FIELD
13-TT-10066 - PUMP P-131001 SEAL SYSTEM TEMP ( DE SEAL) ALARM FIELD

HW 13-TT-10066 H Alarm Setpoint


H
A = 70 DEG C
I PUMP P-131001 ANALOG INPUT
SEAL SYSTEM >=
DCS PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
100 DEG C & SCALING
13-TAH-10066
13-TAH- 13-TAH-
LOW LIMIT = 10066
0 DEG C 10066
SHEET :005 SHEET :023

DCS TAGS
NORMAL = 0
ALARM = 1

13-TT-10067 - PUMP P-131001 SEAL SYSTEM TEMP (NDE SEAL)

HW 13-TT-10067 H Alarm Setpoint


H
A = 70 DEG C
I PUMP P-131001 ANALOG INPUT >=
SEAL SYSTEM
DCS HIGH LIMIT = SIGNAL PROCESSING
PRESS (DE SEAL)
100 DEG C & SCALING
13-TAH-10067
13-TAH- 13-TAH-
LOW LIMIT = 10067
0 DEG C 10067
SHEET :005 SHEET :023

DCS TAGS
NORMAL = 0
ALARM = 1

SHEET NO :005
INPUT OUTPUT
FIELD
13-LT-10022 - PUMP P-131001 SEAL SYSTEM TANK LEVEL ALARM FIELD

HW 13-LT-10022 H Alarm Setpoint


H = 88.3%
A
I PUMP P-131001 ANALOG INPUT
SEAL SYSTEM L >=
DCS TANK LEVEL HIGH LIMIT = SIGNAL PROCESSING
100 % & SCALING 13-LAH-10022
13-LAH- 13-LAH-
LOW LIMIT = 10022
0% L Alarm Setpoint 10022
= 26.5% SHEET :006 SHEET :001
<=

13-LAL-10022
13-LAL- 13-LAL-
10022 10022
DCS TAGS
SHEET :006 SHEET :027 NORMAL = 0
ALARM = 1

SHEET NO :006
INPUT OUTPUT
FIELD
13-LT-10021 - VOITH CPLNG GB-131001 OIL RESERVOIR LEVEL ALARM FIELD

HW 13-LT-10021 H Alarm Setpoint


H = 84.2%
A VOITH CPLNG
I GB-131001 OIL ANALOG INPUT >=
DCS L
RESERVOIR LEVEL HIGH LIMIT = SIGNAL PROCESSING
100 % & SCALING 13-LAH-10021
13-LAH- 13-LAH-
LOW LIMIT = 10021
0% L Alarm Setpoint 10021
= 60.5% SHEET :001 SHEET :001
<=

13-LAL-10021
13-LAL- 13-LAL-
10021 10021 DCS TAGS
SHEET :007 SHEET :030 NORMAL = 0
SHEET :036 ALARM = 1

13-PT-10081 - VOITH CPLNG GB-131001 LO PRESS AFTER LO FILTER

HW 13-PT-10081 H Alarm Setpoint


H = 170/200 KPag
A VOITH CPLNG
I GB-131001 LO ANALOG INPUT
PRESS AFTER LO L >=
DCS HIGH LIMIT = SIGNAL PROCESSING
FILTER
600 KPag & SCALING 13-PAH-10081
13-PAH- 13-PAH-
LOW LIMIT = 10081 10081
0 KPag L Alarm Setpoint
= 150 KPag SHEET :007 SHEET :030
<=

13-PAL-10081
13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :030
SHEET :045 DCS TAGS
NORMAL = 0
ALARM = 1

SHEET NO :007
INPUT OUTPUT
FIELD
13-PZT-10082 - VOITH CPLNG GB-131001 LO PRESSURE AFTER LO FILTER ALARM FIELD

HW 13-PZT-10082 LL Alarm Setpoint


A VOITH CPLNG GB- = 80 KPag
I 131001 LO ANALOG INPUT
PRESSURE AFTER L <=
IPS HIGH LIMIT = SIGNAL PROCESSING
LO FILTER
150 KPag & SCALING
13-PALL-10082
13-PALL- 13-PALL-
LOW LIMIT = 10082
0 KPag 10082
SHEET :008 SHEET :030 IPS TAGS
NORMAL = 1
TRIP/ALARM = 0

13-PDT-10083 - VOITH CPLNG GB-131001 LO FILTER DIFF. PRESS

HW 13-PDT-10083 H Alarm Setpoint


H
A = 80 KPag
I VOITH CPLNG GB- ANALOG INPUT
131001 LO FILTER <=
DCS HIGH LIMIT = SIGNAL PROCESSING
DIFF. PRESS
150 KPag & SCALING
13-PAHH-10083
13-PAHH- 13-PAHH-
LOW LIMIT = 10083
0 KPag 10083
SHEET :001 SHEET :001 IPS TAGS
NORMAL = 1
TRIP/ALARM = 0

SHEET NO :008
INPUT OUTPUT
FIELD
13-TZT-10061 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD

HH Alarm Setpoint
HW 13-TZT-10061 = 70 DEG C
A
I VOITH CPLNG GB- ANALOG INPUT
131001 LO TEMP L >=
IPS AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAHH-10061
13-TAHH- 13-TAHH-
LOW LIMIT = 10061 10061
0 DEG C
IPS TAGS
SHEET :009 SHEET :031
NORMAL = 1
TRIP/ALARM = 0

13-TZT-10063 - VOITH CPLNG GB-131001 WO TEMP BEFORE COOLER

HW 13-TZT-10063 H Alarm Setpoint


A = 110 DEG C
I VOITH CPLNG GB- ANALOG INPUT
131001 WO TEMP L >=
IPS HIGH LIMIT = SIGNAL PROCESSING
BEFORE COOLER
150 DEG C & SCALING
13-TAH-10063
13-TAH- 13-TAH-
LOW LIMIT = 10063 10063
0 DEG C
SHEET :001 SHEET :001
HH Alarm Setpoint
= 130 DEG C
>=

13-TAHH-10063
13-TAHH- 13-TAHH-
10063 10063
SHEET :009 SHEET :031
IPS TAGS
NORMAL = 1
TRIP/ALARM = 0
SHEET NO :009
INPUT OUTPUT
FIELD
13-TT-10060 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD

HW 13-TT-10060 H Alarm Setpoint


H
A = 65 DEG C
I VOITH CPLNG GB- ANALOG INPUT
131001 LO TEMP >=
DCS AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAH-10060
13-TAH- 13-TAH-
LOW LIMIT = 10060
0 DEG C 10060
SHEET :001 SHEET :001

DCS TAGS
NORMAL = 0
ALARM = 1

13-TT-10062 - VOITH CPLNG GB-131001 WO TEMP AFTER COOLER

HW 13-TT-10062 H Alarm Setpoint


H
A = 75 DEG C
I PVOITH CPLNG GB- ANALOG INPUT >=
131001 WO TEMP
DCS HIGH LIMIT = SIGNAL PROCESSING
AFTER COOLER
150 DEG C & SCALING
13-TAH-10062
13-TAH- 13-TAH-
LOW LIMIT = 10062
0 DEG C 10062
SHEET :001 SHEET :001

DCS TAGS
NORMAL = 0
ALARM = 1

SHEET NO :010
INPUT OUTPUT
FIELD
13-TC-10064 - VOITH CPLNG GB-131001 OIL RESERVOIR TEMP CTR ALARM FIELD

HW 13-TC-10064 H Alarm Setpoint


H
A VOITH CPLNG = 27 DEG C
I GB-131001 OIL ANALOG INPUT
RESERVOIR TEMP L >=
DCS HIGH LIMIT = SIGNAL PROCESSING
CTR
100 DEG C & SCALING
13-TAH-10064
13-TAH- 13-TAH-
LOW LIMIT = 10060
0 DEG C 10060
L Alarm Setpoint
= 20 DEG C SHEET :011 SHEET :036

<=

13-TAL-10064
13-TAL- 13-TAL-
10064 10064
DCS TAGS
SHEET :011 SHEET :036 NORMAL = 0
ALARM = 1

13-TS-10065 - VOITH CPLNG GB-131001 OIL RESERVOIR TEMP CTR

HW 13-TS-10065 H Alarm Setpoint


H
A VOITH CPLNG GB- = 100 DEG C
I 131001 OIL ANALOG INPUT >=
RESERVOIR TEMP
DCS HIGH LIMIT = SIGNAL PROCESSING
CTR
150 DEG C & SCALING
13-TAH-10065
13-TAH- 13-TAH-
LOW LIMIT = 10065
0 DEG C 10065
SHEET :001 SHEET :001

DCS TAGS
NORMAL = 0
ALARM = 1

SHEET NO :011
INPUT OUTPUT
FIELD
13-TE-10046A/B, 13-TE-10047A/B,13-TE-10048A/B - MOTOR P-131001-ME WIND TEMP (R),(S),(T) ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10046A/B 180 DEG C = 130 DEG C
H
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) LOW LIMIT =
0 DEG C H Alarm Setpoint 13-TAH-10046A/B
= 130 DEG C
HW 13-TE-10047A/B H
A >=
I MOTOR P-131001-ME 13-TAH-10047A/B
MMS WIND TEMP (S) H Alarm Setpoint
= 130 DEG C
HW 13-TE-10048A/B H >=
A
I MOTOR P-131001-ME 13-TAH-100468A/B
MMS WIND TEMP (T)
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10046A/B 180 DEG C = 140 DEG C
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) HH LOW LIMIT =
0 DEG C HH Alarm Setpoint 13-TAHH-10046A/B
= 140 DEG C
HW 13-TE-10047A/B
A >=
I MOTOR P-131001-ME 13-TAHH-10047A/B
MMS WIND TEMP (S) HH HH Alarm Setpoint
= 140 DEG C
HW 13-TE-10048A/B >=
A
I MOTOR P-131001-ME 13-TAHH-100468A/B
MMS WIND TEMP (T) HH
13-TAHH- 13-TAHH-
2OO3 10046A/47A 10046A/47A
VOTING /48A /48A

SHEET :011 SHEET :040


MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0
SHEET NO :011
INPUT OUTPUT
FIELD
13-TE-10043, 13-TE-10044,13-TE-10045 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10043 150 DEG C = 100 DEG C
H
A >=
I MOTOR P-131001-ME
MMS AIR TEMP LOW LIMIT =
0 DEG C H Alarm Setpoint 13-TAH-10043
= 95 DEG C
HW 13-TE-10044 H
A >=
I MOTOR P-131001-ME 13-TAH-10044
MMS BRG TEMP NDE H Alarm Setpoint
= 95 DEG C
HW 13-TE-10045 H >=
A
I MOTOR P-131001-ME 13-TAH-10045
MMS BRG TEMP DE
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10043 150 DEG C = 110 DEG C
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) HH LOW LIMIT =
0 DEG C HH Alarm Setpoint 13-TAHH-10043
= 100 DEG C
HW 13-TE-10044
A >=
I MOTOR P-131001-ME 13-TAHH-10044
MMS WIND TEMP (S) HH HH Alarm Setpoint
= 100 DEG C
HW 13-TE-10045 >=
A
I MOTOR P-131001-ME 13-TAHH-10045
MMS WIND TEMP (T) HH

13-TAHH- 13-TAHH-
AND 10043/44/45 10043/44/45

SHEET :011-1 SHEET :040


MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0
SHEET NO :011-1
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10037 H 150 DEG C = 75 DEG C
A >=
PUMP P-131001
I
CASING SURFACE LOW LIMIT =
MMS TEMP
0 DEG C H Alarm Setpoint 13-TAH-10037
= 93 DEG C
HW 13-TE-10038 H
A >=
I PUMP P-131001 13-TAH-10038
SLEEVE BRG TEMP
MMS DE H Alarm Setpoint
= 93 DEG C
HW 13-TE-10039 H >=
A
PUMP P-131001
I 13-TAH-10039
SLEEVE BRG TEMP
MMS NDE

MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10040 H 150 DEG C = 93 DEG C
A >=
I PUMP P-131001 TILT-
PAD BRG (ACTIVE) LOW LIMIT =
MMS TEMP NDE
0 DEG C H Alarm Setpoint 13-TAH-10040
= 93 DEG C
HW 13-TE-10041 H
A >=
I PUMP P-131001 TILT- 13-TAH-10041
PAD BRG (ACTIVE)
MMS TEMP NDE H Alarm Setpoint
= 93 DEG C
HW 13-TE-10042 H >=
A
PUMP P-131001 TILT-
I 13-TAH-10042
PAD BRG (NON-
MMS ACTIVE) TEMP NDE
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0

SHEET NO :012
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10037 HH 150 DEG C = 80 DEG C
A >=
PUMP P-131001
I
CASING SURFACE LOW LIMIT =
MMS TEMP
0 DEG C HH Alarm Setpoint 13-TAHH-10037
= 104 DEG C
HW 13-TE-10038 HH
A >=
I PUMP P-131001 13-TAHH-10038
SLEEVE BRG TEMP
MMS DE HH Alarm Setpoint
= 104 DEG C
HW 13-TE-10039 HH >=
A
PUMP P-131001
I 13-TAHH-10039
SLEEVE BRG TEMP
MMS NDE
AND 13-TAHH- 13-TAHH-
10037/38 10037/38
SHEET :013 SHEET :040

1002 13-TAHH- 13-TAHH-


VOTING 10039/40 10039/40
SHEET :013 SHEET :040
HIGH LIMIT = HH Alarm Setpoint
HW 13-TE-10040 HH 150 DEG C = 104 DEG C
A >=
I PUMP P-131001 TILT-
PAD BRG (ACTIVE) LOW LIMIT =
MMS TEMP NDE
0 DEG C HH Alarm Setpoint 13-TAHH-10040
= 104 DEG C
HW 13-TE-10041 HH
A >=
I PUMP P-131001 TILT- 13-TAHH-10041
PAD BRG (ACTIVE)
MMS TEMP NDE HH Alarm Setpoint
= 104 DEG C
HW 13-TE-10042 HH >=
A
PUMP P-131001 TILT-
I 13-TAHH-10042
PAD BRG (NON-
MMS ACTIVE) TEMP NDE 13-TAHH- 13-TAHH-
1002
VOTING 10041/42 10041/42
MCMS TAGS
SHEET :013 SHEET :040 NORMAL = 1
TRIP/ALARM = 0 SHEET NO :013
INPUT OUTPUT
FIELD
13-VZT-10007, 13-VZT-10008,13-VZT-10009, 13-VZT-10010 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10007 H 10 MILS = 3.5 MILS
A >=
MOTOR P-131001-ME
I
BRG RADIAL VIBR LOW LIMIT =
MMS NDE - X
0 MILS H Alarm Setpoint 13-VAH-10007
= 3.5 MILS
HW 13-VZT-10008 H
A >=
I MOTOR P-131001-ME 13-VAH-10008
BRG RADIAL VIBR
MMS NDE - Y H Alarm Setpoint
= 3.5 MILS
HW 13-VZT-10009 H >=
A
MOTOR P-131001-ME
I 13-VAH-10009
MMS
BRG RADIAL VIBR H Alarm Setpoint
DE - X = 3.5 MILS
HW 13-VZT-10010 H >=
A
I MOTOR P-131001-ME 13-VAH-10010
BRG RADIAL VIBR
MMS DE - Y

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10007 10 MILS = 4 MILS
A >=
I MOTOR P-131001-ME
BRG RADIAL VIBR HH LOW LIMIT =
MMS NDE - X
0 MILS HH Alarm Setpoint 13-VAHH-10007
= 4 MILS
HW 13-VZT-10008
A >=
I MOTOR P-131001-ME 13-VAHH-10008
BRG RADIAL VIBR HH 13-VAHH- 13-VAHH-
MMS NDE - Y 1002
HH Alarm Setpoint VOTING 10007/08 10007/08
= 4 MILS
SHEET :014 SHEET :040
HW 13-VZT-10009 >=
A
MOTOR P-131001-ME 13-VAHH-10009
I
BRG RADIAL VIBR HH
MMS H Alarm Setpoint
DE - X
= 4 MILS
HW 13-VZT-10010 >=
A
MOTOR P-131001-ME
I 13-VAHH-10010
BRG RADIAL VIBR HH 13-VAHH-
MMS 1002 13-VAHH-
DE - Y
VOTING 10009/10 10009/10
MCMS TAGS
SHEET :014 SHEET :040 NORMAL = 1
SHEET NO :014
TRIP/ALARM = 0
INPUT OUTPUT
FIELD
13-VZT-10001, 13-VZT-10002,13-VZT-10003, 13-VZT-10004 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10001 H 10 MILS = 5 MILS
A >=
PUMP P-131001
I
RADIAL BRG VIBR LOW LIMIT =
MMS DE - X
0 MILS H Alarm Setpoint 13-VAH-10001
= 5 MILS
HW 13-VZT-10002 H
A >=
I PUMP P-131001 13-VAH-10002
RADIAL BRG VIBR
MMS DE - Y H Alarm Setpoint
= 5 MILS
HW 13-VZT-10003 H >=
A
PUMP P-131001
I 13-VAH-10003
MMS
RADIAL BRG VIBR H Alarm Setpoint
NDE - X = 5 MILS
HW 13-VZT-10004 H >=
A
I PUMP P-131001 13-VAH-10004
RADIAL BRG VIBR
MMS NDE - Y

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10001 10 MILS = 7.5 MILS
A >=
I PUMP P-131001
RADIAL BRG VIBR HH LOW LIMIT =
MMS DE - X
0 MILS HH Alarm Setpoint 13-VAHH-10001
= 7.5 MILS
HW 13-VZT-10002
A >=
I PUMP P-131001 13-VAHH-10002
RADIAL BRG VIBR HH
MMS DE - Y
1002 13-VAHH- 13-VAHH-
VOTING 10001/02 10001/02
HH Alarm Setpoint
= 7.5 MILS SHEET :015 SHEET :040
HW 13-VZT-10003 >=
A
I PUMP P-131001 13-VAHH-10003
RADIAL BRG VIBR HH
MMS H Alarm Setpoint
NDE - X
= 7.5 MILS
HW 13-VZT-10004 >=
A
PUMP P-131001
I 13-VAHH- 13-VAHH- 13-VAHH-10004
MMS
RADIAL BRG VIBR HH 1002
NDE - Y VOTING 10003/04 10003/04 MCMS TAGS
NORMAL = 1
SHEET :015 SHEET :040 SHEET NO :015
TRIP/ALARM = 0
INPUT OUTPUT
FIELD
13-VZT-10005, 13-VZT-100064 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10005 30 MILS = ±15.5 MILS
H
A >=
I PUMP P-131001
SHAFT NDE ACTIAL LOW LIMIT =
MMS SHIFT - Z
-30 MILS H Alarm Setpoint 13-VAH-10005
= ±15.5 MILS
HW 13-VZT-10006 H
A >=
I PUMP P-131001 13-VAH-10006
SHAFT NDE ACTIAL
MMS SHIFT - Z

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10005 30 MILS = ±20.5 MILS
A >=
I PUMP P-131001
SHAFT NDE ACTIAL HH LOW LIMIT =
MMS SHIFT - Z
-30 MILS HH Alarm Setpoint 13-VAHH-10005
= ±20.5 MILS
HW 13-VZT-10006
A >=
I PUMP P-131001
SHAFT NDE ACTIAL HH 13-VAHH-10006
MMS SHIFT - Z

1002 13-VAHH- 13-VAHH-


VOTING 10005/06 10005/06

SHEET :016 SHEET :040

MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0 SHEET NO :016
INPUT OUTPUT
FIELD
13-TE-10052, 13-TE-10053,13-TE-10054, 13-TE-10055 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10052 H 150 DEG C = 100 DEG C
A >=
VOITH CPLNG GB-
I
131001 RADIAL BRG LOW LIMIT =
MMS TEMP
0 DEG C H Alarm Setpoint 13-TAH-10052
= 100 DEG C
HW 13-TE-10053 H
A >=
I VOITH CPLNG GB- 13-TAH-10053
131001 THRUST BRG
MMS TEMP H Alarm Setpoint
= 100 DEG C
HW 13-TE-100054 H >=
A
VOITH CPLNG GB-
I 13-TAH-10054
MMS
131001 THRUST BRG H Alarm Setpoint
TEMP = 100 DEG C
HW 13-TE-100055 H >=
A
I VOITH CPLNG GB- 13-TAH-10055
131001 RADIAL BRG
MMS TEMP

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10052 150 DEG C = 105 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG HH LOW LIMIT =
MMS TEMP
0 DEG C HH Alarm Setpoint 13-TAHH-10052
= 105 DEG C
HW 13-TE-10053
A >=
I VOITH CPLNG GB- 13-TAHH-10053
131001 THRUST BRG HH
MMS TEMP HH Alarm Setpoint
= 105 DEG C
HW 13-TE-10054 >=
A
I VOITH CPLNG GB- 13-TAHH- 13-TAHH- 13-TAHH-10054
131001 THRUST BRG HH 1002
MMS H Alarm Setpoint 10053/54 10053/54
TEMP VOTING
= 105 DEG C
SHEET :017 SHEET :040
HW 13-VZT-10055 >=
A
I VOITH CPLNG GB- 13-TAHH-10055
131001 RADIAL BRG HH
MMS TEMP

13-TAHH- 13-TAHH- MCMS TAGS


AND 10052/55 10052/55 NORMAL = 1
TRIP/ALARM = 0 SHEET NO :017
SHEET :017 SHEET :040
INPUT OUTPUT
FIELD
13-TE-10056, 13-TE-10057,13-TE-10058, 13-TE-10059 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10056 H 150 DEG C = 100 DEG C
A >=
VOITH CPLNG GB-
I
131001 RADIAL BRG LOW LIMIT =
MMS TEMP
0 DEG C H Alarm Setpoint 13-TAH-10056
= 100 DEG C
HW 13-TE-10057 H
A >=
I VOITH CPLNG GB- 13-TAH-10057
131001 THRUST BRG
MMS TEMP H Alarm Setpoint
= 100 DEG C
HW 13-TE-100058 H >=
A
VOITH CPLNG GB-
I 13-TAH-10058
MMS
131001 THRUST BRG H Alarm Setpoint
TEMP = 100 DEG C
HW 13-TE-100059 H >=
A
I VOITH CPLNG GB- 13-TAH-10059
131001 RADIAL BRG
MMS TEMP

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10056 150 DEG C = 105 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG HH LOW LIMIT =
MMS TEMP
0 DEG C HH Alarm Setpoint 13-TAHH-10056
= 105 DEG C
HW 13-TE-10057
A >=
I VOITH CPLNG GB- 13-TAHH-10057
131001 THRUST BRG HH
MMS TEMP HH Alarm Setpoint
= 105 DEG C
HW 13-TE-10058 >=
A
VOITH CPLNG GB- 13-TAHH- 13-TAHH- 13-TAHH-10058
I 1002
131001 THRUST BRG HH 10057/58
MMS H Alarm Setpoint VOTING 10057/58
TEMP
= 105 DEG C
SHEET :018 SHEET :040
HW 13-VZT-10059 >=
A
I VOITH CPLNG GB- 13-TAHH-10059
131001 RADIAL BRG HH
MMS TEMP

13-TAHH- 13-TAHH- MCMS TAGS


AND 10056/59 10056/59 NORMAL = 1
TRIP/ALARM = 0 SHEET NO :018
SHEET :018 SHEET :040
INPUT OUTPUT
FIELD
13-VZT-10011, 13-VZT-10012,13-VZT-10013 ALARM FIELD

H Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 H = 220 MIL/S
10 MILS
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR
0 MILS H Alarm Setpoint 13-VAH-10011
HIGH LIMIT = = ±22.2 MILS
HW 13-VZT-10012 H 40 MILS >=
A
I VOITH CPLNG GB- LOW LIMIT = 13-VAH-10012
131001 AXL 1ST
MMS H Alarm Setpoint
SHAFT VIBR - Z -40 MILS
= ±22.2 MILS
13-VZT-10013 HIGH LIMIT = >=
HW H 40 MILS
A
VOITH CPLNG GB-
I LOW LIMIT = 13-VAH-10013
131001 AXL 2ND
MMS SHAFT VIBR - Z -40 MILS

HH Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 = 315 MIL/S
10 MIL/S
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR HH
0 MIL/S HH Alarm Setpoint 13-VAHH-10011
HIGH LIMIT = = ±27.2 MILS
HW 13-VZT-10012
40 MILS >=
A
I VOITH CPLNG GB- LOW LIMIT = 13-VAHH-10012
131001 AXL 1ST HH
MMS SHAFT VIBR - Z -40 MILS HH Alarm Setpoint
= ±27.2 MILS
13-VZT-10013 HIGH LIMIT = >=
HW
40 MILS
A
VOITH CPLNG GB- 13-VAHH-10013
I LOW LIMIT =
131001 AXL 2ND HH
MMS SHAFT VIBR - Z -40 MILS

13-VAHH- 13-VAHH-
10011/12/ 10011/12/
AND
13 13
MCMS TAGS
SHEET :019 SHEET :040 NORMAL = 1
TRIP/ALARM = 0 SHEET NO :019
INPUT OUTPUT
FIELD
13-VZT-10014, 13-VZT-10012,15-VZT-10016 ALARM FIELD

H Alarm Setpoint
13-VZT-10014 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VAH-10014
= 16 MM/S
HW 13-VZT-10015 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VAH-10015
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10016 H >=
A
LO/WO COOLER E-
I 13-VAH-10016
131002/E-131003
MMS FAN (K-131002) VIBR

MCMS TAGS
HH Alarm Setpoint NORMAL = 1
HIGH LIMIT =
HW 13-VZT-10014 = 17.8 MM/S TRIP/ALARM = 0
63.5 MM/S
A >=
I LO/WO COOLER E- LOW LIMIT = 13-VAHH-10014
131002/E-131003 HH
MMS FAN (K-131001) VIBR 0 MM/S HH Alarm Setpoint
= 17.8 MM/S
HW 13-VZT-10015
A LO/WO COOLER E- >=
I 131002/E-131003 13-VAHH-10015
FAN MOTOR (K- HH
MMS 131001-ME) VIBR 1OO2 13-XZ-131007 A/B
VOTING V HW
LO/WO COOLER
FAN K-131001 W
HH Alarm Setpoint HIHI VIB TRIP IPS
= 17.8 MM/S
HIGH LIMIT =
HW 13-VZT-10016 >=
63.5 MM/S 13-VAHH-10016
A
LO/WO COOLER E- 1OO2 13-XZ-1310078A/B V HW
I LOW LIMIT =
131002/E-131003 HH
MMS VOTING LO/WO COOLER
FAN (K-131002) VIBR 0 MM/S
HH Alarm Setpoint FAN K-131002 W
HW 13-VZT-10017 = 17.8 MM/S HIHI VIB TRIP IPS
A >=
I LO/WO COOLER E- 13-VAHH-10017
131002/E-131003 HH
MMS FAN (K-131001) VIBR SHEET NO :020
INPUT OUTPUT
FIELD
13-VZT-10017, 13-VZT-10018,15-VZT-10019 ALARM FIELD

H Alarm Setpoint
13-VZT-10017 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VAH-10017
= 16 MM/S
HW 13-VZT-10018 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VAH-10018
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10019 H >=
A
LO/WO COOLER E-
I 13-VAH-10019
131002/E-131003
MMS FAN (K-131002) VIBR

MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0

HH Alarm Setpoint
HIGH LIMIT = = 17.8 MM/S
HW 13-VZT-10018
63.5 MM/S >=
A LO/WO COOLER E-
I 131002/E-131003
FAN MOTOR (K- HH LOW LIMIT = 13-VAHH-10018
MMS 131001-ME) VIBR HH Alarm Setpoint
0 MM/S = 17.8 MM/S
HW 13-VZT-10019 >=
A
LO/WO COOLER E- 13-VAHH-10019
I
131002/E-131003 HH
MMS FAN (K-131002) VIBR
13-XZ-1310079A/B V HW
1OO2 LO/WO COOLER
VOTING FAN K-131003 HIHI W
VIB TRIP IPS

SHEET NO :021
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 ALARM FIELD

HW 13-EMRN-10001
D
RUNNING =1
I RUNNING FB
DCS NOT RUNNING =0

AND
13-EMAV-10001
HW D
OR
DCS I AVAIABLE FB AVAILABLE=1
NOT AVAILABLE =0 START 13-EMST-10001 V
AND S Q
START HW
W MCC
SR
R
SK S 13-HS-10202 STOP 13-EMSP-10001 V
A
O STOP HW
F AUTO /MANUAL AUTO=1
W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
AND TIMER
T#1S

SK S 13-EMST-10001
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S 13-EMSP-10001
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :023 SHEET :022 SHEET NO :022
SHEET :023 SHEET :022
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

13-TAH- 13-TAH-
10066 10066
SHEET :005 SHEET :023
AUTO AUTO
START START
SHEET :023 SHEET :022
13-TAH- 13-TAH-
10067 OR
10067
SHEET :005 SHEET :023

ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :023

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :023 AND

13-PALL- 13-PALL-
10088 10088
INTER INTER
SHEET :004 SHEET :023
LOCK LOCK
SHEET :023 SHEET :022
SP_SEQ SP_SEQ
ST-4 ST-4
OR
SHEET :048 SHEET: 023

TRP SEQ TRP SEQ


ST-3 ST-3
SHEET :053 SHEET: 023

SHEET NO :023
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022,10023 – MAIN/STANDBY SELECTION ALARM FIELD

AND MAIN MAIN


PUMP PUMP
SK S 13-HS-10203 B A SHEET :024 SHEET :025
A
O
AUTO /MANUAL
F AUTO=1
SELECTION M
DCS T MANUAL =0
FROM GRAPHICS

SK S 13-HS-10204
O
F DUTY/STANDY
M
DCS T FROM GRAPHICS ST STBY STBY
PUMP PUMP
A
SK S 13-HS-10206 AND B SHEET :024 SHEET :026
O
F DUTY/STANDY
S
DCS T FROM GRAPHICS ST

SK S 13-HS-10205 A
O AUTO /MANUAL
F SELECTION AUTO=1
M
DCS T FROM GRAPHICS MANUAL =0

SHEET NO :024
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022 - MAIN PUMP ALARM FIELD
MAIN MAIN
PUMP PUMP
HW 13-PMRN-10004
D SHEET :024 SHEET :025
RUNNING =1
I PUMP RUNNING FB
DCS NOT RUNNING =0

AND
13-PMAV-10004
HW D
OR
DCS I PUMP AVAIABLE FB AVAILABLE=1
NOT AVAILABLE =0 START 13-PMST-10004 V
AND S Q
MAIN PUMP HW
START W MCC
SR
R
SK S 13-HS-10203 STOP 13-PMSP-10004 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
TIMER
T#1S
AND

SK S 13-PMST-10004
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S 13-PMSP-10004
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :027 SHEET :025 SHEET NO :025
SHEET :027 SHEET :025
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10023 – STANDBY PUMP ALARM FIELD
STBY STBY
PUMP PUMP
HW 13-PMRN-10005
D SHEET :024 SHEET :026
PUMP RUNNING RUNNING =1
I
DCS FB NOT RUNNING =0

AND
13-PMAV-10005
HW D
OR
DCS I PUMP AVAIABLE AVAILABLE=1
NOT AVAILABLE =0 START 13-PMST-10005 V
AND S Q
STBY PUMP HW
START W MCC
SR
R
SK S 13-HS-10205 STOP 13-PMSP-10005 V
A
O AUTO /MANUAL STBY PUMP HW
F SELECTION STOP W MCC
M AUTO=1
DCS T FROM GRAPHICS MANUAL =0

PULSE
AND TIMER
T#1S

SK S 13-PMST-10005
O
F MANUAL START
ST
DCS T FROM GRAPHICS ST

SK S 13-PMSP-10005
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START
INTER INTER
SHEET :028 SHEET :026 LOCK LOCK SHEET NO :026
SHEET :028 SHEET :026
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM MAIN PUMP 13-KS-10022 – INTERLOCK ALARM FIELD

13-LAL- AUTO AUTO


13-LAL-
10022 START START
10022 AND
SHEET :006 SHEET :027 SHEET :027 SHEET :025

13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :027

13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :027
ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :027

13-PAH- TRP SEQ TRP SEQ


13-PAH-
10085 ST-3 ST-3
10085
SHEET :053 SHEET: 027
SHEET :003 SHEET :027 OR
INTER INTER
SP_SEQ SP_SEQ LOCK LOCK
13-PAH- 13-PAH- ST-4 ST-4 OR
10087 10087 SHEET :027 SHEET :025
SHEET :048 SHEET: 027
SHEET :003 SHEET :027

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :027 `

AND
13-PALL- 13-PALL-
10088 10088
SHEET :004 SHEET :027

SHEET NO :027
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

13-LAL- AUTO AUTO


13-LAL-
10022 START START
10022 AND
SHEET :006 SHEET :028 SHEET :028 SHEET :026

13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :028

13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :028
ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :028

TRP SEQ TRP SEQ


13-PAH- 13-PAH- ST-3 ST-3
10085 10085 SHEET :053 SHEET: 028
SHEET :003 SHEET :028 INTER INTER
OR OR LOCK LOCK
SP_SEQ SP_SEQ
ST-4 ST-4 SHEET :028 SHEET :026
13-PAH- 13-PAH-
10087 10087 SHEET :048 SHEET: 028
SHEET :003 SHEET :028
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :028
AND
13-PALL- 13-PALL-
10088 10088
SHEET :004 SHEET :028

SHEET NO :028
INPUT OUTPUT
DCS/FIELD
AUX LO PUMP P-131006 ALARM FIELD

HW 13-PMRN-131006
D
AUX LO PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

AND
HW 13-PMAV-131006
D
OR
AUX LO PUMP AVAILABLE=1
I
DCS AVAIABLE FB
NOT AVAILABLE =0 START 13-PMST-131006 V
AND S Q
AUX LO PUMP HW
START W MCC
SR
R
SK S AUX LO PUMP STOP 13-PMSP-131006 V
A
O AUX LO PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
AND TIMER
T#1S

SK S AUX LO PUMP
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S AUX LO PUMP
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
SHEET :029 LOCK LOCK SHEET NO :029
SHEET :030
SHEET :030 SHEET :029
INPUT OUTPUT
DCS/FIELD
AUX LO PUMP 13-KS-10001 – INTERLOCK ALARM FIELD

13-PAL- 13-PAL-
10081 10081
HW 13-PMRN-131006 SHEET :007 SHEET :030
D
AND AUTO AUTO
AUX LO PUMP RUNNING =1 START START
I
DCS RUNNING FB NOT RUNNING =0
SHEET :030 SHEET :029

13-LAL- 13-LAL- AND OR


10021 10021

SHEET :007 SHEET :030

ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :030

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :030

13-PALL- 13-PALL-
10088 10088 INTER INTER
SHEET :004 SHEET :030 LOCK LOCK
SHEET :030 SHEET :029
13-PAH- 13-PAH-
10081 10081
SHEET :007 SHEET :030 OR

13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :030
SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :048 SHEET: 030

TRP SEQ TRP SEQ


ST-3 ST-3
SHEET :053 SHEET: 030 SHEET NO :030
INPUT OUTPUT
IPS/FIELD
LO/WO COOLER FAN 13-UZ-10031A ALARM FIELD

HW 13-EMRN-10031A LOGIC IN LO/WO


D COOLER
LO/WO COOLER FAN RUNNING =1 SAFEGUARDING LOGIC
I (13-UZ-10031A)IPS
IPS RUNNING FB NOT RUNNING =0
SYSTEM

AND
HW 13-EMAV-10031A
D
OR
LO/WO COOLER FAN AVAILABLE=1
I
IPS AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
SK S LO/WO COOLER TIMER
O FAN AND T#1S
F MANUAL START
DCS T FROM GRAPHICS ST

SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS

13-KMZA-
SK S 13101_2_3
O AND PULSE
F SOFT SIGNAL FROM
IPS TO DCS TO TIMER
IPS T T#1S
START LO/WO OR
COOLER

13-KMXZ-13101
SK S
O
F TRIP LO/WO
IPS T COOLER FAN K-
13101 MOTOR SHEET NO :031
INPUT OUTPUT
IPS/FIELD
LO/WO COOLER FAN 13-UZ-10031B ALARM FIELD

LOGIC IN LO/WO
HW 13-EMRN-10031B COOLER
D SAFEGUARDING LOGIC
LO/WO COOLER FAN RUNNING =1 (13-UZ-10031A)IPS
I SYSTEM
IPS RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
I
IPS AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031B V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031B V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
SK S LO/WO COOLER TIMER
O FAN AND T#1S
F MANUAL START
DCS T FROM GRAPHICS ST

SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS

13-KMZA-
SK S 13101_2_3
O AND PULSE
F SOFT SIGNAL FROM
IPS TO DCS TO TIMER
IPS T START LO/WO T#1S
OR
COOLER

13-KMZA-
SK S 131001_2_3
O
F SOFT SIGNAL FROM
DCS TO IPS TO
IPS T TRIP/STOP LO/WO SHEET NO :032
COOLER
INPUT OUTPUT
IPS/FIELD
LO/WO COOLER FAN 13-UZ-10031C ALARM FIELD

LOGIC IN LO/WO
HW 13-EMRN-10031C COOLER
D SAFEGUARDING LOGIC
LO/WO COOLER FAN RUNNING =1 (13-UZ-10031A)IPS
I SYSTEM
IPS RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
I
IPS AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S LO/WO COOLER PULSE


O FAN AND TIMER
T#1S
F MANUAL START
ST
DCS T FROM GRAPHICS

SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS

13-KMZA-
S 13101_2_3
SK O
SOFT SIGNAL FROM AND PULSE
F TIMER
IPS T DCS TO IPS TO
START LO/WO T#1S
OR
COOLER

13-KMZA-
SK S 131001_2_3
O
F SOFT SIGNAL FROM
DCS TO IPS TO
IPS T TRIP/STOP LO/WO
COOLER SHEET NO :033
INPUT OUTPUT
DCS/FIELD
LO/WO FAN COOLER 13-KS-10013A/B/C – CONTROL LOGIC ALARM FIELD

13-PAL- 13-PAL- 13-KMZA-


10081 10081 13101_2_3 S SK
SHEET :007 SHEET :034 O
SOFT SIGNAL FROM
DCS TO IPS TO
F
AND TRIP/STOP LO/WO T IPS
13-LAL- 13-LAL- COOLER
OR
10021 10021
SOFT SIGNAL FROM 13-KS-
SHEET :007 SHEET :034
10001(DCS) TO 13-UZ-10006 IPS
TO START LO/WO COOLER 13-
ST_SEQ ST_SEQ UZ-10031A(IPS)
ST-2 ST-2
SHEET :043 SHEET :034 TO
SHEET :031
SHEET :032
SHEET: 033

13-KMXZ-13101
S SK
O
TRIP LO/WO F
COOLER FAN K- T IPS
13101 MOTOR
SK S 13-XZ-13107A/B
O 13-KMXZ-13102
F LO/WO COOLER FAN S SK
K-131001 HIHI VIB
IPS T TRIP O
TRIP LO/WO F
SK S 13-XZ-13108A/B COOLER FAN K- T IPS
O 13102 MOTOR
LO/WO COOLER FAN
F
K-131002 HIHI VIB
IPS T TRIP 13-KMXZ-13103
S SK
SK S 13-XZ-13109A/B O
OR
O TRIP LO/WO F
LO/WO COOLER FAN
F COOLER FAN K- T IPS
K-131003 HIHI VIB
IPS T TRIP
13103 MOTOR

SP_SEQ SP_SEQ
ST-4 ST-4 SOFT SIGNAL FROM 13-KS-
10001(DCS) TO 13-UZ-10006 IPS
SHEET :048 SHEET: 034 TO TRIP/STOP LO/WO COOLER
13-UZ-10031A(IPS)
TRP SEQ TRP SEQ
ST-3 ST-3
SHEET :053 SHEET: 034 SHEET NO :034
INPUT OUTPUT
DCS/FIELD
13-KS-10024 L.O HEATER E-131004 CONTROL LOGIC ALARM FIELD

HW 13-EMRN-10004
D
LO HEATER RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

AND
13-EMAV-10004
HW D
OR
LO HEATER AVAILABLE=1
DCS I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-131004 V
AND S Q
LO HEATER HW
START W MCC
SR
R
SK S LO HEATER STOP 13-EMSP-131004 V
A
O LO HEATER HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
AND TIMER
T#1S

SK S LO HEATER
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S LO HEATER
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :036 SHEET :035 SHEET NO :035
SHEET :036 SHEET :035
INPUT OUTPUT
DCS/FIELD
13-KS-10024 L.O HEATER E-131004 CONTROL LOGIC ALARM FIELD

13-TAL- 13-TAL- AUTO AUTO


10064 10064 START START
SHEET :011 SHEET :036 SHEET :036 SHEET :035

13-TAH- 13-TAH- INTER INTER


10060 10060 LOCK LOCK
SHEET :011 SHEET :036 SHEET :036 SHEET :035

OR
13-LAL- 13-LAL-
10021 10021
SHEET :007 SHEET :036

TRP SEQ TRP SEQ TON


END END TIMER
T#60S
SHEET :054 SHEET :036

SHEET NO :036
INPUT OUTPUT
DCS/FIELD
MANI PUMP -P-131001 ALARM FIELD

HW 13-PMRN-131001
D
MAIN PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

AND
HW 13-PMAV-131001
D
OR
MAIN PUMP AVAILABLE=1
I
DCS AVAILABLE FB
NOT AVAILABLE =0 START 13-PMST-131001 V
AND S Q MAIN PUMP HW
START W MCC
SR
R
SK S MAIN PUMP STOP 13-PMSP-131001 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

PULSE
AND TIMER
T#1S

SK S MAIN PUMP
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S MAIN PUMP
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :038 SHEET :037 SHEET NO :037
SHEET :038 SHEET :037
INPUT OUTPUT
DCS/FIELD
MANI PUMP -P-131001 CONTROL LOGIC ALARM FIELD

STARUP PERMISSIVE CONDITION

STARTUP STARTUP
PERM PERM AUTO AUTO
START START
SHEET :039 SHEET :038 AND
SHEET :038 SHEET :037

ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :046 SHEET :038

SP_SEQ SP_SEQ INTER INTER


ST-2 ST-2 LOCK LOCK
OR
SHEET :048 SHEET: 038 SHEET :038 SHEET :037

TRP SEQ TRP SEQ


ST-1 ST-1
SHEET :052 SHEET: 038

SHEET NO :038
INPUT OUTPUT
MCMS/IPS/DCS / FIELD
STARTUP PERMISSIVE 13-KS-10001, WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

SK S 13-FZT-10001
O
PUMP-P-131001
F
DISCHARGE FLOW
IPS T LOW LOW

SK S 13-PZT - 10014
O
PUMP-P-131001
F
SUCTION PRESSURE
IPS T STARUP PERMISSIVE CONDITION
LOW LOW

SK S 13-PZT-10010A/B
O STARTUP STARTUP
PUMP-P-131001 PERM PERM
F
DISCHARGE
IPS T PRESSURE HI HI
SHEET :039 SHEET :038
SK S 13-HZS-10003 SHEET :041
O PUMP-P-131001
F EMERGENCY TRIP
PB ACTIVATED
IPS T FROM FILED
SK 13-HZS-10016
S PUMP-P-131001
O EMERGENCY TRIP
F PB ACTIVATED
IPS
T FROM SROS 13-PALL- 13-PALL- AND
CONSOLE 10086 10086

SHEET :039 13-PALL- 13-PALL-


SHEET :004
10088 10088
SK S 13-FIC-10002 SHEET :004 SHEET :039
O
MIINIMUM BY-PASS
F
LINE ON AND IN
DCS T AUTO MODE 13-TAHH- 13-TAHH-
10061 10061

SHEET :009 SHEET :039 13-TAHH- 13-TAHH-


10063 10063
SK 13-XZ-13101A/B
S SHEET :009 SHEET :039
O
WTR INJ PUMP P-
IPS F 131001 MCMS TO IPS
T 13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :039
SK S 13-ZIC-10001
O
F CLOSE FB FORM
SHEET NO :039
IPS T DISCHARGE VALVE
INPUT OUTPUT
MCMS / FIELD
MCMS TRIP LOGIC TO IPS ALARM FIELD

13-TAHH- 13-TAHH-
10046A/47A 10046A/47A
/48A /48A

SHEET :011 SHEET :040

13-TAHH- 13-TAHH-
10043/44/45 10043/44/45

SHEET :011-1 SHEET :040

13-TAHH- 13-TAHH-
10037/38 10037/38
13-VAHH- 13-VAHH-
SHEET :013 SHEET :040
10007/08 10007/08

SHEET :014 SHEET :040


13-TAHH- 13-TAHH-
10039/40 10039/40
13-VAHH- 13-VAHH- 13-XZ-13101A/B
SHEET :013 SHEET :040 10009/10 10009/10 V HW
WTR INJ PUMP P-
SHEET :014 SHEET :040 131001 MCMS TO W
AND
IPS IPS
13-TAHH- 13-TAHH-
10041/42 10041/42 13-VAHH- 13-VAHH-
SHEET :013 SHEET :040 10001/02 10001/02
SHEET :015 SHEET :040
13-TAHH- 13-TAHH-
10053/54 10053/54
13-VAHH- 13-VAHH-
SHEET :017 SHEET :040 10003/04 10003/04

13-TAHH- 13-TAHH- SHEET :015 SHEET :040


10052/55 10052/55

SHEET :017 SHEET :040 13-VAHH- 13-VAHH-


10005/06 10005/06
13-TAHH- 13-TAHH- SHEET :016 SHEET :040
10057/58 10057/58
SHEET :018 SHEET :040

13-TAHH- 13-TAHH- 13-VAHH- 13-VAHH-


10056/59 10056/59 10011/12/ 10011/12/
13 13 SHEET NO :040
SHEET :018 SHEET :040 SHEET :001 SHEET :001
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

START SEQUENCE FROM GRAPHICS`

SK S 13-PMST-10001
O START
F START SEQ FROM SEQ
ST
ST
DCS T GRAPHICS
START SEQ
SK S 13-ABORT-10001
O ABORT ABORT
F ABORT SEQ FROM SEQ SEQ
SP
DCS T GRAPHICS SHEET :041 SHEET :041,042,043,04 ABORT SEQ
4,045,046,047
SK S 13-REST-10001
O RESET RESET
F RESET SEQ FROM SEQ SEQ
ST
ST
DCS T GRAPHICS SHEET :041 SHEET :047
RESET SEQ

SEQUENCE START`

START
SEQ

AND
STARTUP STARTUP
PERM PERM S Q
ST_SEQ ST_SEQ
SHEET :039 SHEET :041 SR ON ON
R SHEET :041 SHEET :042
ST_SEQ ST_SEQ
END END
SHEET :047 SHEET :041 OR

ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :041

SHEET NO :041
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STEP 1 – VENT VALVE (OPEN/CLOSE) 13-KSV-10002

ST_SEQ ST_SEQ
ON ON

SHEET :041 SHEET :042 AND S Q ST_SEQ


HW 13-PMRN-10001A `` ST-1
D
O 13-KSY-10002 HW
SR V
MAIN PUMP RUNNING =1 VENT VALVE -
I C W DCS
DCS RUNNING FB NOT RUNNING =0 SOV
R
ST_SEQ ST_SEQ
END END
SHEET :047 SHEET :042 OR

ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :042

ST_SEQ
13-ZIO-10002 ST-1 AND
HW TON ST_SEQ
D
TIMER ST-01A
OPEN FB FORM T#60S
I
DCS VENT VALVE

ST_SEQ
ST-01A S Q ST_SEQ ST_SEQ
SR ST-01B ST-01B
R SHEET :042 SHEET :043
ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET: 042

ABORT ABORT OR
SEQ SEQ
SHEET :041 SHEET :042

SHEET NO :042
INPUT OUTPUT
IPS/ DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STEP 2 –AUX LO PUMP AND LO/WO COOLER START

ST_SEQ ST_SEQ
ST-01B ST-01B ST_SEQ ST_SEQ
HW 13-ZIC-10002 AND S1 C
D SHEET :042 SHEET :043 ST-2 ST-2
SR
CLOSE FB FORM SHEET :043 SHEET: 030
I
DCS VENT VALVE SHEET :034
R
ST_SEQ ST_SEQ SK
ACTIVATE MCMS S
END END
TRIP MULTIPLY O
SHEET :047 SHEET :043 OR x3 F
T
IPS
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :043

SK S 13-EMRN-10031A
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

SK S 13-EMRN-10031B ST_SEQ ST_SEQ


O ST-2A ST-2A
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0 SHEET :044 SHEET :044

SK S 13-EMRN-10031C
O
AND
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :043
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

SHEET NO :043
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STEP 2 A–AUX LO PUMP PRESSURE CHECK , START SEAL SYSTEM AND SEAL SYSTEM
COOLER
SK S 13-EMRN-10031A
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

SK S 13-EMRN-10031B
O TON ST_SEQ ST_SEQ
S1 C ST-2B ST-2B
F LO/WO COOLER FAN RUNNING =1 TIMER
IPS T RUNNING FB NOT RUNNING =0 T#60S SR SHEET :045 SHEET :023
SHEET :027
SK S 13-EMRN-10031C R SHEET :028
O ST_SEQ ST_SEQ
F LO/WO COOLER FAN RUNNING =1 END END
IPS T RUNNING FB NOT RUNNING =0
SHEET :047 SHEET :044 OR
AND
ST_SEQ ST_SEQ ABORT ABORT
ST-2A ST-2A SEQ SEQ
SHEET :044 SHEET :045 SHEET :041 SHEET :044
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
I
SDE RUNNING FB NOT RUNNING =0

13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :045

SHEET NO :044
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STEP 2B – SEAL SYSTEM PRESSURE CHECK


SK S 13-EMRN-10031A
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

SK S 13-EMRN-10031B
O TON ST_SEQ ST_SEQ
S1 C ST-2C ST-2C
F LO/WO COOLER FAN RUNNING =1 TIMER
IPS T RUNNING FB NOT RUNNING =0 T#60S SR SHEET :045 SHEET :030
SHEET :046
SK S 13-EMRN-10031C R
O ST_SEQ ST_SEQ
F LO/WO COOLER FAN RUNNING =1 END END
IPS T RUNNING FB NOT RUNNING =0
SHEET :047 SHEET :046 OR
AND
ST_SEQ ST_SEQ ABORT ABORT
ST-2B ST-2B SEQ SEQ

SHEET :044 SHEET :045 SHEET :041 SHEET :045


13-PMRN-10001
HW D

DCS
AUX LO PUMP RUNNING =1
I RUNNING FB NOT RUNNING =0

13-PAL- 13-PAL-
10085 10085
SHEET :003 SHEET :027
13-PAL- 13-PAL-
10087 10087

HW 13-EMRN-10001 SHEET :003 SHEET :027


D
SEAL SYSTEM
RUNNING =1
I COOLER FAN
DCS RUNNING FB NOT RUNNING =0

HW 13-PMRN-10004
D
SEAL SYSTEM PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0
OR
HW 13-PMRN-10005
D
SEAL SYSTEM PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0 SHEET NO :045
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STEP 3-- MAIN MOTOR START ,RECYCLE VALVE (FLOW CHECK), SPEED CHECK, DISCHARGE VALVE OPEN

SK S 13-FIC-10002 ST_SEQ ST_SEQ


O S1 C ST-3 ST-3
MIINIMUM BY-PASS
F LINE ON AND IN SR
DCS T SHEET :046 SHEET :038
AUTO MODE AND
R
ST_SEQ ST_SEQ ST_SEQ ST_SEQ
ST-2B ST-2B END END
SHEET :045 SHEET :046 SHEET :047 SHEET :046 OR
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :046

HW 13-PMRN-10001A
D
MAIN PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

ST_SEQ ST_SEQ
ST-3 ST-3 ST_SEQ ST_SEQ
SHEET :046 SHEET :046 ST-3A ST-3A
AND
SK S 13-FZT-10001 SHEET :046 SHEET :046
O
PUMP-P-131001
F
DISCHARGE FLOW
DCS T LOW LOW

SK S 13-VFD SPEED
O
PUMP-P-131001 VFD
F
SPEED ABOVE SET
DCS T SPEED REQUIREMENT

ST_SEQ ST_SEQ O 13-UZ-10007 S SK


C O
ST-3A ST-3A S1 DISCHARGE F
SR VALVE - SOV T IPS
SHEET :046 SHEET :046 ST_SEQ ST_SEQ
END END ST_SEQ ST_SEQ
R ST-4 ST-4
SHEET :047 SHEET :046 OR
SHEET :046 SHEET :047
ABORT ABORT
SEQ SEQ SHEET NO :046
SHEET :041 SHEET :046
INPUT OUTPUT
DCS / FIELD
START SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD
STEP 4—AUX LO PUMP STOP

ST_SEQ ST_SEQ
ST-4 ST-4 TON
TIMER
SHEET :046 SHEET :047 AND T#120S
SK S 13-ZIO-10001 S1 C
O SR
F OPEN FB FORM ST_SEQ
ST_SEQ
IPS T DISCHARGE VALVE
R ST-4A ST-4A
SHEET :047 SHEET :030

ST_SEQ ST_SEQ
END END
SHEET :047 SHEET :047 OR
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :047

ST_SEQ ST_SEQ ST_SEQ ST_SEQ


ST-4A ST-4A END END
OR
SHEET :047 SHEET :047 SHEET :047 SHEET :047
AND
13-PMRN-10001
HW D

DCS
AUX LO PUMP RUNNING =1
I RUNNING FB NOT RUNNING =0

RESET RESET
SEQ SEQ
SHEET :041 SHEET :047

SHEET NO :047
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

STOP SEQUENCE FROM GRAPHICS`

SK S
O STOP
F STOP SEQ FROM SEQ
ST
ST
DCS T GRAPHICS
STOP SEQ

START AUX LO PUMP

STOP
SEQ
SP_SEQ SP_SEQ
AND TON
HW 13-PMRN-10001A ST-1 ST-1
D TIMER
T#5S SHEET :048 SHEET: 048
MAIN PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

STOP MAIN PUMP

SP_SEQ SP_SEQ
ST-1 ST-1
SHEET :048 SHEET: 048
AND
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1 TON S Q SP_SEQ SP_SEQ
I ST-2 ST-2
DCS RUNNING FB NOT RUNNING =0 TIMER
T#10S SR
SHEET :048 SHEET: 049
R SHEET: 038
SP_SEQ SP_SEQ
END END
SHEET :050 SHEET :050
OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :048

SHEET NO :048
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

DISCHARGE VALVE CLOSE AND RECYCLE OPEN

13-UZ-10001 S SK
SP_SEQ SP_SEQ O
DISCHARGE F
ST-2 ST-2 C VALVE - SOV
T IPS
SP_SEQ SP_SEQ
SHEET :048 SHEET: 049 TON
HW 13-PMRN-10001A ST-3 ST-3
D TIMER
T#150S SHEET :049 SHEET: 049 13-FIC-10002
O S SK
MAIN PUMP RUNNING =1 AND
I O
DCS RUNNING FB NOT RUNNING =0 MIINIMUM BY-PASS
LINE ON AND IN F
AUTO MODE T DCS
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

STOP --AUX LO PUMP ,SEAL SYSTEM ,SEAL COOLER,LO/WO COOLER

SK S 13-ZIC-10001
O
F CLOSE FB FORM
IPS T DISCHARGE VALVE

SP_SEQ SP_SEQ AND


ST-3 ST-3
SHEET :049 SHEET: 049 S Q SP_SEQ SP_SEQ
ST-4 ST-4
SK S 13-FZT-10001
SR
O SHEET :049 SHEET: 050
PUMP-P-131001 SHEET: 030
F R
DISCHARGE FLOW SP_SEQ SP SEQ
IPS T LOW LOW SHEET:027
END END SHEET:028
SHEET :050 SHEET :049 SHEET:023
SHEET:034
OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :048

SHEET NO :049
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

SK S 13-EMRN-10031A
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

SK S 13-EMRN-10031B
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

SK S 13-EMRN-10031C
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0 SP_SEQ SP SEQ
END END

SP_SEQ SP_SEQ AND SHEET :050 SHEET :049


ST-4 ST-4
SHEET :048 SHEET: 050
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

SK S 13-ZIC-10001
O
F CLOSE FB FORM
DCS T DISCHARGE VALVE

HW 13-EMRN-10001
D
SEAL SYSTEM
RUNNING =1
I COOLER FAN
DCS RUNNING FB NOT RUNNING =0
13-PMRN-10004
HW D

DCS SEAL SYSTEM PUMP RUNNING =1


I RUNNING FB NOT RUNNING =0
OR
HW 13-PMRN-10005
D
SEAL SYSTEM PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

SHEET NO :050
INPUT OUTPUT
DCS / FIELD
TRIP CONDITION – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

SK S 13-FZT-10001
O
PUMP-P-131001
F
DISCHARGE FLOW
IPS T LOW LOW

SK S 13-PZT - 10014
O
PUMP-P-131001
F
SUCTION PRESSURE
IPS T LOW LOW

SK S 13-PZT-10010A/B
O
PUMP-P-131001
F
DISCHARGE
IPS T PRESSURE HI HI

SK S 13-HZS-10003
O PUMP-P-131001
F EMERGENCY TRIP
PB ACTIVATED
IPS T TRIP CONDITION
FROM FILED
13-HZS-10016
SK S PUMP-P-131001 13- 13-
O EMERGENCY TRIP PMXZ- PMXZ-
F PB ACTIVATED 10001 10001
IPS FROM SROS OR
T
CONSOLE SHEET :051 SHEET :052
13-PALL- 13-PALL-
10086 10086

SHEET :004 SHEET :039 13-PALL- 13-PALL-


10088 10088

SHEET :004 SHEET :039

13-TAHH- 13-TAHH-
10061 10061
13-TAHH- 13-TAHH-
SHEET :009 SHEET :039 10063
10063
SK 13-XZ-13101A/B
S SHEET :009 SHEET :039
O
WTR INJ PUMP P-
F 131001 MCMS TO IPS
T 13-PALL- 13-PALL-
IPS 10082 10082
SHEET :008 SHEET :039 13-XZ- 13-XZ-
13101A/B 13101A/B

SHEET :040 SHEET :039 SHEET NO :051


INPUT OUTPUT
DCS / FIELD
TRIP SEQUENCES – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

TRIP MAIN PUMP


TRIP CONDITION

13- 13-
PMXZ- PMXZ-
10001 10001
SHEET :051 SHEET :052 AND S Q
HW 13-PMRN-10001A TRP SEQ TRP SEQ
D SR ST-1 ST-1
MAIN PUMP RUNNING =1 R SHEET :052 SHEET: 038
I
DCS RUNNING FB NOT RUNNING =0

TRP SEQ TRP SEQ


END END
SHEET :054 SHEET :052 OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :052

CLOSE DISCHARGE VALVE, RECYCLE VALVE OPEN AND AUTO MODE

TRP SEQ TRP SEQ


ST-1 ST-1
SHEET :052 SHEET: 052 S SK
C 13-UZ-10001
AND O
HW 13-PMRN-10001 DISCHARGE F
D VALVE - SOV T IPS
AUX LO PUMP RUNNING =1 S Q TRP SEQ TRP SEQ
I ST-2 ST-2
DCS RUNNING FB NOT RUNNING =0
SR SHEET: 053
SHEET :052
R 13-FIC-10002 S SK
TRP SEQ TRP SEQ O
END END O
MIINIMUM BY-PASS
LINE ON AND IN F
SHEET :054 SHEET :052 T DCS
AUTO MODE
OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :052 SHEET NO :052
INPUT OUTPUT
DCS / FIELD
TRIP SEQUENCES – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

TRIP - AUX LO PUMP, SEAL SYSTEM,SEAL COOLER ,LO/WO COOLER

TRP SEQ TRP SEQ


ST-2 ST-2
SHEET :052 SHEET: 053 TON
TIMER
T#160S
HW 13-PMRN-10001
D
AND
AUX LO PUMP RUNNING =1 S Q TRP SEQ TRP SEQ
I ST-3 ST-3
DCS RUNNING FB NOT RUNNING =0
SR
SHEET :053 SHEET: 054
SK S 13-ZIC-10001 R SHEET: 038
O SHEET: 034
F CLOSE FB FORM SHEET :030
IPS T DISCHARGE VALVE SHEET :028
SHEET :027
TRP SEQ TRP SEQ SHEET :023
END END
SHEET :054 SHEET :052
OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :052

SHEET NO :053
INPUT OUTPUT
IPS/DCS / FIELD
TRIP SEQUENCES – 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD

S 13-EMRN-10031A
SK
O
F LO/WO COOLER FAN RUNNING =1
IPS
T RUNNING FB NOT RUNNING =0
TRP SEQ TRP SEQ
SK S 13-EMRN-10031B END END
O
F LO/WO COOLER FAN RUNNING =1 SHEET :054 SHEET :052
IPS T RUNNING FB NOT RUNNING =0 SHEET :053
SHEET :036
SK S 13-EMRN-10031C
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0

AND
TRP SEQ TRP SEQ
ST-3 ST-3
HW 13-PMRN-10001 SHEET :053 SHEET: 054
D
AUX LO PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0

SK S 13-ZIC-10001
O
F CLOSE FB FORM
DCS T DISCHARGE VALVE

HW 13-EMRN-10001
D
SEAL SYSTEM
RUNNING =1
I COOLER FAN
DCS RUNNING FB NOT RUNNING =0
13-PMRN-10004
HW D

DCS
SEAL SYSTEM PUMP RUNNING =1
I RUNNING FB NOT RUNNING =0
OR
HW 13-PMRN-10005
D
SEAL SYSTEM PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0 SHEET NO :054

You might also like