FOUNDATION POWER COMPANY (DAHARKI) LIMITED

Rev. No. : 00
OPERATION FORM

DHK-FPCDL-O-F-069 WTP Quality Monitoring Daily Log Sheet Page: 1 of 1

Date & Time :

System Parameter Unit Limit Analyzer Lab: Analyzer Lab:

Canal / Well Water pH 6.5 - 8.2

Conductivity Micro S /cm 265 -1860


Hydro
ppb < 10
Carbons
Turbidity NTU 1 - 1200

Coagulation Tank pH 6.5 - 7.5

PSF Inlet Turbidity NTU < 15

PSF Outlet Turbidity NTU 0 - 1.7

SS ppm < 10

Service Water (ACF) pH 7.0 - 8.2

Conductivity Micro S /cm 265 -1860

MgH ppm 30 - 190

CaH ppm 60 - 200

SDI <5

Free Chlorine ppm 0.02

DM Micro filter Outlet pH 6 - 6. 7

RO Product Unit "A/B" pH 4.8 - 5.7

Conductivity Micro S /cm < 165

RO Reject Water "A/B" pH 6.7 - 7.4

Conductivity Micro S /cm < 6500

Demin Water MBE "A/B" pH 6.5 - 7.5

Conductivity Micro S /cm 0.2

Silica as SiO2 ppb < 20

Demin Storage Tank pH 6.5 - 7.5

Conductivity Micro S /cm <1

Silica as SiO2 ppb < 20

Drinking Water pH 6.8 ~ 7.8

Conductivity Micro S /cm 400 ~ 700

Free Chlorine ppm 0.2

Neutralization Pit pH 6.0 - 9.0

Conductivity Micro S /cm < 5500

Remarks:
JTO Laboratory Laboratory Officer Sr. Chemical Engineer