Professional Documents
Culture Documents
Current Transducer 5A - MACX-MCR-SL-CAC-5-I-EN-02
Current Transducer 5A - MACX-MCR-SL-CAC-5-I-EN-02
Data sheet
103161_en_02 © PHOENIX CONTACT 2013-04-22
1 Description
The MACX MCR-SL-CAC-5-I(-UP) current transducer con- Features
verts sinusoidal alternating currents 1 A or 5 A into standard
– Wide-range version (MACX MCR-...-UP) up to 253 V
analog signals 0...20 mA or 4...20 mA. The DIP switches ac-
AC/DC
cessible on the topside of the housing enable configuration
of the input and output current. The MACX MCR-SL-CAC-5- – 24 V DC version with additional supply via DIN rail con-
I current transducer provides a voltage supply range of 19.2 nector
V DC to 30 V DC. – Input/output can be configured via DIP switch
The MACX MCR-SL-CAC-5-I-UP current transducer in- – Operating state indication via LED
cludes a wide-range version with a supply voltage range
from 19.2 V AC/DC to 253 V AC/DC.
This data sheet is valid for all products listed on the following page:
MACX MCR-SL-CAC- 5-I
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Safety regulations and installation notes.................................................................................. 6
5.1 Installation notes ................................................................................................................. 6
5.2 Installation in the Ex area (zone 2)............................................................................................ 6
6 Installation ............................................................................................................................... 7
6.1 Connection notes ................................................................................................................ 7
6.2 Structure ........................................................................................................................... 7
6.3 Block diagram ..................................................................................................................... 7
6.4 Power supply ...................................................................................................................... 7
6.5 Assembly........................................................................................................................... 8
6.6 Connecting the wires ............................................................................................................ 8
7 Configuration ........................................................................................................................... 9
8 Application example ................................................................................................................ 9
3 Ordering data
4 Technical data
Signal input
Voltage input signal ≤ 300 V AC
Current input signal 0 A AC ... 0.001 A AC
0 A AC ... 0.005 A AC
Input impedance < 50 mΩ
Output
Output description Current output
Non-load voltage 15 V
Current output signal 0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Max. current output signal 25 mA
Configurable/programmable Via DIP switches
Ripple < 10 mVPP (for 500 Ω at 20 mA)
Load/output load current output < 500 Ω (at 20 mA)
Status display LED red (error), LED green (ready)
Output description No switching output
General data
Measuring principle True r.m.s. value measurement at 50 Hz
Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions)
Additional error approx. 2 % (45 Hz)
approx. 1 % (65 Hz)
Temperature coefficient, typical < 0.015 %/K
Maximum temperature coefficient < 0.02 %/K
Step response (10-90%) max. 300 ms
typ. 200 ms
Protection against polarity reversal Yes
Mounting position Any
Degree of protection IP20
Surge voltage category II
Pollution degree 2
Dimensions W / H / D 22.5 mm / 104 mm / 114.5 mm
Type of housing Polyamide PA non-reinforced green
Connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C (-4°F ... 149°F)
Ambient temperature (storage/transport) -40 °C ... 85 °C (-40°F...185°F)
Permissible humidity (operation) 10 % ... 95 % (no condensation)
Maximum altitude for use above sea level 2000 m
Conformance / approvals
Conformance CE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada UL 508 Recognized
The device contains components that can be N(-) 1.4 3.3 GND
3.4 GND
damaged or destroyed by electrostatic dis-
charge. When handling the device, observe 4.1 1A
the necessary safety precautions against 4.2 5A
electrostatic discharge (ESD) according to 4.3 NC
EN 61340-5-1 and EN 61340-5-1. 4.4
IN
NOTE:
5A
1
1A
2
O 1
F
4
F
N
O
R
-C
R
E
A
C
W
P
-I
-U
P
D
N
G
N
(-
G
N
D
)
(-
N
N
IG
T
)
+
U
L(
O
)
+
L(
A B C block.
Use a screwdriver to tighten the screw in the opening above
the connection terminal block.
DIP
C
N
0...20mA
5A
1A
2
O 1
F
F
N
O
S
L
5A
R
-C
R
E
A
C
R
-5
W
P
-I
-U
P
D
N
G
D
)
N
(-
G
N
D
)
(-
N
N
IG
T
)
+
U
L(
O
)
+
L(
24V
A
00
10 Mains voltage
32823 Blomberg, Germany