Symbol sheet

13-LT-10022 H> S Q
L Alarm Setpoint A AI1 SH: 008
= 26.5% I Diff level
Transmitter SR
<= R

13-LT-10022 H>
A 13-LAL- 13-LAL-
H Alarm Setpoint I Diff level >L 10022 10022
= 88.5% Transmitter

>= SHEET :001 SHEET :008


13-LT-10022
A
I Diff level >L
Transmitter 13-LAL-
13-LAL- 10022
>= 10022
<=
SHEET :001 SHEET :008 13-LAL-10022

13-LAH-
10022

SHEET :001

H Alarm Setpoint
13-LT-10022 = 88.3%
H
A
>=
I PUMP P-131001
SEAL SYSTEM L
TANK LEVEL

L Alarm Setpoint
= 26.5%

<=

Page 1
Symbol sheet

13-LT-10022 H>
A START 13-LT-10022 V
I Diff level
Transmitter Diff level HW
Transmitter W IFB

AND

SHEET NO :001

OR

13-LAH- 13-LAH- 13-LAH-10022


10022 10022

SHEET :001 SHEET :001

13-LAL- 13-LAL- 13-LAL-10022


10022 10022

SHEET :001 SHEET :001

Page 2
13-PT-10085 & 13-PT-10087

A1
INPUT OUTPUT
FIELD
13-PT-10085 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD

HW 13-PT-10085 L Alarm Setpoint


A = 8637 KPag
I PUMP P-131001 ANALOG INPUT <=
DCS SEAL SYSTEM L
PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
20000 KPag & SCALING
13-PAL-10085
13-PAL- 13-PAL-
LOW LIMIT = 10085
0 KPag LL Alarm Setpoint 10085
= 8100 KPag SHEET :003 SHEET :027
<=

13-PALL-10085
13-PALL- 13-PALL-
10085 10085
SHEET :003 SHEET :027

13-PT-10087 - PUMP P-131001 SEAL SYSTEM PRESS (NDE SEAL)

HW 13-PT-10087 L Alarm Setpoint


A = 8637 KPag
I PUMP P-131001 ANALOG INPUT <=
DCS SEAL SYSTEM L SIGNAL PROCESSING
PRESS (NDE SEAL) HIGH LIMIT =
20000 KPag & SCALING
13-PAL-10087
13-PAL- 13-PAL-
LOW LIMIT = 10087
0 KPag LL Alarm Setpoint 10087
= 8100 KPag SHEET :003 SHEET :028
<=

13-PALL-10087
13-PALL- 13-PALL-
10087 10087
SHEET :003 SHEET :028

SHEET NO :003
A1

Page 3
13-PZT-10086 & 13-PZT-10088

A1
INPUT OUTPUT
FIELD
13-PZT-10086 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD

HW 13-PZT-10086 LL Alarm Setpoint


A = 7920 KPag
I PUMP P-131001 ANALOG INPUT <=
IPS SEAL SYSTEM L
PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
20000 KPag & SCALING
13-PALL-10086
13-PALL- 13-PALL-
LOW LIMIT = 10086
0 KPag 10086
SHEET :004 SHEET :023
SHEET :027
SHEET :028

13-PZT-10088 - PUMP P-131001 SEAL SYSTEM PRESS (NDE SEAL)

HW 13-PZT-10088 LL Alarm Setpoint


A = 7920 KPag
I PUMP P-131001 ANALOG INPUT <=
IPS SEAL SYSTEM L SIGNAL PROCESSING
PRESS (NDE SEAL) HIGH LIMIT =
20000 KPag & SCALING
13-PALL-10088
13-PALL- 13-PALL-
LOW LIMIT = 10088
0 KPag 10088
SHEET :004 SHEET :023
SHEET :027
SHEET :028

SHEET NO :004
A1

Page 4
13-TT-10066 & 13-TT-10067

A1
INPUT OUTPUT
FIELD
13-TT-10066 - PUMP P-131001 SEAL SYSTEM TEMP ( DE SEAL) ALARM FIELD

HW 13-TT-10066 H Alarm Setpoint


H
A = 70 DEG C
I PUMP P-131001 ANALOG INPUT >=
SEAL SYSTEM
DCS PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
100 DEG C & SCALING
13-TAH-10066
13-TAH- 13-TAH-
LOW LIMIT = 10066
0 DEG C 10066
SHEET :005 SHEET :023

13-TT-10067 - PUMP P-131001 SEAL SYSTEM TEMP (NDE SEAL)

HW 13-TT-10067 H Alarm Setpoint


H
A = 70 DEG C
I PUMP P-131001 ANALOG INPUT >=
SEAL SYSTEM
DCS PRESS (DE SEAL) HIGH LIMIT = SIGNAL PROCESSING
100 DEG C & SCALING
13-TAH-10067
13-TAH- 13-TAH-
LOW LIMIT = 10067
0 DEG C 10067
SHEET :005 SHEET :023

SHEET NO :005
A1

Page 5
13-TT-10066 & 13-TT-10067

13-TAH- 13-TAH-
10066 10066
SHEET :005 SHEET :023

13-TAH- 13-TAH-
10067 10067
SHEET :005 SHEET :023

Page 6
13-LT-10022

A1
INPUT OUTPUT
FIELD
13-LT-10022 - PUMP P-131001 SEAL SYSTEM TANK LEVEL ALARM FIELD

13-LT-10022 H Alarm Setpoint


HW H = 88.3%
A
I PUMP P-131001 ANALOG INPUT >=
SDE SEAL SYSTEM L
TANK LEVEL HIGH LIMIT = SIGNAL PROCESSING
100 % & SCALING 13-LAH-10022
13-LAH- 13-LAH-
LOW LIMIT = 10022
0% L Alarm Setpoint 10022
= 26.5% SHEET :006 SHEET :001
<=

13-LAL-10022
13-LAL- 13-LAL-
10022 10022
SHEET :006 SHEET :027

SHEET NO :006
A1

Page 7
13-LT-10021 & 13-PT-10081

A1
INPUT OUTPUT
FIELD
13-LT-10021 - VOITH CPLNG GB-131001 OIL RESERVOIR LEVEL ALARM FIELD

HW 13-LT-10021 H Alarm Setpoint


H = 84.2%
A VOITH CPLNG
I GB-131001 OIL ANALOG INPUT >=
DCS L
RESERVOIR LEVEL HIGH LIMIT = SIGNAL PROCESSING
100 % & SCALING 13-LAH-10021
13-LAH- 13-LAH-
LOW LIMIT = 10021
0% L Alarm Setpoint 10021
= 60.5% SHEET :001 SHEET :001
<=

13-LAL-10021
13-LAL- 13-LAL-
10021 10021
SHEET :007 SHEET :030
SHEET :036

13-PT-10081 - VOITH CPLNG GB-131001 LO PRESS AFTER LO FILTER

HW 13-PT-10081 H Alarm Setpoint


H = 170/200 KPag
A VOITH CPLNG
I GB-131001 LO ANALOG INPUT
PRESS AFTER LO L >=
DCS FILTER HIGH LIMIT = SIGNAL PROCESSING
600 KPag & SCALING 13-PAH-10081
13-PAH- 13-PAH-
LOW LIMIT = 10081 10081
0 KPag L Alarm Setpoint
= 150 KPag SHEET :007 SHEET :030
<=

13-PAL-10081
13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :030

SHEET NO :007
A1

Page 8
13-PZT-10082 & 13-PDT-10083

A1
INPUT OUTPUT
FIELD
13-PZT-10082 - VOITH CPLNG GB-131001 LO PRESSURE AFTER LO FILTER ALARM FIELD

HW 13-PZT-10082 LL Alarm Setpoint


A VOITH CPLNG GB- = 80 KPag
I 131001 LO ANALOG INPUT <=
IPS PRESSURE AFTER L
LO FILTER HIGH LIMIT = SIGNAL PROCESSING
150 KPag & SCALING
13-PALL-10082
13-PALL- 13-PALL-
LOW LIMIT = 10082
0 KPag 10082
SHEET :008 SHEET :030

13-PDT-10083 - VOITH CPLNG GB-131001 LO FILTER DIFF. PRESS

HW 13-PDT-10083 H Alarm Setpoint


H
A = 80 KPag
I VOITH CPLNG GB- ANALOG INPUT <=
131001 LO FILTER
DCS DIFF. PRESS HIGH LIMIT = SIGNAL PROCESSING
150 KPag & SCALING
13-PAHH-10083
13-PAHH- 13-PAHH-
LOW LIMIT = 10083
0 KPag 10083
SHEET :001 SHEET :001

SHEET NO :008
A1

Page 9
13-TZT-10061 & 13-TZT-10063

A1
INPUT OUTPUT
FIELD
13-TZT-10061 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD

HH Alarm Setpoint
HW 13-TZT-10061 = 70 DEG C
A
I VOITH CPLNG GB- ANALOG INPUT >=
IPS 131001 LO TEMP L
AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAHH-10061
13-TAHH- 13-TAHH-
LOW LIMIT = 10061 10061
0 DEG C
SHEET :009 SHEET :031

13-TZT-10063 - VOITH CPLNG GB-131001 WO TEMP BEFORE COOLER

HW 13-TZT-10063 H Alarm Setpoint


A = 110 DEG C
I VOITH CPLNG GB- ANALOG INPUT >=
IPS 131001 WO TEMP L SIGNAL PROCESSING
BEFORE COOLER HIGH LIMIT =
150 DEG C & SCALING
13-TAH-10063
13-TAH- 13-TAH-
LOW LIMIT = 10063 10063
0 DEG C
SHEET :001 SHEET :001
HH Alarm Setpoint
= 130 DEG C
>=

13-TAHH-10063
13-TAHH- 13-TAHH-
10063 10063
SHEET :009 SHEET :031

SHEET NO :009
A1

Page 10
13-TT-10060 & 13-TT-10062

A1
INPUT OUTPUT
FIELD
13-TT-10060 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD

HW 13-TT-10060 H Alarm Setpoint


H
A = 65 DEG C
I VOITH CPLNG GB- ANALOG INPUT >=
131001 LO TEMP
DCS AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAH-10060
13-TAH- 13-TAH-
LOW LIMIT = 10060
0 DEG C 10060
SHEET :001 SHEET :001

13-TT-10062 - VOITH CPLNG GB-131001 WO TEMP AFTER COOLER

HW 13-TT-10062 H Alarm Setpoint


H
A = 75 DEG C
I PVOITH CPLNG GB- ANALOG INPUT >=
131001 WO TEMP
DCS AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAH-10062
13-TAH- 13-TAH-
LOW LIMIT = 10062
0 DEG C 10062
SHEET :001 SHEET :001

SHEET NO :010
A1

Page 11
13-TC-10064 & 13-TS-10065

A1
INPUT OUTPUT
FIELD
13-TC-10064 - VOITH CPLNG GB-131001 OIL RESERVOIR TEMP CTR ALARM FIELD

HW 13-TC-10064 H Alarm Setpoint


H
A VOITH CPLNG = 27 DEG C
I GB-131001 OIL ANALOG INPUT >=
DCS RESERVOIR TEMP L SIGNAL PROCESSING
CTR HIGH LIMIT =
100 DEG C & SCALING
13-TAH-10064
13-TAH- 13-TAH-
LOW LIMIT = 10060
0 DEG C 10060
L Alarm Setpoint
= 20 DEG C SHEET :011 SHEET :036

<=

13-TAL-10064
13-TAL- 13-TAL-
10064 10064
SHEET :011 SHEET :036

13-TS-10065 - VOITH CPLNG GB-131001 OIL RESERVOIR TEMP CTR

HW 13-TS-10065 H Alarm Setpoint


H
A VOITH CPLNG GB- = 100 DEG C
I 131001 OIL ANALOG INPUT >=
RESERVOIR TEMP
DCS HIGH LIMIT = SIGNAL PROCESSING
CTR
150 DEG C & SCALING
13-TAH-10065
13-TAH- 13-TAH-
LOW LIMIT = 10065
0 DEG C 10065
SHEET :001 SHEET :001

SHEET NO :011
A1

Page 12
MMS PUMP P-131001_1

A1
INPUT OUTPUT
FIELD
13-TE-10046A/B, 13-TE-10047A/B,13-TE-10048A/B - MOTOR P-131001-ME WIND TEMP (R),(S),(T) ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10046A/B H 180 DEG C = 130 DEG C
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) LOW LIMIT =
0 DEG C H Alarm Setpoint 13-TE-10046A/B
= 130 DEG C
HW 13-TE-10047A/B H
A >=
I MOTOR P-131001-ME 13-TE-10047A/B
MMS WIND TEMP (S) H Alarm Setpoint
= 130 DEG C
HW 13-TE-10048A/B H >=
A
I MOTOR P-131001-ME 13-TE-100468A/B
MMS WIND TEMP (T)

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10046A/B 180 DEG C = 140 DEG C
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) HH LOW LIMIT =
0 DEG C HH Alarm Setpoint 13-TE-10046A/B
= 140 DEG C
HW 13-TE-10047A/B
A >=
I MOTOR P-131001-ME 13-TE-10047A/B
MMS WIND TEMP (S) HH HH Alarm Setpoint
= 140 DEG C
HW 13-TE-10048A/B >=
A
I MOTOR P-131001-ME 13-TE-100468A/B
MMS WIND TEMP (T) HH

13-TAHH- 13-TAHH-
AND 10046 10046
SHEET :001 SHEET :001

SHEET NO :011
A1

Page 13
MMS PUMP P-131001_2

A1
INPUT OUTPUT
FIELD
13-TE-10043, 13-TE-10044,13-TE-10045 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10043 H 150 DEG C = 100 DEG C
A >=
I MOTOR P-131001-ME
MMS AIR TEMP LOW LIMIT =
0 DEG C H Alarm Setpoint 13-TE-10043
= 95 DEG C
HW 13-TE-10044 H
A >=
I MOTOR P-131001-ME 13-TE-10044
MMS BRG TEMP NDE H Alarm Setpoint
= 95 DEG C
HW 13-TE-10045 H >=
A
I MOTOR P-131001-ME 13-TE-10045
MMS BRG TEMP DE

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10043 150 DEG C = 110 DEG C
A >=
I MOTOR P-131001-ME
MMS WIND TEMP (R) HH LOW LIMIT =
0 DEG C HH Alarm Setpoint 13-TE-10043
= 100 DEG C
HW 13-TE-10044
A >=
I MOTOR P-131001-ME 13-TE-10044
MMS WIND TEMP (S) HH HH Alarm Setpoint
= 100 DEG C
HW 13-TE-10045 >=
A
I MOTOR P-131001-ME 13-TE-10045
MMS WIND TEMP (T) HH

13-TAHH- 13-TAHH-
AND 10043 10043
SHEET :001 SHEET :001

SHEET NO :011
A1

Page 14
MMS PUMP P-131001_3_H

A1
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10037 H 150 DEG C = 75 DEG C
A >=
I PUMP P-131001
CASING SURFACE
MMS LOW LIMIT =
TEMP
0 DEG C H Alarm Setpoint 13-TE-10037
= 93 DEG C
HW 13-TE-10038 H
A >=
PUMP P-131001
I SLEEVE BRG TEMP 13-TE-10038
MMS DE H Alarm Setpoint
= 93 DEG C
HW 13-TE-10039 H >=
A
I PUMP P-131001 13-TE-10039
SLEEVE BRG TEMP
MMS NDE

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10040 H 150 DEG C = 93 DEG C
A >=
I PUMP P-131001 TILT-
PAD BRG (ACTIVE) LOW LIMIT =
MMS TEMP NDE
0 DEG C H Alarm Setpoint 13-TE-10040
= 93 DEG C
HW 13-TE-10041 H
A >=
I PUMP P-131001 TILT- 13-TE-10041
PAD BRG (ACTIVE)
MMS TEMP NDE H Alarm Setpoint
= 93 DEG C
HW 13-TE-10042 H >=
A
PUMP P-131001 TILT-
I PAD BRG (NON- 13-TE-10042
MMS ACTIVE) TEMP NDE

SHEET NO :012
A1

Page 15
MMS PUMP P-131001_3_HH

A1
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10037 HH 150 DEG C = 80 DEG C
A >=
I PUMP P-131001
CASING SURFACE
MMS LOW LIMIT =
TEMP
0 DEG C HH Alarm Setpoint 13-TE-10037
= 104 DEG C
HW 13-TE-10038 HH
A >=
PUMP P-131001
I SLEEVE BRG TEMP 13-TE-10038
MMS DE HH Alarm Setpoint
= 104 DEG C
HW 13-TE-10039 HH >=
A
I PUMP P-131001 13-TE-10039
SLEEVE BRG TEMP
MMS NDE

13-TAHH- 13-TAHH-
AND 10037 10037
SHEET :001 SHEET :001

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10040 HH 150 DEG C = 104 DEG C
A >=
I PUMP P-131001 TILT-
PAD BRG (ACTIVE) LOW LIMIT =
MMS TEMP NDE
0 DEG C HH Alarm Setpoint 13-TE-10040
= 104 DEG C
HW 13-TE-10041 HH
A >=
I PUMP P-131001 TILT- 13-TE-10041
PAD BRG (ACTIVE)
MMS TEMP NDE HH Alarm Setpoint
= 104 DEG C
HW 13-TE-10042 HH >=
A
PUMP P-131001 TILT-
I PAD BRG (NON- 13-TE-10042
MMS ACTIVE) TEMP NDE

SHEET NO :013

Page 16
MMS PUMP P-131001_VIB_1

A1
INPUT OUTPUT
FIELD
13-VZT-10007, 13-VZT-10008,13-VZT-10009, 13-VZT-10010 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10007 H 10 MILS = 3.5 MILS
A >=
I MOTOR P-131001-ME
BRG RADIAL VIBR
MMS LOW LIMIT =
NDE - X
0 MILS H Alarm Setpoint 13-VZT-10007
= 3.5 MILS
HW 13-VZT-10008 H
A >=
MOTOR P-131001-ME
I BRG RADIAL VIBR 13-VZT-10008
MMS NDE - Y H Alarm Setpoint
= 3.5 MILS
HW 13-VZT-10009 H >=
A
I MOTOR P-131001-ME 13-VZT-10009
BRG RADIAL VIBR H Alarm Setpoint
MMS DE - X = 3.5 MILS
HW 13-VZT-10010 H >=
A
MOTOR P-131001-ME 13-VZT-10010
I
BRG RADIAL VIBR
MMS DE - Y

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10007 10 MILS = 4 MILS
A >=
I MOTOR P-131001-ME
BRG RADIAL VIBR HH LOW LIMIT =
MMS NDE - X
0 MILS HH Alarm Setpoint 13-VZT-10007
= 4 MILS
HW 13-VZT-10008
A >=
MOTOR P-131001-ME
I 13-VZT-10008
BRG RADIAL VIBR HH
MMS NDE - Y HH Alarm Setpoint
= 4 MILS
HW 13-VZT-10009 >=
A
I MOTOR P-131001-ME
BRG RADIAL VIBR
13-VZT-10009
MMS HH H Alarm Setpoint
DE - X
= 4 MILS
HW 13-VZT-10010 H >=
A
MOTOR P-131001-ME
I 13-VZT-10010
BRG RADIAL VIBR HH
MMS DE - Y 13-VAHH-
13-VAHH-
10007 10007
AND
SHEET :001 SHEET :001
SHEET NO :014
A1

Page 17
MMS PUMP P-131001_VIB_2

A1
INPUT OUTPUT
FIELD
13-VZT-10001, 13-VZT-10002,13-VZT-10003, 13-VZT-10004 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10001 H 10 MILS = 5 MILS
A >=
I PUMP P-131001
RADIAL BRG VIBR
MMS LOW LIMIT =
DE - X
0 MILS H Alarm Setpoint 13-VZT-10001
= 5 MILS
HW 13-VZT-10002 H
A >=
PUMP P-131001
I RADIAL BRG VIBR 13-VZT-10002
MMS DE - Y H Alarm Setpoint
= 5 MILS
HW 13-VZT-10003 H >=
A
I PUMP P-131001 13-VZT-10003
RADIAL BRG VIBR H Alarm Setpoint
MMS NDE - X = 5 MILS
HW 13-VZT-10004 H >=
A
PUMP P-131001 13-VZT-10004
I
RADIAL BRG VIBR
MMS NDE - Y

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10001 10 MILS = 7.5 MILS
A >=
I PUMP P-131001
RADIAL BRG VIBR HH LOW LIMIT =
MMS DE - X
0 MILS HH Alarm Setpoint 13-VZT-10001
= 7.5 MILS
HW 13-VZT-10002
A >=
PUMP P-131001
I 13-VZT-10002
RADIAL BRG VIBR HH
MMS DE - Y HH Alarm Setpoint
= 7.5 MILS
HW 13-VZT-10003 >=
A
I PUMP P-131001
RADIAL BRG VIBR
13-VZT-10003
MMS HH H Alarm Setpoint
NDE - X
= 7.5 MILS
HW 13-VZT-10004 >=
A
I PUMP P-131001 13-VZT-10004
RADIAL BRG VIBR HH
MMS NDE - Y 13-VAHH-
13-VAHH-
10001 10001
AND
SHEET :001 SHEET :001
SHEET NO :015
A1

Page 18
MMS PUMP P-131001_VIB_3

A1
INPUT OUTPUT
FIELD
13-VZT-10005, 13-VZT-100064 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-VZT-10005 H 30 MILS = ±15.5 MILS
A >=
I PUMP P-131001
SHAFT NDE ACTIAL
MMS LOW LIMIT =
SHIFT - Z
-30 MILS H Alarm Setpoint 13-VZT-10005
= ±15.5 MILS
HW 13-VZT-10006 H
A >=
I PUMP P-131001 13-VZT-10006
SHAFT NDE ACTIAL
MMS SHIFT - Z

HIGH LIMIT = HH Alarm Setpoint


HW 13-VZT-10005 30 MILS = ±20.5 MILS
A >=
I PUMP P-131001
SHAFT NDE ACTIAL HH
MMS LOW LIMIT =
SHIFT - Z 13-VZT-10005
-30 MILS HH Alarm Setpoint
= ±20.5 MILS
HW 13-VZT-10006
A >=
I PUMP P-131001 13-VZT-10006
SHAFT NDE ACTIAL HH
MMS SHIFT - Z

13-VAHH- 13-VAHH-
10005 10005
AND
SHEET :001 SHEET :001

SHEET NO :016
A1

Page 19
MMS VOITH GB-131001_TEM_1

A1
INPUT OUTPUT
FIELD
13-TE-10052, 13-TE-10053,13-TE-10054, 13-TE-10055 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10052 H 150 DEG C = 100 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG
MMS LOW LIMIT =
TEMP
0 DEG C H Alarm Setpoint 13-TE-10052
= 100 DEG C
HW 13-TE-10053 H
A >=
VOITH CPLNG GB-
I 131001 THRUST BRG 13-TE-10053
MMS TEMP H Alarm Setpoint
= 100 DEG C
HW 13-TE-100054 H >=
A
I VOITH CPLNG GB- 13-TE-10054
131001 THRUST BRG H Alarm Setpoint
MMS TEMP = 100 DEG C
HW 13-TE-100055 H >=
A
VOITH CPLNG GB- 13-TE-10055
I
131001 RADIAL BRG
MMS TEMP

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10052 150 DEG C = 105 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG HH LOW LIMIT =
MMS TEMP
0 DEG C HH Alarm Setpoint 13-TE-10052
= 105 DEG C
HW 13-TE-10053
A >=
VOITH CPLNG GB-
I 13-T-100053
131001 THRUST BRG HH
MMS TEMP HH Alarm Setpoint
= 105 DEG C
HW 13-TE-10054 >=
A
I VOITH CPLNG GB-
131001 THRUST BRG HH
13-TE-10054
MMS H Alarm Setpoint
TEMP
= 105 DEG C
HW 13-VZT-10055 >=
A
I VOITH CPLNG GB- 13-TE-10055
131001 RADIAL BRG HH
MMS TEMP 13-TAHH-
13-TAHH-
10052 10052
AND
SHEET :001 SHEET :001
SHEET NO :017
A1

Page 20
MMS VOITH GB-131001_TEM_2

A1
INPUT OUTPUT
FIELD
13-TE-10056, 13-TE-10057,13-TE-10058, 13-TE-10059 ALARM FIELD

HIGH LIMIT = H Alarm Setpoint


HW 13-TE-10056 H 150 DEG C = 100 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG
MMS LOW LIMIT =
TEMP
0 DEG C H Alarm Setpoint 13-TE-10056
= 100 DEG C
HW 13-TE-10057 H
A >=
VOITH CPLNG GB-
I 131001 THRUST BRG 13-TE-10057
MMS TEMP H Alarm Setpoint
= 100 DEG C
HW 13-TE-100058 H >=
A
I VOITH CPLNG GB- 13-TE-100548
131001 THRUST BRG H Alarm Setpoint
MMS TEMP = 100 DEG C
HW 13-TE-100059 H >=
A
VOITH CPLNG GB- 13-TE-10059
I
131001 RADIAL BRG
MMS TEMP

HIGH LIMIT = HH Alarm Setpoint


HW 13-TE-10056 150 DEG C = 105 DEG C
A >=
I VOITH CPLNG GB-
131001 RADIAL BRG HH LOW LIMIT =
MMS TEMP
0 DEG C HH Alarm Setpoint 13-TE-10056
= 105 DEG C
HW 13-TE-10057
A >=
VOITH CPLNG GB-
I 13-T-100057
131001 THRUST BRG HH
MMS TEMP HH Alarm Setpoint
= 105 DEG C
HW 13-TE-10058 >=
A
I VOITH CPLNG GB-
131001 THRUST BRG HH
13-TE-10058
MMS H Alarm Setpoint
TEMP
= 105 DEG C
HW 13-VZT-10059 >=
A
I VOITH CPLNG GB- 13-TE-10059
131001 RADIAL BRG HH
MMS TEMP 13-TAHH-
13-TAHH-
10056 10056
AND
SHEET :001 SHEET :001
SHEET NO :018
A1

Page 21
MMS VOITH GB-131001_VIB_1

A1
INPUT OUTPUT
FIELD
13-VZT-10011, 13-VZT-10012,13-VZT-10013 ALARM FIELD

H Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 H = 220 MIL/S
10 MILS
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR
0 MILS H Alarm Setpoint 13-VZT-10011
HIGH LIMIT = = ±22.2 MILS
HW 13-VZT-10012 H 40 MILS >=
A
I VOITH CPLNG GB-
131001 AXL 1ST LOW LIMIT = 13-VZT-10012
MMS H Alarm Setpoint
SHAFT VIBR - Z -40 MILS
= ±22.2 MILS
13-VZT-10013 HIGH LIMIT = >=
HW H 40 MILS
A
I VOITH CPLNG GB-
131001 AXL 2ND LOW LIMIT = 13-VZT-10013
MMS SHAFT VIBR - Z -40 MILS

HH Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 = 315 MIL/S
10 MIL/S
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR HH
0 MIL/S HH Alarm Setpoint 13-VZT-10011
HIGH LIMIT = = ±27.2 MILS
HW 13-VZT-10012
40 MILS >=
A
VOITH CPLNG GB-
I LOW LIMIT = 13-VZT-10012
131001 AXL 1ST HH
MMS SHAFT VIBR - Z -40 MILS HH Alarm Setpoint
= ±27.2 MILS
HW 13-VZT-10013 HIGH LIMIT = >=
40 MILS
A
I VOITH CPLNG GB-
131001 AXL 2ND LOW LIMIT =
13-VZT-10013
MMS HH
SHAFT VIBR - Z -40 MILS

13-VAHH- 13-VAHH-
10011 10011
AND
SHEET :001 SHEET :001
SHEET NO :019
A1

Page 22
MMS LO_WO_E-131002_3_VIB_1

A1
INPUT OUTPUT
FIELD
13-VZT-10014, 13-VZT-10012,15-VZT-10016 ALARM FIELD

H Alarm Setpoint
13-VZT-10014 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VZT-10014
= 16 MM/S
HW 13-VZT-10015 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VZT-10015
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10016 H >=
A
I LO/WO COOLER E-
131002/E-131003 13-VZT-10016
MMS FAN (K-131002) VIBR

HH Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10014 = 17.8 MM/S
63.5 MM/S
A >=
I LO/WO COOLER E- LOW LIMIT =
131002/E-131003 HH
MMS FAN (K-131001) VIBR 0 MM/S HH Alarm Setpoint 13-VZT-10014
= 17.8 MM/S
HW 13-VZT-10015
A LO/WO COOLER E- >=
I 131002/E-131003
MMS
FAN MOTOR (K- HH 13-VZT-10015
131001-ME) VIBR HH Alarm Setpoint
= 17.8 MM/S
HW 13-VZT-10016 >=
A
I LO/WO COOLER E-
131002/E-131003
13-VZT-10016
MMS HH
FAN (K-131002) VIBR

VIB-HH VIB-HH
LO/WO- LO/WO-
COOLER COOLER
AND
SHEET :020 SHEET :034
SHEET NO :020
A1

Page 23
MMS LO_WO_E-131002_3_VIB_2

A1
INPUT OUTPUT
FIELD
13-VZT-10017, 13-VZT-10018,15-VZT-10019 ALARM FIELD

H Alarm Setpoint
13-VZT-10017 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VZT-10017
= 16 MM/S
HW 13-VZT-10018 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VZT-10018
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10019 H >=
A
I LO/WO COOLER E-
131002/E-131003 13-VZT-10019
MMS FAN (K-131002) VIBR

HH Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10017 = 17.8 MM/S
63.5 MM/S
A >=
I LO/WO COOLER E- LOW LIMIT =
131002/E-131003 HH
MMS FAN (K-131001) VIBR 0 MM/S HH Alarm Setpoint 13-VZT-10017
= 17.8 MM/S
HW 13-VZT-10018
A LO/WO COOLER E- >=
I 131002/E-131003
MMS
FAN MOTOR (K- HH 13-VZT-10018
131001-ME) VIBR HH Alarm Setpoint
= 17.8 MM/S
HW 13-VZT-10019 >=
A
I LO/WO COOLER E-
131002/E-131003
13-VZT-10019
MMS HH
FAN (K-131002) VIBR

VIB-HH VIB-HH
LO/WO- LO/WO-
COOLER COOLER
AND
SHEET :021 SHEET :034
SHEET NO :021

Page 24
SEAL SYSTEM FAN_COOLER_13-KS-10021

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 ALARM FIELD

HW 13-EMRN-10001
D
RUNNING =1
SDE I FAN RUNNING FB
NOT RUNNING =0

AND
HW 13-EMAV-10001
D
OR
I FAN AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST V
AND S Q
PUMP START HW
W IFB
SR
R
SK S SEAL SYSTEM FAN STOP 13-PMSP- V
A
O COOLER PUMP STOP HW
F AUTO /MANUAL AUTO=1
W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM FAN


O COOLER PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
LOCK LOCK SHEET NO :022
SHEET :023 SHEET :022
SHEET :023 SHEET :022

Page 25
SEAL SYSTEM FAN_COOLER_13-KS-10021_INTERLOCK

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

13-TAH- 13-TAH-
10066 10066
SHEET :005 SHEET :023
OR AUTO AUTO
START START
SHEET :023 SHEET :022
13-TAH- 13-TAH-
10067 10067
SHEET :005 SHEET :023

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :023 AND

13-PALL- 13-PALL-
10088 10088
INTER INTER
SHEET :004 SHEET :023
LOCK LOCK
SHEET :023 SHEET :022

SHEET NO :023

Page 26
SEAL_SYSTEM_PM_13-KS-10022_023_1

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022,10023 – MAIN/STANDBY SELECTION ALARM FIELD

AND MAIN MAIN


PUMP PUMP
SK S SEAL SYSTEM B A SHEET :024 SHEET :025
A
O PUMP
F AUTO /MANUAL AUTO=1
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S MAIN PUMP
O
F MAIN SELECTION
M
ST STBY STBY
DCS T FROM GRAPHICS
AND PUMP PUMP
A
SK S STANDY PUMP B SHEET :024 SHEET :026
O
F STANDY SELECTION
S
ST
DCS T FROM GRAPHICS

SHEET NO :024

Page 27
SEAL_SYSTEM_PM_13-KS-10022_1

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022 - MAIN PUMP ALARM FIELD
MAIN MAIN
PUMP PUMP
HW 13-PMRN-10022
D SHEET :024 SHEET :025
RUNNING =1
SDE I PUMP RUNNING FB
NOT RUNNING =0

AND
HW 13-PMAV-10022
D
OR
I PUMP AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST-10022 V
AND S Q
P-131004 MAIN HW
PUMP START W IFB
SR
AUTO AUTO
START R
START
SK S SEAL SYSTEM STOP 13-PMSP-10022 V
A SHEET :027 SHEET :025
O PUMP P-131004 MAIN HW
F AUTO /MANUAL AUTO=1 PUMP STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM
O PUMP PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S SEAL SYSTEM
O PUMP
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S SEAL SYSTEM
O PUMP AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S SEAL SYSTEM
O PUMP
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
SHEET :023 SHEET :022 LOCK LOCK SHEET NO :025
SHEET :027 SHEET :025

Page 28
SEAL_SYSTEM_PM_13-KS-10023_1

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10023 – STANDBY PUMP ALARM FIELD
STBY STBY
PUMP PUMP
HW 13-PMRN-10023
D SHEET :024 SHEET :026
RUNNING =1
SDE I PUMP RUNNING FB
NOT RUNNING =0

AND
HW 13-PMAV-10023
D
OR
I PUMP AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST-10023 V
AND S Q
P-131005 STBY HW
PUMP START W IFB
SR
AUTO AUTO
START R
START
SK S SEAL SYSTEM STOP 13-PMSP-10023 V
A SHEET :027 SHEET :026
O PUMP P-131005 STBY HW
F AUTO /MANUAL AUTO=1 PUMP STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM
O PUMP OR PULSE
F AUTO START FROM TIMER
DCS ST AND T#1S
T GRAPHICS

SK S SEAL SYSTEM
O PUMP
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S SEAL SYSTEM
O PUMP AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S SEAL SYSTEM
O PUMP
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START
INTER INTER
SHEET :023 SHEET :022 LOCK LOCK SHEET NO :026
SHEET :005 SHEET :022

Page 29
SEAL SYSTEM_13-KS-10021_INTERLOCK

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

13-LAL- AUTO AUTO


13-LAL-
10022 START START
10022 AND
SHEET :006 SHEET :027 SHEET :027 SHEET :025

13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :027

13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :027
ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :027

SETPOINT NOT
AVAILABLE
13-PAH- 13-PAH-
10085 10085
SHEET :003 SHEET :027 OR
INTER INTER
OR LOCK LOCK
13-PAH- 13-PAH-
10087 10087 SHEET :027 SHEET :025
SHEET :003 SHEET :027

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :027

HW 13-HZS-10003 AND
D PUMP-P-131001
EMERGENCY TRIP 13-PALL- 13-PALL-
I PB ACTIVATED 10088 10088
SDE FROM FILED
SHEET :004 SHEET :027
HW 13-HZS-10016
D PUMP-P-131001
EMERGENCY TRIP
PB ACTIVATED
SDE I FROM SROS SHEET NO :027
CONSOLE

Page 30
SEAL SYSTEM_13-KS-10023_INTERLOCK

INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

13-LAL- AUTO AUTO


13-LAL-
10022 START START
10022 AND
SHEET :006 SHEET :028 SHEET :028 SHEET :026

13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :028

13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :028

ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :028

SETPOINT NOT
AVAILABLE
13-PAH- 13-PAH-
10085 10085
SHEET :003 SHEET :028 INTER INTER
OR OR LOCK LOCK
SHEET :028 SHEET :026
13-PAH- 13-PAH-
10087 10087
SHEET :003 SHEET :028
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :028

HW 13-HZS-10003 AND
D PUMP-P-131001
EMERGENCY TRIP 13-PALL- 13-PALL-
I PB ACTIVATED 10088 10088
SDE
FROM FILED
SHEET :004 SHEET :028
HW 13-HZS-10016
D PUMP-P-131001
EMERGENCY TRIP
PB ACTIVATED
SDE I FROM SROS
SHEET NO :028
CONSOLE

Page 31
AUX LO PUMP_13-KS-10001

INPUT OUTPUT
DCS/FIELD
AUX LO PUMP 13-KS-10001 ALARM FIELD

HW 13-PMRN-10001
D
RUNNING =1
SDE I PUMP RUNNING FB
NOT RUNNING =0

AND
HW 13-PMAV-10001
D
OR
I PUMP AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST V
AND S Q
PUMP START HW
W IFB
SR
R
SK S AUX LO PUMP STOP 13-PMSP- V
A
O PUMP STOP HW
F AUTO /MANUAL AUTO=1
W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0 `1890-
]o
SK S AUX LO PUMP
O PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S AUX LO PUMP
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S AUX LO PUMP
O AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S AUX LO PUMP
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
SHEET :022 LOCK LOCK SHEET NO :029
SHEET :023
SHEET :023 SHEET :022

Page 32
AUX LO PUMP_13-KS-10001_INTERLOCK

INPUT OUTPUT
DCS/FIELD
AUX LO PUMP 13-KS-10001 – INTERLOCK ALARM FIELD

13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :030
AND AUTO AUTO
START START
13-LAL- 13-LAL-
10021 10021 SHEET :030 SHEET :029

SHEET :007 SHEET :030

13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :030

13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :023

13-PALL- 13-PALL-
10088 10088 INTER INTER
SHEET :004 SHEET :023 LOCK LOCK
OR SHEET :030 SHEET :029
13-PAH- 13-PAH-
10081 10081
SHEET :007 SHEET :030
13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :030
ESD

SHEET NO :030

Page 33
LO_WO_COOLER_13-KS-10031A

INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031A ALARM FIELD

HW 13-EMRN-10031A
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-10031A
D
OR
LO/WO COOLER FAN AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W IFB
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S LO/WO COOLER
O FAN PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S LO/WO COOLER
O FAN
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S LO/WO COOLER
O FAN AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S LO/WO COOLER
O FAN
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :034 SHEET :031 SHEET NO :031
SHEET :034 SHEET :031

Page 34
LO_WO_COOLER_13-KS-10031B

INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031A ALARM FIELD

HW 13-EMRN-10031B
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031B V
AND S Q
LO/WO COOLER HW
FAN START W IFB
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031B V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S LO/WO COOLER
O FAN PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S LO/WO COOLER
O FAN
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S LO/WO COOLER
O FAN AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S LO/WO COOLER
O FAN
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :034 SHEET :032 SHEET NO :032
SHEET :034 SHEET :032

Page 35
LO_WO_COOLER_13-KS-10031C

INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031A ALARM FIELD

HW 13-EMRN-10031C
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W IFB
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S LO/WO COOLER
O FAN PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S LO/WO COOLER
O FAN
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S LO/WO COOLER
O FAN AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S LO/WO COOLER
O FAN
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :034 SHEET :033 SHEET NO :033
SHEET :034 SHEET :033

Page 36
LO_WO_COOLER FAN_13-KS-10031ABC_INTERLOCK

INPUT OUTPUT
DCS/FIELD
LO/WO FAN COOLER 13-KS-10013A/B/C – INTERLOCK ALARM FIELD

13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :034
AUTO AUTO
START START
13-LAL- 13-LAL-
10021 10021 AND SHEET :030 SHEET :031
SHEET :032
SHEET :007 SHEET :034 SHEET: 033

13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :034

ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :034

VIB-HH VIB-HH
LO/WO- LO/WO-
COOLER COOLER
SHEET :020 SHEET :034
VIB-HH VIB-HH AND
LO/WO- LO/WO-
COOLER COOLER INTER INTER
LOCK LOCK
SHEET :021 SHEET :034
SHEET :034 SHEET :031
SHEET :032
SHEET: 033

SHEET NO :034

Page 37
LO_HEATER_E-131004

INPUT OUTPUT
DCS/FIELD
LO HEATER - E-131004 ALARM FIELD

HW 13-EMRN-131004
D
LO HEATER RUNNING =1
SDE I RUNNING FB NOT RUNNING =0

AND
HW 13-EMAV-131004
D
OR
LO HEATER AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-131004 V
AND S Q
LO HEATER HW
START W IFB
SR
R
SK S LO HEATER STOP 13-EMSP-131004 V
A
O LO HEATER HW
F AUTO /MANUAL AUTO=1 STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S LO HEATER
O PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S LO HEATER
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S LO HEATER
O AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S LO HEATER
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :036 SHEET :035 SHEET NO :035
SHEET :036 SHEET :035

Page 38
LO HEATER_E-131004_ INTERRLOCK

INPUT OUTPUT
DCS/FIELD
LO HEATER E-131004 – INTERLOCK ALARM FIELD

13-TAL- 13-TAL- AUTO AUTO


10064 10064 START START
SHEET :011 SHEET :036 SHEET :036 SHEET :035

13-TAH- 13-TAH- INTER INTER


10060 10060 OR LOCK LOCK
SHEET :011 SHEET :036 SHEET :036 SHEET :035

13-LAL- 13-LAL-
10021 10021
SHEET :007 SHEET :030
SHEET :036

SHEET NO :036

Page 39
MANI PUMP -P-131001

INPUT OUTPUT
DCS/FIELD
MANI PUMP -P-131001 ALARM FIELD

HW 13-PMRN-131001
D
MAIN PUMP RUNNING =1
SDE I RUNNING FB NOT RUNNING =0

AND
HW 13-PMAV-131001
D
OR
MAIN PUMP AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-PMST-131001 V
AND S Q MAIN PUMP HW
START W IFB
SR
R
SK S MAIN PUMP STOP 13-PMSP-131001 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W IFB
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S MAIN PUMP
O PULSE
F AUTO START FROM OR TIMER
DCS ST AND T#1S
T GRAPHICS

SK S MAIN PUMP
O
F MANUAL START
ST
ST
DCS T FROM GRAPHICS

SK S MAIN PUMP
O AND
F AUTO STOP FROM
SP
DCS T GRAPHICS

SK S MAIN PUMP
O
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO INTER INTER


START START LOCK LOCK
SHEET :036 SHEET :035 SHEET NO :037
SHEET :036 SHEET :035

Page 40
MAIN PUMP_P-131001_ INTERRLOCK

INPUT OUTPUT
DCS/FIELD
LO HEATER E-131004 – INTERLOCK ALARM FIELD

AUTO AUTO
START START
SHEET :038 SHEET :035

INTER INTER
OR LOCK LOCK
SHEET :036 SHEET :035

13- 13-
PMXZ- PMXZ-
10001 10001
SHEET :039 SHEET :038

SHEET NO :038

Page 41
MAIN PUMP_P-131001_ INTERRLOCK

13-TAH- 13-TAH-
10060 10060
SHEET :011 SHEET :036

13-LAL- 13-LAL-
10021 10021
SHEET :007 SHEET :030
SHEET :036

Page 42
WIP_PERMISSIVE

INPUT OUTPUT
DCS / FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

HW 13-FZT-10001
D
PUMP-P-131001
I DISCHARGE FLOW
SDE LOW LOW

HW 13-PZT - 10014
D
PUMP-P-131001
I SUCTION PRESSURE
SDE LOW LOW

HW 13-PZT-10010A/B
D
PUMP-P-131001
I DISCHARGE
SDE PRESSURE HI HI

HW 13-HZS-10003
D PUMP-P-131001
EMERGENCY TRIP PUMP PERMISSIVE
SDE I PB ACTIVATED
FROM FILED
HW 13-HZS-10016
D PUMP-P-131001 13- 13-
EMERGENCY TRIP PMXZ- PMXZ-
PB ACTIVATED 10001 10001
SDE I FROM SROS AND
CONSOLE SHEET :039 SHEET :038
13-PALL- 13-PALL-
10086 10086

SHEET :004 SHEET :039 13-PALL- 13-PALL-


10088 10088

SHEET :004 SHEET :039

13-TAHH- 13-TAHH-
10061 10061

SHEET :009 SHEET :039


13-TAHH- 13-TAHH-
10063 10063

STARUP OVERRIDE SHEET :009 SHEET :039


REQUIRED 13-PALL- 13-PALL-
10082 10082
HW 13-ZI-10007 SHEET :008 SHEET :039 13-XZ- 13-XZ-
D 13101A/B 13101A/B
DISCHARGE VALVE
SDE I CLOSE STATUS SHEET :040 SHEET :039 SHEET NO :039

Page 43
WIP_PERMISSIVE

13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :030
AND AUTO AUTO
START START
13-LAL- 13-LAL-
10021 SHEET :023 SHEET :022
10021
SHEET :007 SHEET :030

INTER INTER
LOCK LOCK
13-TAHH- 13-TAHH-
10061 10061 SHEET :023 SHEET :022
IPS INPUT
SHEET :009 SHEET :031

13-TAHH- 13-TAHH-
10063 10063

SHEET :009 SHEET :031

MMS ITEMP
INPUT

Page 44
MMS_TRIP

INPUT OUTPUT
DCS / FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD

PUMP PERMISSIVE

13- 13-
PMXZ- PMXZ-
AND 10001 10001
SHEET :039 SHEET :038
13-PALL- 13-PALL-
10086 10086

SHEET :004 SHEET :039 13-PALL- 13-PALL-


10088 10088

SHEET :004 SHEET :039

13-TAHH- 13-TAHH-
10061 10061

SHEET :009 SHEET :039


13-TAHH- 13-TAHH-
10063 10063

SHEET :009 SHEET :039


13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :039 13-XZ- 13-XZ-
13101A/B 13101A/B

SHEET :040 SHEET :039 SHEET NO :040

Page 45
START_SEQUENCE

INPUT OUTPUT
DCS / FIELD
START SEQUENCE ALARM FIELD

START SEQUENCE FROM GRAPHICS`

SK S
O START
F START SEQ FROM SEQ
ST
ST
DCS T GRAPHICS
START SEQ
SK S
O ABORT
F ABORT SEQ FROM SEQ
SP
DCS T GRAPHICS ABORT SEQ

SK S
O RESET
F RESET SEQ FROM SEQ
DCS T GRAPHICS ST
RESET SEQ

SEQUENCE START`

START
SEQ

AND
13- 13-
PMXZ- PMXZ-
10001 10001 S Q
SHEET :039 SHEET :041 ST_SEQ
SR ON
R
ST_SEQ
END

OR
ABORT ABORT
SEQ SEQ
SHEET :023 SHEET :022

SHEET NO :041

Page 46
START_SEQUENCE

HW 13-EMRN-10001
D
RUNNING =1
I FAN RUNNING FB
SDE NOT RUNNING =0

AND
HW 13-EMAV-10001
D
` OR
I FAN AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST V
AND S Q
PUMP START
W
SR
R
SK S SEAL SYSTEM FAN STOP 13-PMSP- V
A
O COOLER PUMP STOP
F AUTO /MANUAL AUTO=1
W
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM FAN


O COOLER PULSE START START
F AUTO START FROM OR TIMER SEQ SEQ
DCS ST AND T#1S
T GRAPHICS
SHEET :041 SHEET :022
SK S SEAL SYSTEM FAN
O COOLER ABORT ABORT
F MANUAL START SEQ SEQ
ST
ST
DCS T FROM GRAPHICS SHEET :022
SHEET :023

SK S SEAL SYSTEM FAN RESET RESET


O COOLER AND SEQ SEQ
F AUTO STOP FROM
SP SHEET :023 SHEET :022
DCS T GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
LOCK LOCK SHEET NO :022
SHEET :023 SHEET :022
SHEET :023 SHEET :022

Page 47
START_SEQUENCE

V
HW
W IFB

V
HW
W IFB

SHEET NO :022

Page 48
START_SEQUENCE_2

INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD

STEP 1 – VENT VALVE (OPEN/CLOSE) 13-KSV-10002

ST_SEQ
ON S Q ST_SEQ
SR ST-1

R O 13-KSY-10002 V
HW
ST_SEQ VENT VALVE - IFB
ST-01A C SOV W

OR

ABORT
SEQ
SHEET :041

ST_SEQ
13-ZIO-10002 ST-1 AND
HW TON ST_SEQ
D
TIMER ST-01A
OPEN FB FORM T#60S
I
SDE VENT VALVE

ST_SEQ
ST-01A S Q ST_SEQ
SR ST-01B
R SHEET :042
ST_SEQ
ST-01A

OR

ABORT
SEQ
SHEET :041

SHEET NO :042

Page 49
START_SEQUENCE_2

HW 13-EMRN-10001
D
RUNNING =1
I FAN RUNNING FB
SDE NOT RUNNING =0

AND
HW 13-EMAV-10001
D
` OR
I FAN AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST V
AND S Q
PUMP START
W
SR
R
SK S SEAL SYSTEM FAN STOP 13-PMSP- V
A
O COOLER PUMP STOP
F AUTO /MANUAL AUTO=1
W
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM FAN


O COOLER PULSE START START
F AUTO START FROM OR TIMER SEQ SEQ
DCS ST AND T#1S
T GRAPHICS
SHEET :041 SHEET :022
SK S SEAL SYSTEM FAN
O COOLER ABORT ABORT
F MANUAL START SEQ SEQ
ST
ST
DCS T FROM GRAPHICS SHEET :022
SHEET :023

SK S SEAL SYSTEM FAN RESET RESET


O COOLER AND SEQ SEQ
F AUTO STOP FROM
SP SHEET :023 SHEET :022
DCS T GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
LOCK LOCK SHEET NO :022
SHEET :023 SHEET :022
SHEET :023 SHEET :022

Page 50
START_SEQUENCE_2

V
HW
W IFB

V
HW
W IFB

SHEET NO :022

Page 51
START_SEQUENCE_3

INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD

STEP 2 – SEAL SYSTEM PUMP

ST_SEQ
ST-01B
C ST_SEQ ST_SEQ
HW 13-ZIC-10002 SHEET :042 AND S1
D ST-2 ST-2
SR
CLOSE FB FORM SHEET :043 SHEET :034
SDE I VENT VALVE
R
ST_SEQ
END

OR

ABORT
SEQ
SHEET :041

HW 13-EMRN-10031A
D
LO/WO COOLER FAN RUNNING =1
I
SDE RUNNING FB NOT RUNNING =0

HW 13-EMRN-10031B
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
AND
HW 13-EMRN-10031C
D
LO/WO COOLER FAN RUNNING =1
I
SDE RUNNING FB NOT RUNNING =0

SHEET NO :043

Page 52
START_SEQUENCE_3

HW 13-EMRN-10001
D
RUNNING =1
I FAN RUNNING FB
SDE NOT RUNNING =0

AND
HW 13-EMAV-10001
D
` OR
I FAN AVAIABLE FB AVAILABLE=1
SDE NOT AVAILABLE =0 START 13-PMST V
AND S Q
PUMP START
W
SR
R
SK S SEAL SYSTEM FAN STOP 13-PMSP- V
A
O COOLER PUMP STOP
F AUTO /MANUAL AUTO=1
W
SELECTION FROM M
DCS T GRAPHICS MANUAL =0

SK S SEAL SYSTEM FAN


O COOLER PULSE START START
F AUTO START FROM OR TIMER SEQ SEQ
DCS ST AND T#1S
T GRAPHICS
SHEET :041 SHEET :022
SK S SEAL SYSTEM FAN
O COOLER ABORT ABORT
F MANUAL START SEQ SEQ
ST
ST
DCS T FROM GRAPHICS SHEET :022
SHEET :023

SK S SEAL SYSTEM FAN RESET RESET


O COOLER AND SEQ SEQ
F AUTO STOP FROM
SP SHEET :023 SHEET :022
DCS T GRAPHICS

SK S SEAL SYSTEM FAN


O COOLER
AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR

AUTO AUTO
START START INTER INTER
LOCK LOCK SHEET NO :022
SHEET :023 SHEET :022
SHEET :023 SHEET :022

Page 53
START_SEQUENCE_3

V
HW
W IFB

V
HW
W IFB

SHEET NO :022

Page 54
Document

Project ---Tibr Haushi Development Phase 2B


S.No Document Title Document Number Revision Document type
1 Input/Output list - FCS & IPS water injection pump P-131001 TIB-13-4800096337-ZV-D05-00001-0001_04.pdf PDF
2 Cause and effect Diagram TIB-13-4800096337-ZV-D15-00001-0001_03.pdf 3 PDF
3 Control Philosophy and Safeguarding narrative TIB-13-4800096337-ZV-D05-00002-0001 3 Word
4 FUNCTIONAL LOGIC DIAGRAM_Sample STD 5 0403 003 A PDF