Technical Specification For Dual Fuel Fire Tube Boiler

Sr No Description Specification

Installation type Horizontal Fire Tube Gas


Fired Steam Boiler
1 Supply Of Fire Tube Gas Boiler Capacity 1000kg/Hr
Safety Nos Double
Burner Type Fully auto Dual Fuel Burner
Diameter 12"*30' Length
2 Supply of Chimney for 1000 Thickness 3mm MS
kg/hr Boiler Chimney Cap. 01 pcs
Chimney Base 01 pcs
Diameter 12"*54"
Inlet 01 point
3 Supply Of Steam Header Outlet 01 point
Specific Points Drain point, steam trap set
Insulated By Glass Wool & SS Sheet
Recovery Type Condensed water
Tank Material MS Sheet
4 Supply Of Preheated Feed Thickness 3mm
water Tank for 1000kg/hr Preheated by Condensed Steam
Boiler Points Water inlet & outlet point
Capacity 500 Ltr
Thickness 3mm
5 Supply Of Diesel Oil Tank Material Type MS Sheet
Oil lucking glass. oil
inline,outline
Capacity 1000 liter/hr
Softner body PVC
Softner head Same Auto
6 Supply of water softner Resin Lanxess
origin India
Maximum Hardness 80 PPM
Input water 0 to 5 PPM
Specification Of Steam Boiler
Brand Name To be mention
Model No To be mention
Type Horizontal three pass
Boiler Manufacturer Capacity 1000 kg/hr
1
Design Pressure 10.5 kg/cm
Working Pressure 10 kg/cm
Power 3.5 KW
Fuel Gas & Diesel Fired
Fire Shell T 12 mm
Water Shell T 10 mm
Base Plate Front T 14 mm
2 Boiler Metal Base Plate Back T 14 mm
Outer Sheet MS color sheet
Hi Castable Fire Cement USA
Fire Tube Seamless Dia51mm, T-
3.5mm
Burner Type Gun Type
Main Solenoid Valves Korea or equivalent
3 Burner Pilot Solenoid Valves Korea or equivalent
Ignition Transformer Korea or equivalent
Spark Electrode rod USA or equivalent
Flame sensor USA or equivalent
Panel Board Box Golden Boiler Co. Ltd
Burner Controller Korea or equivalent
Water Controller Korea or equivalent
Magnetic conductor Korea or equivalent
4 Panel Board
Fuse Korea or equivalent
Selector switch Korea or equivalent
Push switch Korea or equivalent
Indicator Lamp Korea or equivalent
Connector Korea or equivalent
Pressure switch Korea or equivalent
Pressure meter Korea or equivalent
Safety valves Taiwan or equivalent
5 Safety System Steam valves Italy or equivalent
Drain valves Italy or equivalent
Water level control valve Taiwan or equivalent
Glass cock set Korea or equivalent
Pump Italy or equivalent
None Return Valve Italy or equivalent
6 Pump Check Valves Italy or equivalent
Feed water stop valve Italy or equivalent
Ball Valve-100% SS Italy or equivalent
Terms and Condition:

01. Suppler will arrange test, trail , installation and operational training
02. Manufacturer should be submitting design and drawing and boiler authorize approval.
03. Supplier should provide all tested document which is relevant with Quality Control
during boiler delivery period.

a. Butt weld 100% Test by Radiography Testing by ISO Certify third party Company and test
report should be submit with boiler document
b. Fillet Weld 100% Test by Phased Array Ultrasonic Testing by third party Company.
c. Heat Treatment Report with Testing Graphs.
d. Hydraulic Test Report
Boiler structure can be made local or foreign but spare and accessories should be use world
renowned manufacturer only.
01 Year warranty