13-LT-10022 H>
A 13-LAL- 13-LAL-
H Alarm Setpoint I Diff level >L 10022 10022
= 88.5% Transmitter
AND
>= SHEET :001 SHEET :008
13-LT-10022
A
I Diff level >L
Transmitter 13-LAL-
13-LAL- 10022 SHEET NO :001
>= 10022
<=
SHEET :001 SHEET :008 13-LAL-10022
OR
13-LAH-
10022
SHEET :001
H Alarm Setpoint
13-LT-10022 = 88.3%
H
A
>=
I PUMP P-131001
SEAL SYSTEM L
TANK LEVEL
13-LAH- 13-LAH-
10022 10022
L Alarm Setpoint
= 26.5% SHEET :001 SHEET :001
<=
13-LAL- 13-LAL-
10022 10022
Page 1
Symbol sheet
START 13-LT-10022 V
Diff level HW
Transmitter W IFB
SHEET NO :001
13-LAH-10022
13-LAL-10022
Page 2
13-PT-10085 & 13-PT-10087
A1
INPUT OUTPUT
FIELD
13-PT-10085 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD
13-PALL-10085
13-PALL- 13-PALL-
10085 10085
DCS TAGS
SHEET :003 SHEET :027 NORMAL = 0
ALARM = 1
13-PALL-10087
13-PALL- 13-PALL-
10087 10087
SHEET :003 SHEET :028
DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :003
Page 3
13-PZT-10086 & 13-PZT-10088
A1
INPUT OUTPUT
FIELD
13-PZT-10086 - PUMP P-131001 SEAL SYSTEM PRESS ( DE SEAL) ALARM FIELD
SHEET NO :004
Page 4
13-TT-10066 & 13-TT-10067
A1
INPUT OUTPUT
FIELD
13-TT-10066 - PUMP P-131001 SEAL SYSTEM TEMP ( DE SEAL) ALARM FIELD
DCS TAGS
NORMAL = 0
ALARM = 1
DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :005
Page 5
13-LT-10022
A1
INPUT OUTPUT
FIELD
13-LT-10022 - PUMP P-131001 SEAL SYSTEM TANK LEVEL ALARM FIELD
13-LAL-10022
13-LAL- 13-LAL-
10022 10022
SHEET :006 SHEET :027 DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :006
Page 6
13-LT-10021 & 13-PT-10081
A1
INPUT OUTPUT
FIELD
13-LT-10021 - VOITH CPLNG GB-131001 OIL RESERVOIR LEVEL ALARM FIELD
13-LAL-10021
13-LAL- 13-LAL-
10021 10021 DCS TAGS
SHEET :007 SHEET :030 NORMAL = 0
SHEET :036 ALARM = 1
13-PAL-10081
13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :030
SHEET :045 DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :007
Page 7
13-PZT-10082 & 13-PDT-10083
A1
INPUT OUTPUT
FIELD
13-PZT-10082 - VOITH CPLNG GB-131001 LO PRESSURE AFTER LO FILTER ALARM FIELD
SHEET NO :008
Page 8
13-TZT-10061 & 13-TZT-10063
A1
INPUT OUTPUT
FIELD
13-TZT-10061 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD
HH Alarm Setpoint
HW 13-TZT-10061 = 70 DEG C
A
I VOITH CPLNG GB- ANALOG INPUT
131001 LO TEMP L >=
IPS AFTER COOLER HIGH LIMIT = SIGNAL PROCESSING
150 DEG C & SCALING
13-TAHH-10061
13-TAHH- 13-TAHH-
LOW LIMIT = 10061 10061
0 DEG C
IPS TAGS
SHEET :009 SHEET :031
NORMAL = 1
TRIP/ALARM = 0
13-TAHH-10063
13-TAHH- 13-TAHH-
10063 10063
SHEET :009 SHEET :031
IPS TAGS
NORMAL = 1
TRIP/ALARM = 0
SHEET NO :009
Page 9
13-TT-10060 & 13-TT-10062
A1
INPUT OUTPUT
FIELD
13-TT-10060 - VOITH CPLNG GB-131001 LO TEMP AFTER COOLER ALARM FIELD
DCS TAGS
NORMAL = 0
ALARM = 1
DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :010
Page 10
13-TC-10064 & 13-TS-10065
A1
INPUT OUTPUT
FIELD
13-TC-10064 - VOITH CPLNG GB-131001 OIL RESERVOIR TEMP CTR ALARM FIELD
<=
13-TAL-10064
13-TAL- 13-TAL-
10064 10064
DCS TAGS
SHEET :011 SHEET :036 NORMAL = 0
ALARM = 1
DCS TAGS
NORMAL = 0
ALARM = 1
SHEET NO :011
Page 11
MMS PUMP P-131001_1
A1
INPUT OUTPUT
FIELD
13-TE-10046A/B, 13-TE-10047A/B,13-TE-10048A/B - MOTOR P-131001-ME WIND TEMP (R),(S),(T) ALARM FIELD
Page 12
MMS PUMP P-131001_2
A1
INPUT OUTPUT
FIELD
13-TE-10043, 13-TE-10044,13-TE-10045 ALARM FIELD
13-TAHH- 13-TAHH-
AND 10043/44/45 10043/44/45
Page 13
MMS PUMP P-131001_3_H
A1
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0
SHEET NO :012
Page 14
MMS PUMP P-131001_3_HH
A1
INPUT OUTPUT
FIELD
13-TE-10037, 13-TE-10038,13-TE-10039, 13-TE-10040,13-TE-10041,13-TE-10042 ALARM FIELD
Page 15
MMS PUMP P-131001_VIB_1
A1
INPUT OUTPUT
FIELD
13-VZT-10007, 13-VZT-10008,13-VZT-10009, 13-VZT-10010 ALARM FIELD
Page 16
MMS PUMP P-131001_VIB_2
A1
INPUT OUTPUT
FIELD
13-VZT-10001, 13-VZT-10002,13-VZT-10003, 13-VZT-10004 ALARM FIELD
Page 17
MMS PUMP P-131001_VIB_3
A1
INPUT OUTPUT
FIELD
13-VZT-10005, 13-VZT-100064 ALARM FIELD
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0 SHEET NO :016
Page 18
MMS VOITH GB-131001_TEM_1
A1
INPUT OUTPUT
FIELD
13-TE-10052, 13-TE-10053,13-TE-10054, 13-TE-10055 ALARM FIELD
Page 19
MMS VOITH GB-131001_TEM_2
A1
INPUT OUTPUT
FIELD
13-TE-10056, 13-TE-10057,13-TE-10058, 13-TE-10059 ALARM FIELD
Page 20
MMS VOITH GB-131001_TEM_2
13-TAHH-
10053/54
SHEET :040
13-TAHH-
10052/55
SHEET :040
13-TAHH-
10057/58
SHEET :040
13-TAHH-
10056/59
SHEET :040
Page 21
MMS VOITH GB-131001_VIB_1
A1
INPUT OUTPUT
FIELD
13-VZT-10011, 13-VZT-10012,13-VZT-10013 ALARM FIELD
H Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 H = 220 MIL/S
10 MILS
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR
0 MILS H Alarm Setpoint 13-VZT-10011
HIGH LIMIT = = ±22.2 MILS
HW 13-VZT-10012 H 40 MILS >=
A
I VOITH CPLNG GB-
131001 AXL 1ST LOW LIMIT = 13-VZT-10012
MMS SHAFT VIBR - Z -40 MILS H Alarm Setpoint
= ±22.2 MILS
13-VZT-10013 HIGH LIMIT = >=
HW H 40 MILS
A
VOITH CPLNG GB-
I 131001 AXL 2ND LOW LIMIT = 13-VZT-10013
MMS SHAFT VIBR - Z -40 MILS
HH Alarm Setpoint
HIGH LIMIT =
HW 13-VZT-10011 = 315 MIL/S
10 MIL/S
A >=
I VOITH CPLNG GB- LOW LIMIT =
MMS 131001 CASING VIBR HH
0 MIL/S HH Alarm Setpoint 13-VZT-10011
HIGH LIMIT = = ±27.2 MILS
HW 13-VZT-10012
40 MILS >=
A
I VOITH CPLNG GB- LOW LIMIT = 13-VZT-10012
131001 AXL 1ST HH
MMS SHAFT VIBR - Z -40 MILS HH Alarm Setpoint
= ±27.2 MILS
HW 13-VZT-10013 HIGH LIMIT = >=
40 MILS
A
I VOITH CPLNG GB-
131001 AXL 2ND LOW LIMIT =
13-VZT-10013
MMS HH
SHAFT VIBR - Z -40 MILS
13-VAHH- 13-VAHH-
10011/12/ 10011/12/
AND
13 13
MCMS TAGS
SHEET :001 SHEET :001 NORMAL = 1
TRIP/ALARM = 0 SHEET NO :019
Page 22
MMS LO_WO_E-131002_3_VIB_1
A1
INPUT OUTPUT
FIELD
13-VZT-10014, 13-VZT-10012,15-VZT-10016 ALARM FIELD
H Alarm Setpoint
13-VZT-10014 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VZT-10014
= 16 MM/S
HW 13-VZT-10015 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VZT-10015
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10016 H >=
A
I LO/WO COOLER E-
131002/E-131003 13-VZT-10016
MMS FAN (K-131002) VIBR
MCMS TAGS
HH Alarm Setpoint NORMAL = 1
HIGH LIMIT =
HW 13-VZT-10014 = 17.8 MM/S TRIP/ALARM = 0
63.5 MM/S
A >=
I LO/WO COOLER E-
131002/E-131003 LOW LIMIT = 13-VZT-10014
MMS HH
FAN (K-131001) VIBR 0 MM/S HH Alarm Setpoint
= 17.8 MM/S
HW 13-VZT-10015
A LO/WO COOLER E- >=
I 131002/E-131003 13-VZT-10015
FAN MOTOR (K- HH
MMS 131001-ME) VIBR 1OO2 13-XZ-131007 A/B V
VOTING LO/WO COOLER
FAN K-131001 HIHI W HW
HH Alarm Setpoint VIB TRIP IPS
= 17.8 MM/S
HIGH LIMIT =
HW 13-VZT-10016 >=
63.5 MM/S 13-VZT-10016
A
LO/WO COOLER E- 1OO2 13-XZ-1310078A/B V
I 131002/E-131003 LOW LIMIT =
MMS HH VOTING LO/WO COOLER
FAN (K-131002) VIBR 0 MM/S
HH Alarm Setpoint FAN K-131002 HIHI W HW
HW 13-VZT-10017 = 17.8 MM/S VIB TRIP IPS
A >=
I LO/WO COOLER E-
131002/E-131003 13-VZT-10017
MMS HH
FAN (K-131001) VIBR
SHEET NO :020
Page 23
MMS LO_WO_E-131002_3_VIB_2
A1
INPUT OUTPUT
FIELD
13-VZT-10017, 13-VZT-10018,15-VZT-10019 ALARM FIELD
H Alarm Setpoint
13-VZT-10017 HIGH LIMIT = = 16 MM/S
HW H 63.5 MM/S
A LO/WO COOLER E- >=
I 131002/E-131003 LOW LIMIT =
MMS FAN (K-131001) VIBR 0 MM/S H Alarm Setpoint 13-VZT-10017
= 16 MM/S
HW 13-VZT-10018 H
A LO/WO COOLER E- >=
I 131002/E-131003 13-VZT-10018
FAN MOTOR (K-
MMS 131001-ME) VIBR H Alarm Setpoint
= 16 MM/S
HW 13-VZT-10019 H >=
A
LO/WO COOLER E-
I 131002/E-131003 13-VZT-10019
MMS FAN (K-131002) VIBR
HH Alarm Setpoint
HIGH LIMIT = = 17.8 MM/S
HW 13-VZT-10018
63.5 MM/S >=
A LO/WO COOLER E-
I 131002/E-131003
FAN MOTOR (K- HH LOW LIMIT = 13-VZT-10018
MMS 131001-ME) VIBR HH Alarm Setpoint
0 MM/S = 17.8 MM/S
HW 13-VZT-10019 >=
A
I LO/WO COOLER E-
131002/E-131003
13-VZT-10019
MMS HH
FAN (K-131002) VIBR
13-XZ-1310079A/B V
1OO2 LO/WO COOLER
VOTING FAN K-131003 HIHI W HW
VIB TRIP IPS
MCMS TAGS
NORMAL = 1
TRIP/ALARM = 0 SHEET NO :021
Page 24
SEAL SYSTEM FAN_COOLER_13-KS-10021
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 ALARM FIELD
HW 13-EMRN-10001
D
RUNNING =1
DCS I RUNNING FB
NOT RUNNING =0
AND
13-EMAV-10001
HW D
OR
DCS I AVAIABLE FB AVAILABLE=1
NOT AVAILABLE =0 START 13-EMST-10001 V
AND S Q
START HW
W MCC
SR
R
SK S 13-HS-10202 STOP 13-EMSP-10001 V
A
O STOP HW
F AUTO /MANUAL AUTO=1
W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
AND TIMER
T#1S
SK S 13-EMST-10001
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S 13-EMSP-10001
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START INTER INTER
LOCK LOCK SHEET NO :022
SHEET :023 SHEET :022
SHEET :023 SHEET :022
Page 25
SEAL SYSTEM FAN_COOLER_13-KS-10021_INTERLOCK
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD
13-TAH- 13-TAH-
10066 10066
SHEET :005 SHEET :023
AUTO AUTO
START START
SHEET :023 SHEET :022
13-TAH- 13-TAH-
10067 OR
10067
SHEET :005 SHEET :023
ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :023
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :023 AND
13-PALL- 13-PALL-
10088 10088
INTER INTER
SHEET :004 SHEET :023 LOCK
LOCK
SHEET :023 SHEET :022
SP_SEQ SP_SEQ
ST-4 ST-4
OR
SHEET :048 SHEET: 023
SHEET NO :023
Page 26
SEAL_SYSTEM_PM_13-KS-10022_023_1
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022,10023 – MAIN/STANDBY SELECTION ALARM FIELD
SK S 13-HS-10204
O
F DUTY/STANDY
M
DCS T FROM GRAPHICS ST STBY STBY
PUMP PUMP
A
SK S 13-HS-10206 AND B SHEET :024 SHEET :026
O
F DUTY/STANDY
S
DCS T FROM GRAPHICS ST
SK S 13-HS-10205 A
O AUTO /MANUAL
F SELECTION AUTO=1
M
DCS T FROM GRAPHICS MANUAL =0
SHEET NO :024
Page 27
SEAL_SYSTEM_PM_13-KS-10022_1
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10022 - MAIN PUMP ALARM FIELD
MAIN MAIN
PUMP PUMP
HW 13-PMRN-10004
D SHEET :024 SHEET :025
RUNNING =1
DCS I PUMP RUNNING FB
NOT RUNNING =0
AND
13-PMAV-10004
HW D
OR
DCS I PUMP AVAIABLE FB AVAILABLE=1
NOT AVAILABLE =0 START 13-PMST-10004 V
AND S Q
MAIN PUMP HW
START W MCC
SR
R
SK S 13-HS-10203 STOP 13-PMSP-10004 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
TIMER
T#1S
AND
SK S 13-PMST-10004
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S 13-PMSP-10004
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START INTER INTER
SHEET :027 SHEET :025 LOCK LOCK SHEET NO :025
SHEET :027 SHEET :025
Page 28
SEAL_SYSTEM_PM_13-KS-10023_1
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM PUMP – 12-KS-10023 – STANDBY PUMP ALARM FIELD
STBY STBY
PUMP PUMP
HW 13-PMRN-10005
D SHEET :024 SHEET :026
PUMP RUNNING RUNNING =1
DCS I
FB NOT RUNNING =0
AND
13-PMAV-10005
HW D
OR
DCS I PUMP AVAIABLE AVAILABLE=1
NOT AVAILABLE =0 START 13-PMST-10005 V
AND S Q
STBY PUMP HW
START W MCC
SR
R
SK S 13-HS-10205 STOP 13-PMSP-10005 V
A
O AUTO /MANUAL STBY PUMP HW
F SELECTION STOP W MCC
M AUTO=1
DCS T FROM GRAPHICS MANUAL =0
PULSE
AND TIMER
T#1S
SK S 13-PMST-10005
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S 13-PMSP-10005
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START
INTER INTER
SHEET :028 SHEET :026 LOCK LOCK SHEET NO :026
SHEET :028 SHEET :026
Page 29
SEAL SYSTEM_13-KS-10021_INTERLOCK
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM MAIN PUMP 13-KS-10022 – INTERLOCK ALARM FIELD
13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :027
13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :027
ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :027
SETPOINT NOT
AVAILABLE TRP SEQ TRP SEQ
13-PAH- 13-PAH-
10085 ST-3 ST-3
10085
SHEET :053 SHEET: 027
SHEET :003 SHEET :027 OR
INTER INTER
SP_SEQ SP_SEQ LOCK LOCK
13-PAH- 13-PAH- ST-4 ST-4 OR
10087 10087 SHEET :027 SHEET :025
SHEET :048 SHEET: 027
SHEET :003 SHEET :027
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :027 `
AND
13-PALL- 13-PALL-
10088 10088
SHEET :004 SHEET :027
SHEET NO :027
Page 30
SEAL SYSTEM_13-KS-10023_INTERLOCK
INPUT OUTPUT
DCS/FIELD
SEAL SYSTEM COOLER FAN 13-KS-10021 – INTERLOCK ALARM FIELD
13-PAL- 13-PAL-
10085 10085 OR
SHEET :003 SHEET :028
13-PAL- 13-PAL-
10087 10087
SHEET :003 SHEET :028
ST_SEQ ST_SEQ
ST-2B ST-2B
SHEET :045 SHEET :028
SETPOINT NOT
TRP SEQ TRP SEQ
AVAILABLE
13-PAH- 13-PAH- ST-3 ST-3
10085 10085 SHEET :053 SHEET: 028
SHEET :003 SHEET :028 INTER INTER
OR OR LOCK LOCK
SP_SEQ SP_SEQ
ST-4 ST-4 SHEET :028 SHEET :026
13-PAH- 13-PAH-
10087 10087 SHEET :048 SHEET: 028
SHEET :003 SHEET :028
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :028
AND
13-PALL- 13-PALL-
10088 10088
SHEET :004 SHEET :028
SHEET NO :028
Page 31
AUX LO PUMP_13-KS-10001
INPUT OUTPUT
DCS/FIELD
AUX LO PUMP P-131006 ALARM FIELD
HW 13-PMRN-131006
D
AUX LO PUMP RUNNING =1
DCS I RUNNING FB NOT RUNNING =0
AND
HW 13-PMAV-131006
D
OR
AUX LO PUMP AVAILABLE=1
DCS I AVAIABLE FB
NOT AVAILABLE =0 START 13-PMST-131006 V
AND S Q
AUX LO PUMP HW
START W MCC
SR
R
SK S AUX LO PUMP STOP 13-PMSP-131006 V
A
O AUX LO PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
AND TIMER
T#1S
SK S AUX LO PUMP
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S AUX LO PUMP
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
AUTO AUTO
START START INTER INTER
SHEET :029 LOCK LOCK SHEET NO :029
SHEET :030
SHEET :030 SHEET :029
Page 32
AUX LO PUMP_13-KS-10001_INTERLOCK
INPUT OUTPUT
DCS/FIELD
AUX LO PUMP 13-KS-10001 – INTERLOCK ALARM FIELD
13-PAL- 13-PAL-
10081 10081
HW 13-PMRN-131006 SHEET :007 SHEET :030
D
AND AUTO AUTO
AUX LO PUMP RUNNING =1 START START
I
DCS RUNNING FB NOT RUNNING =0
SHEET :030 SHEET :029
ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :030
13-PALL- 13-PALL-
10086 10086
SHEET :004 SHEET :030
13-PALL- 13-PALL-
10088 10088 INTER INTER
SHEET :004 SHEET :030 LOCK LOCK
SHEET :030 SHEET :029
13-PAH- 13-PAH-
10081 10081
SHEET :007 SHEET :030 OR
13-PALL- 13-PALL-
10082 10082
SHEET :008 SHEET :030
SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :048 SHEET: 030
Page 33
LO_WO_COOLER_13-KS-10031A
INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031A ALARM FIELD
HW 13-EMRN-10031A
D
LO/WO COOLER FAN RUNNING =1
IPS I RUNNING FB NOT RUNNING =0
AND
HW 13-EMAV-10031A
D
OR
LO/WO COOLER FAN AVAILABLE=1
IPS I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
SK S LO/WO COOLER TIMER
O FAN AND T#1S
F MANUAL START
DCS T FROM GRAPHICS ST
SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS
13-KMZA-
SK S 13101_2_3
O AND PULSE
F SOFT SIGNAL FROM
DCS TO IPS TO TIMER
IPS T START LO/WO T#1S
OR
COOLER
13-KMXZ-13101
SK S
O
F TRIP LO/WO
IPS T COOLER FAN K-
13101 MOTOR SHEET NO :031
Page 34
LO_WO_COOLER_13-KS-10031B
INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031B ALARM FIELD
HW 13-EMRN-10031B
D
LO/WO COOLER FAN RUNNING =1
IPS I RUNNING FB NOT RUNNING =0
AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
IPS I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031B V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031B V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
SK S LO/WO COOLER TIMER
O FAN AND T#1S
F MANUAL START
DCS T FROM GRAPHICS ST
SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS
13-KMZA-
SK S 13101_2_3
O AND PULSE
F SOFT SIGNAL FROM
DCS TO IPS TO TIMER
IPS T START LO/WO T#1S
OR
COOLER
13-KMZA-
SK S 131001_2_3
O
F SOFT SIGNAL FROM
DCS TO IPS TO
IPS T TRIP/STOP LO/WO SHEET NO :032
COOLER
Page 35
LO_WO_COOLER_13-KS-10031C
INPUT OUTPUT
DCS/FIELD
LO/WO COOLER FAN 13-UZ-10031C ALARM FIELD
HW 13-EMRN-10031C
D
LO/WO COOLER FAN RUNNING =1
IPS I RUNNING FB NOT RUNNING =0
AND
HW 13-EMAV-10031B
D
OR
LO/WO COOLER FAN AVAILABLE=1
IPS I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-10031A V
AND S Q
LO/WO COOLER HW
FAN START W MCC
SR
R
SK S LO/WO COOLER STOP 13-EMSP-10031A V
A
O FAN LO/WO COLLER HW
F AUTO /MANUAL AUTO=1 FAN STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
SK S LO/WO COOLER
O FAN
F MANUAL STOP
SP
DCS T FROM GRAPHICS
13-KMZA-
S 13101_2_3
SK O
SOFT SIGNAL FROM AND PULSE
F TIMER
IPS T DCS TO IPS TO
START LO/WO T#1S
OR
COOLER
13-KMZA-
SK S 131001_2_3
O
F SOFT SIGNAL FROM
DCS TO IPS TO
IPS T TRIP/STOP LO/WO
COOLER SHEET NO :033
Page 36
LO_WO_COOLER FAN_13-KS-10031ABC_INTERLOCK
INPUT OUTPUT
DCS/FIELD
LO/WO FAN COOLER 13-KS-10013A/B/C – INTERLOCK ALARM FIELD
13-KMXZ-13101
S SK
O
TRIP LO/WO F
COOLER FAN K- T IPS
13101 MOTOR
SK S 13-XZ-13107A/B
O 13-KMXZ-13102
LO/WO COOLER FAN
F K-131001 HIHI VIB S SK
IPS T TRIP O
TRIP LO/WO F
SK S 13-XZ-13108A/B COOLER FAN K- T IPS
O 13102 MOTOR
LO/WO COOLER FAN
F
K-131002 HIHI VIB
IPS T TRIP 13-KMXZ-13103
S SK
SK S 13-XZ-13109A/B O
OR
O TRIP LO/WO F
LO/WO COOLER FAN
F K-131003 HIHI VIB
COOLER FAN K- T IPS
IPS T 13103 MOTOR
TRIP
SP_SEQ SP_SEQ
ST-4 ST-4 SOFT SIGNAL FROM 13-KS-
10001(DCS) TO 13-UZ-10006 IPS
SHEET :048 SHEET: 034 TO TRIP/STOP LO/WO COOLER
13-UZ-10031A(IPS)
TRP SEQ TRP SEQ
ST-3 ST-3
SHEET :053 SHEET: 034 SHEET NO :034
Page 37
LO_HEATER_E-131004
INPUT OUTPUT
DCS/FIELD
13-KS-10024 L.O HEATER E-131004 CONTROL LOGIC ALARM FIELD
HW 13-EMRN-10004
D
LO HEATER RUNNING =1
DCS I RUNNING FB NOT RUNNING =0
AND
13-EMAV-10004
HW D
OR
LO HEATER AVAILABLE=1
DCS I AVAILABLE FB
NOT AVAILABLE =0 START 13-EMST-131004 V
AND S Q
LO HEATER HW
START W MCC
SR
R
SK S LO HEATER STOP 13-EMSP-131004 V
A
O LO HEATER HW
F AUTO /MANUAL AUTO=1 STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
AND TIMER
T#1S
SK S LO HEATER
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S LO HEATER
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
Page 38
LO HEATER_E-131004_ INTERRLOCK
INPUT OUTPUT
DCS/FIELD
13-KS-10024 L.O HEATER E-131004 CONTROL LOGIC ALARM FIELD
OR
13-LAL- 13-LAL-
10021 10021
SHEET :007 SHEET :036
SHEET NO :036
Page 39
MANI PUMP -P-131001
INPUT OUTPUT
DCS/FIELD
MANI PUMP -P-131001 ALARM FIELD
HW 13-PMRN-131001
D
MAIN PUMP RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
AND
HW 13-PMAV-131001
D
OR
MAIN PUMP AVAILABLE=1
SDE I AVAILABLE FB
NOT AVAILABLE =0 START 13-PMST-131001 V
AND S Q MAIN PUMP HW
START W MCC
SR
R
SK S MAIN PUMP STOP 13-PMSP-131001 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
DCS
SELECTION FROM M
T GRAPHICS MANUAL =0
PULSE
AND TIMER
T#1S
SK S MAIN PUMP
O
F MANUAL START
ST
DCS T FROM GRAPHICS
SK S MAIN PUMP
O AND PULSE
F MANUAL STOP
SP TIMER
DCS T FROM GRAPHICS T#1S OR
Page 40
MAIN PUMP_P-131001_ INTERRLOCK
INPUT OUTPUT
DCS/FIELD
MANI PUMP -P-131001 CONTROL LOGIC ALARM FIELD
STARTUP STARTUP
PERM PERM AUTO AUTO
START START
SHEET :039 SHEET :038 AND
SHEET :038 SHEET :037
ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :046 SHEET :038
SHEET NO :038
Page 41
WIP_PERMISSIVE
INPUT OUTPUT
DCS / FIELD
STARTUP PERMISSIVE 13-KS-10001 WI PUMP P-131001 CONTROL LOGIC ALARM FIELD
HW S 13-FZT-10001
O
PUMP-P-131001
F
DISCHARGE FLOW
IPS T LOW LOW
HW S 13-PZT - 10014
O
PUMP-P-131001
F
SUCTION PRESSURE
IPS T STARUP PERMISSIVE CONDITION
LOW LOW
S 13-PZT-10010A/B
HW
O STARTUP STARTUP
PUMP-P-131001 PERM PERM
IPS F DISCHARGE
T PRESSURE HI HI
SHEET :039 SHEET :038
HW S 13-HZS-10003 SHEET :041
O PUMP-P-131001
F EMERGENCY TRIP
PB ACTIVATED
IPS T FROM FILED
HW 13-HZS-10016
S PUMP-P-131001
O EMERGENCY TRIP
F PB ACTIVATED
IPS T FROM SROS 13-PALL- 13-PALL- AND
CONSOLE 10086 10086
SHEET :039 13-PALL- 13-PALL-
SHEET :004
10088 10088
SK S 13-FIC-10002 SHEET :004 SHEET :039
O
MIINIMUM BY-PASS
F LINE ON AND IN
DCS T AUTO MODE 13-TAHH- 13-TAHH-
10061 10061
Page 42
MMS_TRIP
INPUT OUTPUT
DCS / FIELD
MCMS TRIP LOGIC TO IPS ALARM FIELD
13-TAHH- 13-TAHH-
10046A/47A 10046A/47A
/48A /48A
13-TAHH- 13-TAHH-
10043/44/45 10043/44/45
13-TAHH- 13-TAHH-
10037/38 10037/38
13-VAHH- 13-VAHH-
SHEET :013 SHEET :040
10007/08 10007/08
Page 43
START_SEQUENCE
INPUT OUTPUT
DCS / FIELD
START SEQUENCE ALARM FIELD
SK S 13-PMST-10001
O START
F START SEQ FROM SEQ
DCS ST
T GRAPHICS
START SEQ
SK S 13-ABORT-10001
O ABORT ABORT
F ABORT SEQ FROM SEQ SEQ
SP
DCS T GRAPHICS SHEET :041 SHEET :041,042,043,04 ABORT SEQ
4,045,046,047
SK S 13-REST-10001
O RESET RESET
F RESET SEQ FROM SEQ SEQ
DCS T GRAPHICS ST
SHEET :041 SHEET :047 RESET SEQ
SEQUENCE START`
START
SEQ
AND
STARTUP STARTUP
PERM PERM S Q
ST_SEQ ST_SEQ
SHEET :039 SHEET :041 SR ON ON
R SHEET :041 SHEET :042
ST_SEQ ST_SEQ
END END
SHEET :047 SHEET :041 OR
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :041
SHEET NO :041
Page 44
START_SEQUENCE
Page 45
START_SEQUENCE_2
INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD
ST_SEQ ST_SEQ
ON ON
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :042
ST_SEQ
13-ZIO-10002 ST-1 AND
HW TON ST_SEQ
D
TIMER ST-01A
OPEN FB FORM T#60S
DCS I VENT VALVE
ST_SEQ
ST-01A S Q ST_SEQ ST_SEQ
SR ST-01B ST-01B
R SHEET :042 SHEET :043
ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET: 042
ABORT ABORT OR
SEQ SEQ
SHEET :041 SHEET :042
SHEET NO :042
Page 46
START_SEQUENCE_2
Page 47
START_SEQUENCE_3
INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD
ST_SEQ ST_SEQ
ST-01B ST-01B C ST_SEQ ST_SEQ
HW 13-ZIC-10002 AND S1
D SHEET :042 SHEET :043 ST-2 ST-2
SR
CLOSE FB FORM SHEET :043 SHEET: 030
I
DCS VENT VALVE SHEET :034
R
ST_SEQ ST_SEQ SK
MCMS TRIP S
END END
MULTIPLY O
SHEET :047 SHEET :043 OR F
T
IPS
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :043
HW 13-EMRN-10031A
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
HW 13-EMRN-10031C
D
AND
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
ST_SEQ ST_SEQ
ST-2 ST-2
SHEET :043 SHEET :043
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
SHEET NO :043
Page 48
START_SEQUENCE_3
SK
IPS
Page 49
START_SEQUENCE_5
INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD
13-PAL- 13-PAL-
10081 10081
SHEET :007 SHEET :045
SHEET NO :044
Page 50
START_SEQUENCE_5
Page 51
START_SEQUENCE_6
INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD
STEP 2C – SEAL SYSTEM PRESSURE CHECK
HW 13-EMRN-10031A
D
LO/WO COOLER FAN RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
13-PAL- 13-PAL-
10085 10085
SHEET :003 SHEET :027
13-PAL- 13-PAL-
10087 10087
HW 13-PMRN-10004
D
SEAL SYSTEM PUMP RUNNING =1
SDE I RUNNING FB NOT RUNNING =0
OR
HW 13-PMRN-10005
D
SEAL SYSTEM PUMP RUNNING =1
SDE I RUNNING FB NOT RUNNING =0 SHEET NO :045
Page 52
START_SEQUENCE_6
Page 53
START_SEQUENCE_7
INPUT OUTPUT
DCS / FIELD
START SEQUENCE- ALARM FIELD
STEP 3-- MAIN MOTOR START ,RECYCLE VALVE (FLOW CHECK), SPEED
CHECK, DISCHARGE VALVE OPEN
HW 13-PMRN-10001A
D
MAIN PUMP RUNNING =1
DCS I RUNNING FB NOT RUNNING =0
ST_SEQ ST_SEQ
ST-3 ST-3 ST_SEQ ST_SEQ
SHEET :046 SHEET :046 ST-3A ST-3A
AND
SK S 13-FZT-10001 SHEET :046 SHEET :046
O
PUMP-P-131001
F DISCHARGE FLOW
DCS T LOW LOW
SK S 13-VFD SPEED
O
PUMP-P-131001 VFD
F SPEED ABOVE SET
DCS T SPEED REQUIREMENT
Page 54
START_SEQUENCE_7
Page 55
START_SEQUENCE_8
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE ALARM FIELD
STEP 4—AUX LO PUMP STOP
ST_SEQ ST_SEQ
ST-4 ST-4 TON
TIMER
SHEET :046 SHEET :047 AND T#120S
SK S 13-ZIO-10001 S1 C
O SR
F OPEN FB FORM ST_SEQ
ST_SEQ
IPS T DISCHARGE VALVE
R ST-4A ST-4A
SHEET :047 SHEET :030
ST_SEQ ST_SEQ
END END
SHEET :047 SHEET :047 OR
ABORT ABORT
SEQ SEQ
SHEET :041 SHEET :047
RESET RESET
SEQ SEQ
SHEET :041 SHEET :047
SHEET NO :047
Page 56
START_SEQUENCE_8
Page 57
STOP_SEQUENCE
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE ALARM FIELD
SK S
O STOP
F STOP SEQ FROM SEQ
DCS ST
T GRAPHICS
STOP SEQ
STOP
SEQ
SP_SEQ SP_SEQ
AND TON
HW 13-PMRN-10001A ST-1 ST-1
D TIMER
T#5S SHEET :048 SHEET: 048
MAIN PUMP RUNNING =1
I
SDE RUNNING FB NOT RUNNING =0
SP_SEQ SP_SEQ
ST-1 ST-1
SHEET :048 SHEET: 048
AND
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1 TON S Q SP_SEQ SP_SEQ
I ST-2 ST-2
SDE RUNNING FB NOT RUNNING =0 TIMER
T#10S SR SHEET: 049
SHEET :048
R SHEET: 038
SP_SEQ SP_SEQ
END END
SHEET :050 SHEET :050
OR
RESET RESET
SEQ SEQ
SHEET :041 SHEET :048
SHEET NO :048
Page 58
STOP_SEQUENCE
Page 59
STOP_SEQUENCE_1
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE ALARM FIELD
SK S 13-ZIC-10001
O
F CLOSE FB FORM
IPS T DISCHARGE VALVE
SHEET NO :049
Page 60
STOP_SEQUENCE_1
Page 61
STOP_SEQUENCE_2
INPUT OUTPUT
DCS / FIELD
STOP SEQUENCE ALARM FIELD
SK S 13-EMRN-10031A
O
IPS F LO/WO COOLER FAN RUNNING =1
T RUNNING FB NOT RUNNING =0
SK S 13-EMRN-10031B
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0
SK S 13-EMRN-10031C
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0 SP_SEQ SP SEQ
END END
SK S 13-ZIC-10001
O
F CLOSE FB FORM
DCS T DISCHARGE VALVE
HW 13-EMRN-10001
D
SEAL SYSTEM
RUNNING =1
DCS I COOLER FAN
RUNNING FB NOT RUNNING =0
13-PMRN-10004
HW D
SHEET NO :050
Page 62
STOP_SEQUENCE_2
Page 63
TRIP_CONDITIONS
INPUT OUTPUT
DCS / FIELD
TRIP LOGIC AT 13-KS-10001 ALARM FIELD
SK S 13-FZT-10001
O
PUMP-P-131001
F
DISCHARGE FLOW
IPS T LOW LOW
SK S 13-PZT - 10014
O
PUMP-P-131001
F
SUCTION PRESSURE
IPS T LOW LOW
SK S 13-PZT-10010A/B
O
PUMP-P-131001
F DISCHARGE
IPS T PRESSURE HI HI
SK S 13-HZS-10003
O PUMP-P-131001
F EMERGENCY TRIP
PB ACTIVATED
IPS T TRIP CONDITION
FROM FILED
13-HZS-10016
SK S PUMP-P-131001 13- 13-
O EMERGENCY TRIP PMXZ- PMXZ-
F PB ACTIVATED 10001 10001
IPS T FROM SROS OR
CONSOLE SHEET :051 SHEET :052
13-PALL- 13-PALL-
10086 10086
13-TAHH- 13-TAHH-
10061 10061
13-TAHH- 13-TAHH-
SHEET :009 SHEET :039 10063 10063
SK 13-XZ-13101A/B
S SHEET :009 SHEET :039
O
WTR INJ PUMP P-
F 131001 MCMS TO IPS
T 13-PALL- 13-PALL-
IPS 10082 10082
SHEET :008 SHEET :039 13-XZ- 13-XZ-
13101A/B 13101A/B
Page 64
TRIP_SEQUENCE
INPUT OUTPUT
DCS / FIELD
TRIP SEQUENCE ALARM FIELD
13- 13-
PMXZ- PMXZ-
10001 10001
SHEET :051 SHEET :052 AND S Q
HW 13-PMRN-10001A TRP SEQ TRP SEQ
D SR ST-1 ST-1
MAIN PUMP RUNNING =1 R SHEET :052 SHEET: 038
DCS I RUNNING FB NOT RUNNING =0
Page 65
TRIP_SEQUENCE
Page 66
TRIP_SEQUENCE_1
INPUT OUTPUT
DCS / FIELD
TRIP SEQUENCE ALARM FIELD
SHEET NO :053
Page 67
TRIP_SEQUENCE_1
Page 68
TRIP_SEQUENCE_2
INPUT OUTPUT
DCS / FIELD
TRIP SEQUENCE ALARM FIELD
S 13-EMRN-10031A
SK
O
IPS F LO/WO COOLER FAN RUNNING =1
T RUNNING FB NOT RUNNING =0
TRP SEQ TRP SEQ
SK S 13-EMRN-10031B END END
O
F LO/WO COOLER FAN RUNNING =1 SHEET :054 SHEET :052
IPS T RUNNING FB NOT RUNNING =0 SHEET :053
SHEET :036
SK S 13-EMRN-10031C
O
F LO/WO COOLER FAN RUNNING =1
IPS T RUNNING FB NOT RUNNING =0
AND
TRP SEQ TRP SEQ
ST-3 ST-3
HW 13-PMRN-10001 SHEET :053 SHEET: 054
D
AUX LO PUMP RUNNING =1
DCS I RUNNING FB NOT RUNNING =0
SK S 13-ZIC-10001
O
F CLOSE FB FORM
DCS T DISCHARGE VALVE
HW 13-EMRN-10001
D
SEAL SYSTEM
RUNNING =1
I COOLER FAN
DCS RUNNING FB NOT RUNNING =0
13-PMRN-10004
HW D
Page 69
TRIP_SEQUENCE_2
Page 70