Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Commissioning / Status Report Belimo Energy Valve

Device Mp Serial Number 22222-30015-022-168

Protocol creation date/time 19.08.2022 / 00:00

Project Name Project Name

Address ,

Installation Location 16 PAV - CA-01

Device Name Energy Valve

Device Type EV100+AKRX-E

Application Settings IP Settings

Valve Type 2way MAC Address 50:2d:f4:2c:7c:d3

Nominal Pipe Size 1" | DN25 IP Host Address 192.168.0.10

Nominal Flow 4.13 m3/h IP Mode Static

Media Water Network Mask 255.255.255.0

Glycol Concentration 0.00 % Gateway 0.0.0.0

Maximum Flow 3.72 m3/h Broadcast Address 192.168.0.255

Maximum Power 70.83 ton

Control Mode Flow control Communication Settings


Setpoint Source Analog Bus Protocol BACnet MSTP

Control Signal Range (Y3) 0.5-10V

Invert Control Signal inverted Device Object Settings


Range (Y3)
Instance ID 1
Analog Feedback (U5) Relative flow Device Name Energy Valve
Analog Feedback Range 0-10V BACnet Location Device Location

System Status Operational

Protocol Version 1

Protocol Revision 14

Page 1 / 2
BACnet MS/TP Settings Version Information

Baud Rate 38400 BSP Version 13.9.0

Bus Address 16 CSP Version 4.21.2

120 Ohm Termination Disabled Application Model EV4

Max Master 127 Application Version 1.0.10

Live Values

Forced Control None

Valve Position 70.90 %

Actuator Sync Position Sync at 0%

Flow 3.44 m3/h

External Temperature 18.24 °C


Sensor (T1)

Integrated Temperature 19.23 °C


Sensor (T2)

Heating Energy 0.07 tonh

Cooling Energy 61.15 tonh

Total Volume 112.03 m3

Delta T Manager Status not selected

Delta T Manager

dT Limiting Function Off

dT Limiting Value 5.55 °C

Health State

Health State OK

Page 2 / 2