Professional Documents
Culture Documents
A Simple and Quick Chilled Water Loop Balancing Fo
A Simple and Quick Chilled Water Loop Balancing Fo
net/publication/26903239
A Simple and Quick Chilled Water Loop Balancing for Variable Flow System
CITATIONS READS
2 1,277
5 authors, including:
Mao Liu
Chinese Academy of Sciences
179 PUBLICATIONS 1,104 CITATIONS
SEE PROFILE
All content following this page was uploaded by Mao Liu on 22 January 2016.
Yeqiao Zhu, Ph.D. Mingsheng Liu, Ph.D. Tommy Batten Dan Turner, Ph. D.
Project Manager Associate Professor Researcher Professor
Texas A&M University University of Nabraska Texas A&M University
Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 15-17, 2000
ESL-HH-00-05-20
equipped with VFDs. The new approach of two variable speed pumps. Only one pump is on
balancing the variable flow chilled water risers line for each riser with the other in standby,
is: according to the leadlag control sequence. The
1. Fully open the entire manual balancing differential pressure (AP) is maintained by
valves for each coil on each floor. modulating the VFD of the chilled water pumps.
2. Optimize the differential pressure (AP) A typical riser diagram is shown in Figure 1. The
setpoints based on the riser layout and the AF' differential pressure sensor (AF'sensor) is located
sensor location. about 10 to 20 feet away fiom the far-end
3. After the implementation of the new cooling coil of the AHU on the top floor for each
setpoints, check the cold deck temperature for riser. The risers were balanced after the systems
each coil, the AF' for the furthest coils, critical were built.
coils, or any special coils. Make sure that there is
good cold deck temperature control and enough Measurement and Inspection Results
AP for each coil. The authors performed a detailed inspection
4. Identify each faulty sensor and valve and and took measurements for all the riser systems.
any control problems for the coil control valve. Measurements include loop AP, building AF', far-
Repair any that are malfunctioning. end coil AP or riser control AF' (sensor location),
5. Fine-tune the setpoints based on the actual each manual balance valve status, VFDs speed
load conditions and the control results. and cold deck temperature.
Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 15-17, 2000
ESL-HH-00-05-20
AHUs, but also the small FCUs. The new AF' and after the balancing.
setpoints were implemented through the EMCS.
The cold deck temperatures were checked before
Riser A 1
Troubleshooting and Fine-tuning were full open, but were maintaining excessively
From the EMCS readings and field-measured low cold air temperatures. This problem was
results, the following problems were identified: solved after calibrating the sensors and balancing
1. Cold air temperature sensor problem: the systems.
For AHUS 1 - 5 ,- n - t . m & - w ontl
2M4, the sensor readings were higher than w f increased cooling load:
actual temperature. Consequently, the valves
1.
Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 15-17, 2000
L.
ESL-HH-00-05-20
Table 1. Summary of chilled water system condition before and after reset and estimated savings
Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 15-17, 2000
ESL-HH-00-05-20
Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, TX, May 15-17, 2000