This document provides a tagout order for equipment involved in a hydro test of the boiler super heater and economizer system. It lists 57 pieces of equipment that must be isolated including valves, breakers, and instruments. The equipment includes components on the steam drum, superheater headers, reheat headers, drains, vents, and associated piping. All valves and instruments are required to be closed or isolated except for the vent valves which must be open to allow venting during the hydro test.
This document provides a tagout order for equipment involved in a hydro test of the boiler super heater and economizer system. It lists 57 pieces of equipment that must be isolated including valves, breakers, and instruments. The equipment includes components on the steam drum, superheater headers, reheat headers, drains, vents, and associated piping. All valves and instruments are required to be closed or isolated except for the vent valves which must be open to allow venting during the hydro test.
This document provides a tagout order for equipment involved in a hydro test of the boiler super heater and economizer system. It lists 57 pieces of equipment that must be isolated including valves, breakers, and instruments. The equipment includes components on the steam drum, superheater headers, reheat headers, drains, vents, and associated piping. All valves and instruments are required to be closed or isolated except for the vent valves which must be open to allow venting during the hydro test.
Equipment Group Name: Hydro test Boiler Super Heater & Economizer System Hydro Test Eqp Kks Num: 1HAH Eqp Description: Boiler Super Heater & Economizer System Special Note: Make sure that every vent is properly primed and water is coming out of the vents
Tag # Eqp Kks Num: Equipment Description Tagged Position
1 1BBA14 11 KV BKR For FDF-1A 1HLB10AN001 Open / Rackout 2 1BCA24 11 KV BKR For FDF-1B 1HLB20AN001 Open / Rackout 3 1BFD14GS404F BKR For 3ry SH To Auxilary Steam Header MOV 1LBG30AA001 OFF 4 1BFG16GS206F BKR For Crh Steam To Aux Steam Header Mov 1lbg10aa001 OFF 5 1HAD50AA002 Water drum RHS drain valve Close 6 1HAD50AA001 Water drum LHS drain valve Close 7 1HAD50AA003 Water drum common drain line drain v/v to CBD tank Close 8 1HAH10AA004 SP lower header RHS drain isol. Valve Close 9 1HAH10AA003 SP lower header LHS drain isol. valve Close 10 1HAH20AA001 1ry SH inlet header LHS drain valve Close 11 1HAH20AA002 1ry SH inlet header RHS drain valve Close 12 1HAH40AA001 2ry sh inlet header LHS drain valve Close 13 1HAH40AA002 2ry sh inlet header RHS drain valve Close 14 1HAH60AA001 3ry sh outlet header LHS drain valve Close 15 1HAH60AA002 3ry sh outlet header RHS drain valve Close 16 1LAE21AA005 LHS SH spray water drain valve Close 17 1LAE22AA005 RHS SH spray water drain valve Close 18 1LBA20AA011 Main steam electromatic safety valve inlet isol. valve Close 19 1LAF10AA004 Cold RH Spray water TCV outlet isol. valve Close 20 1LBG30AA001 3ry SH Side Auxiliary steam MOV Close 21 1HCB10AA001 Soot blower steam supply MOV Close 22 1MAN10AA003 HP Turbine bypass control v/v inlet isol. valve Close 23 1MAN10AA004 HP Turbine by-pass warming isol. valve Close 24 1LBG10AA001 Aux steam PCV from cold reheat side inlet MOV Close 25 1MAN10AA003-A HP Turbine bypass control v/v inlet isol. v/v upstream balance valve Close 26 1MAN10AA003-B HP Turbine bypass control v/v inlet isol. v/v down stream balance valve Close 27 1LCR10AA014 Demin water to economizer supply line spool piece outlet isol. valve Close 28 1HAD10AA015 Steam drum level transmitter right -1 water side 1st isol. valve Close 29 1QCC02AA105 BCP suction manifold phosphate chemical injection 2nd isol. valve Close 30 1HAD10AA013 Steam drum level transmitter right- 1 steam side 1st isol. v/v Close 31 1HAD10AA041 Steam drum level transmitter right-2 water side 1st isol. valve Close 32 1HAD10AA039 Steam drum lt right-2 steam side 1st isol. valve Close 33 1HAD10AA025 Steam drum level transmitter left-1 water side 1st isol. valve Close 34 1HAD10AA023 Steam drum level transmitter left-1 steam side 1st isol. valve Close 35 1HAD10AA029 Steam drum level transmitter left-2 water side 1st isol. valve Close 36 1HAD10AA027 Steam drum level transmitter left-2 steam side 1st isol. valve Close 37 1QUA08AA003 Main steam sampling 2nd isol. valve Close 38 1QUA06AA001 Drum water sampling 1st isol. valve Close 39 1QUA07AA001 SCW roof inlet header sampling 1st isol. valve Close 40 1QUA04AA001 Economizer inlet feed water sampling isolating valve Close June 25, 2022 5:46 PM Page 1 of 2 Equipment Dependency for Tagout Order Equipment Group Code: 501016 Equipment Group Name: Hydro test Boiler Super Heater & Economizer System Hydro Test Eqp Kks Num: 1HAH Eqp Description: Boiler Super Heater & Economizer System Special Note: Make sure that every vent is properly primed and water is coming out of the vents
Tag # Eqp Kks Num: Equipment Description Tagged Position
41 1HAC22AA001 Economizer outlet header LHS vent & N2 supply isol. valve Open / Close 42 1HAC21AA001 Economizer outlet header RHS vent & N2 supply isol. valve Open / Close 43 1HAC21AA002 Economizer outlet header and N2 common vent valve Open / Close 44 1HAD10AA006 Steam drum RHS vent & N2 supply isol. valve Open / Close 45 1HAD10AA007 Steam drum LHS vent and N2 supply isol. valve Open / Close 46 1HAD10AA008 Steam drum & N2 common vent valve Open / Close 47 1LBA20AA012 Main steam line 1st vent valve Open / Close 48 1LBA20AA013 Main steam line 2nd vent valve Open / Close 49 1HAH11AA001 SP side wall LHS No.1 vent and N2 supply isol. valve Close 50 1HAH11AA002 SP side wall LHS No.2 vent & N2 supply isol. valve Close 51 1HAH12AA001 SP side wall RHS No.1 vent and N2 supply isol. valve Close 52 1HAH12AA002 SP side wall RHS No.2 vent & N2 supply isol. valve Close 53 1HAH10AA001 SCW roof inlet header vent and N2 supply isol. valve Close 54 1HAH21AA001 1ry SH outlet header LHS vent and N2 supply isol. valve Close 55 1HAH22AA001 1ry SH outlet header RHS vent and N2 supply isol. valve Close 56 1HAH51AA002 SH spray water line drain valve Close 57 1HAD10AA009 Steam drum CBD root valve Close