Westinghouse A200 overload heater elements can be identified by the catalog number on
one terminal. Heater selection should be based on the full load current and service factor
which is listed on the motor nameplate.
If the motor and overload relay are in the same ambient, and the service factor of the
motor is 1.15 to 1.25, pick heaters from the table below. If the motor service factor is 1.0
or a maximum of 115% protection is wanted, pick one size smaller heater than indicated.
Heater
Block Type
Size Starter Catalog
Block Type Overload Single Pole Type Overload Single Pole Type
Number
Using 3 Heaters Overload Using 3 Overload
Heaters
[Back to Top]
Ambient Non-
Size
Compensated Encl. Compensating Cat. No.
Starter
Starters Encl. Starters
All Applications
85 - 92 78 - 84 FH88
93 - 101 85 - 91 FH89