Release Notes

EcoStruxure™ Building Operation

v3.0.2

This document is written for and on behalf of Schneider Electric and is supplied on the express terms
that it is to be treated as confidential and that it may not be copied, used or disclosed to others except as
authorized in writing by this Company. This document is intended for internal use only.
[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

Table of contents
1. INTRODUCTION ................................................................................................................................. 3

1.1 Change History.............................................................................................................................................. 3

2. ECOSTRUXURE BUILDING OPERATION V3.0.2 RELEASE AVAILABILITY ................................ 4

3. NEW FEATURES IN THE ECOSTRUXURE BUILDING OPERATION V3.0.2 RELEASE ................ 5

3.1 Device Administrator .................................................................................................................................... 5

3.2 Bluetooth support for IP Controllers ........................................................................................................... 5

4. FIXED DEFECTS IN THE ECOSTRUXURE BUILDING OPERATION V3.0.2 RELEASE ................ 6

4.1 Defects fixed in EBO v3.0.2 .......................................................................................................................... 6

4.2 Workarounds and known defects in v3.0.2 ................................................................................................. 8

5. IMPORTANT ENGINEERING INFORMATION ................................................................................. 15

6. APPENDIX A – SUPPORTED UPGRADE PATHS .......................................................................... 16

6.1 Upgrade paths ............................................................................................................................................. 16

6.2 Server upgrade options .............................................................................................................................. 16

6.3 IP Controllers Shipped from the Factory .................................................................................................. 17

7. APPENDIX B – INSTALLATION ...................................................................................................... 18

7.1 Installing v3.0.2 on a greenfield site .......................................................................................................... 18

7.2 Upgrading from an earlier release to v3.0.2 .............................................................................................. 18

7.3 Upgrading from v3.0.1 to v3.0.2 ................................................................................................................ 18


7.3.1 Automation Server ....................................................................................................................................................... 18
7.3.2 Enterprise Server ......................................................................................................................................................... 20
7.3.3 Enterprise Central ........................................................................................................................................................ 20
7.3.4 WorkStation ................................................................................................................................................................. 20
7.3.5 License Administrator ................................................................................................................................................... 20
7.3.6 Reports Server ............................................................................................................................................................. 20

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 2 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

1. Introduction
The EcoStruxure™ Building Operation (EBO) v3.0.2 Release Notes document details changes
made since the release of v3.0.1.This document should therefore be read in conjunction with
the v3.0.1 release notes.

V3.0.2 is a maintenance release and includes:


• A consolidation of resolved field reported and internal found defects.
• Changes to the Device Administrator to eliminate the need for 2 versions. DA now
supports upgrading a server, applying a hot fix and applying a new database.
• Addition of Bluetooth support for the IP Controllers

For information on the Building Management Systems software support policy please refer to
the Product Announcement (PA-00271 R2) which can be found on The Exchange here and
also the Software Support Policy for EcoStruxure™ Building Operation which can be found
here.

Please note the following:


• This release supersedes the v3.0.1 release and should be used for all upgrades to 3.0
and for new greenfield sites.
• There is a new build of the IP controller firmware to accompany this release (v2.00.02).
• It is imperative that any upgrades be accomplished only after reading and
understanding this document and the v3.0.1 release notes, especially those areas that
are related to the transition process.

1.1 Change History


Revision Date Author Description/Change
A 2019-06-27 C. Bate Initial skeleton document.
2019-07-03 C. Bate Added defect tables
2019-07-12 C. Bate Updated build numbers and defect tables, removed defect
#41933 as not fixed, ready for publication.
B 2019-07-16 C. Bate Added additional fixed defects #41651, #41503. Added known
defect #42131 and referenced in section 5.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 3 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

2. EcoStruxure Building Operation v3.0.2


Release Availability
The software included in the EcoStruxure Building Operation v3.0.2 Release deliverable is
available for download on The Exchange and includes the following software:
Hot fixes to prepare for the direct upgrade to v3.0.2 (see section 9.2 of the 3.0.1 release
note for details)
Upgrading From Required Hot Fix
1.7.2.xxxx WorkStation hotfix v1.7.2.11111
1.8.1.xxxx WorkStation hotfix v1.8.1.23000

Product Version Build


Device Administrator v3.0.2.33- EcoStruxure Building - Software 3.0.2 33
Enterprise Central v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
Enterprise Central Hotfix v3.0.2.33- EcoStruxure Building - Software 3.0.2 33
Enterprise Server v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
Enterprise Server Hotfix v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
WorkStation v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
WorkStation Hotfix v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
License Administrator v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33
Reports Server v3.0.2.33 - EcoStruxure Building - Software 3.0.2 33

This release is also compatible with:


EcoStruxure Building Operation Automated Engineering Tool build 3.0.1.8.
An update will follow for the Vista transition tool in a few weeks.
EcoStruxure Building Operation Project Configuration Tool build 1.2.5.15, note; this version is
also compatible with EBO 3.0.1.
Warning, please see the warning relating to defects fixed #42009 & #42010 on page 7 below.

NOTE: StruxureWare Building Operation Technical Tool is not supported for use with
EcoStruxure Building Operation.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 4 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

3. New Features in the EcoStruxure Building Operation


v3.0.2 Release

3.1 Device Administrator


This release introduces a further enhancement to the new Device Administrator introduced in
v3.0.1. The DA now also supports ‘Applying a hotfix’, consequently there will only be the one
version of DA which supports the following options:
• New database applies a new database
• Upgrade database upgrades from one release to another later release
• Apply hotfix used to apply a hot fix or a maintenance release to the same release
• Get backup set from device

Hotfixes from v3.0.2 and later will consist of a file that is only used with the new device
administrator, (do not attempt to install the hotfix by running the file).
When the ‘Apply hotfix’ is selected the user is presented with a dialogue box where the
required hotfix file can be loaded, this is then applied to the SmartX server.
Hotfixes will continue to be provided by PSS using the existing hotfix process.

Note: Currently an internet connection is required to validate the integrity of the hotfix file when
loading the file into DA, this is being amended for the next release. However until then an
internet connection will be required to apply this maintenance release to a v3.0.2 system.

3.2 Bluetooth support for IP Controllers


The WorkStation has been enhanced to provide support for application images and
configurable menus that can be uploaded to controllers via Bluetooth. If you wish to use
Bluetooth connectivity to manage images and configuration menus, these must have been
created in v3.0.2

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 5 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

4. Fixed Defects in the EcoStruxure Building Operation


v3.0.2 Release

4.1 Defects fixed in EBO v3.0.2


This section lists all defects fixed in this release by functionality since the release of v3.0.1.
The ‘fixed in’ column shows which release the defect was first fixed and released in.
Note: Fixed in releases marked with a ‘*’ were first provided in a Consolidation Point (CP)
i.e. 3.0.2* means the defect was first provided in a 3.0.1 CP and formally released in 3.0.2.

Alarms Defect Fixed PSS


Summary ID in Ticket ID
Alarms and Events are not shown as expected when accessed by 40594 3.0.2 52954629
domain user using WebStation
Workstation AS-P: Alarms integrity check does not remove invalid 41142 3.0.2 55729096
alarms

Device Administrator Defect Fixed PSS


Summary ID in Ticket ID
Device Administrator: Auto refresh of license information can cause the 41724 3.0.2 -
state column to show unexpected status
Device Administrator: Auto generating new ssh fingerprints because 41733 3.0.2 -
servers file has invalid ones, is not considered as a change to the
server list xml file

I/A Series Defect Fixed PSS


Summary ID in Ticket ID
Unable to set multiple values in Priority Array after an application 41578 3.0.2 52714794
download

IP Controller Defect Fixed PSS


Summary ID in Ticket ID
AS-P restarted (Warm Start) when saving a Script program in RPC 41458 3.0.2 99

I/ Net Defect Fixed PSS


Summary ID in Ticket ID
After upgrading from SBO 1.8 to 1.9, a ContractViolation occurs in the 39244 3.0.2 51373846
INetPlugin and the AS-P crashes.
INET UPD update error in AS-P 41503 3.0.2 58068435

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 6 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

Licensing Defect Fixed PSS


Summary ID in Ticket ID
Device Administrator - Some license operations fails when many AS’s 41445 3.0.2 -
are activated at the same time

LonWorks and Xenta Defect Fixed PSS


Summary ID in Ticket ID
Can’t run LNS with LNS Plugins 41862 3.0.2 59031941,
98

Project Configuration Tool (LonWorks) Defect Fixed PSS


Summary ID in Ticket ID
Lon bindings missing binding direction for SNVT Outputs in PCT 42009 1.2.5 59582148
SNVT binding disappear in PCT when upgrading from 2.0.1 to 3.0.1 42010 1.2.5 59795746

WARNING: The above 2 PCT defects were introduced in PCT v1.2.4 for EBO v3.0.1 only (does not
affect EBO 2.0.4), the consequence of these defects are that any Lon-objects created with the PCT
v1.2.4 will be corrupt and therefore must be deleted and recreated using PCT v1.2.5 and then deployed
again using v1.2.5.

Report Server Defect Fixed PSS


Summary ID in Ticket ID
Report Server cannot process Extended Trend Logs where the object 41808 3.0.2 58553388
name has double byte chars in SQL.

Upgrade Defect Fixed PSS


Summary ID in Ticket ID
Cannot log on with WorkStation / WebStation after ES Upgrade to 41791 3.0.2 58704327
2.03: Error: Service is not supported
Workstation freezes after upgrading from v1.9.3.24 to v2.0.3.45 41661 3.0.2 58098500,
58556274

Vista Conversion Defect Fixed PSS


Summary ID in Ticket ID
Binding path changed for graphic when doing Custom Type Check out 41651 3.0.2 58341678
and Undo check Out

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 7 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

WebStation Defect Fixed PSS


Summary ID in Ticket ID
WebStation - Slideshow viewer crash when adding only one item 41807 3.0.2 -
Graphic not working in WebStation when accessed via the ES server 41818 3.0.2 58912300
after upgrading to v3.0.1
WebStation - object without read access shown in menu 41744 3.0.2 -
Server, WebStation - SSL related exception not handled correct when 41809 3.0.2 -
browser closed

WorkStation Defect Fixed PSS


Summary ID in Ticket ID
Workstation crash after changing Alarm View and Event View filter 42063 3.0.2 60095585
setting

4.2 Workarounds and known defects in v3.0.2


This table list the known defects in this release. Those marked with an * after the Defect number
are new with this release.

Defect Functionality Description Workaround

Bindings to BACnet properties


other than Value and Priority are
currently not restricted in the CM
object. When these properties are
viewed/set in the eCT tool,
CAM-Menu item referring to alarm
41414 Alarms however, an error occurs. CM
type settings doesn't work in eCT
object users should avoid making
bindings to BACnet properties
other than Value and Priority. See
EBO help for the CM object for
more details.
Backup: Can't retrieve backup from
Backup and
28490 ES/AS via WorkStation port 80 (only -
Restore
8kb large)
The path simply cannot be edited,
25694 Backup and On ES, Back up sets path, should be
even if looks like it can
Restore greyed out.
Ignore the status flags and trust
Wrong value on Xenta Status flags the object overlay. A Xenta field
26374 Backup and after a device is duplicated using device should always be updated
Restore Restore from a backup set and commissioned when it is
assigned to a new serve

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 8 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

WorkStation offers the choice to


create BACnet objects in the
MP/RP/IP-IO IP Field Controllers
that are not appropriate for the
given terminal type of the
controller. For instance, the user
may be offered a choice to create
WorkStation offers choice to create
a Digital Pulsed Output when no
41493 BACnet "variations" of BACnet objects not
appropriate terminal is present on
intended for the target device model
the controller. Although the
presence of BACnet points that
cannot be associated with a valid
terminal presents no operational
problem, users are advised to
delete objects of these type if they
mistakenly create them.
Do not configure an EBO Event
EBO BACnet Event Enrolment
Enrollment with Event Parameters
accepts Command Failure Event
41537 BACnet that specify the Command Failure
Parameters when written from 3'rd-
Even Type, when using a 3’rd-
party device, but doesn't support them
party B-OWS
Performing a BACnet Device Although the display is expected to
Discovery can cause the display to automatically remove one of these
temporarily show two BACnet devices devices, the user can manually
41675 BACnet with the same name. This condition clear the condition if it persists. To
can result when the name of a hosted do so, hold down the ALT key
BACnet device is changed, then re- while pressing the Refresh button,
discovered in the Device Discovery or restart WorkStation.
Performing a BACnet Device
Discovery can cause the Trace Log to
contain messages that may lead
customers to believe an operational
problem exists. The log messages
look like this:
nsp.pin.BACnet BACnet
devices:GetObjectInstance: Unknown If users observe these Trace Log
Object (0xa0009): entries and the entries coincide
41691 BACnet ~/System/Modules/BACnet with a BACnet Device Discovery
devices/Device operation, they should be aware no
discovery/Network_123/MyDevice operational problem is present.
We believe the presence of these
messages are more likely to occur
when large numbers of BACnet
devices or discovered and/or when
devices are configured on slower
BACnet data links, such as MS/TP.

The resulting list of discovered


BACnet devices may differ from the
41701 count in the status bar in Device
BACnet -
Discovery. The count may be higher
or lower than the actual number of
devices presented.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 9 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

Using binding templates for IP


36764 Binding networks with 170+ configured MPx Drag less number of MPx devices
templates devices can result in workstation into the custom binding template.
crash
MPX: Drag and Drop binding to an
40854 Bindings input is not possible with a value Manually type in point location
already used as an output
41524 CIO modules go offline on an AS-P
CIO None
during runtime
36741 Compatibility Document file type not recognized on Log on with a compatible version
mode a compatibility AS of WorkStation directly on the AS
36742 Compatibility TGML menu not working on a Log on with a compatible version
mode compatibility AS of WorkStation directly on the AS
35685 Re-create the object and fix
Custom types Attaching object with the same name
references
AS-P cannot be added to Device
Device
39352 Administrator if semicolon (;) is Do not use “;” in admin password
Administrator
included in password

Licensing violation alarm is


41732 Device No violation banner is shown and
sometimes triggered without any
Administrator the alarm is reset automatically.
violation cause.

This is a display issue and it has


41738 Device License information shows incorrect
no detrimental effect on the
Administrator number of "Used" licenses
running system
17431 Monitored Variable for a Function
Engineering -
Block Alarm can be edited.
Changing Menta blocks to another
12615 type and keeping the old name ends
FBP/Menta -
up with those blocks showed offline in
SW WorkStation
Runtime compatibility: Unable to
40741 Graphic locate path in graphic on compatibility Upgrade AS
AS
42131 Graphics Documentation: Webhelp - Security Please see section 5 below for
Settings page needs an update to details.
include information on new setting
"Enable WebStation to use unsafe
string evaluated JavaScript methods
like 'eval'
39811 I/A Series After uninstalling EBO WorkPlace -
Tech version 2.1 it's no longer
possible download or save WPT
applications in other versions of EBO
WPT.
28853 I/A Transition Unable to connect objects in Set the regional settings of the
WorkPlace Tech Editor client machine to use period as
the decimal separator.
30169 I/A Transition No error message displayed when Do not use legacy WorkPlace
two MNB application downloads Tech Tool to download an MNB
occur simultaneously device at the same time as
someone downloading the device
using WorkStation. If this situation

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 10 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

occurs, re-download the controller


using WorkStation.
32566 I/A Transition MNL-800 SNVTs are not all removed Manually remove the SNVTs.
when device type is changed from
MNL-800 to standard controller.
33384 I/A Transition When an AS is restored into PCT, an When updating a PCT from a live
MNL application will not open server containing WPT
applications, delete the
automation server in the PCT,
and then import the server instead
of restoring an existing server.
39214 I/A Transition After manually transitioning an MNL- After the first application
Vx controller to EBO and backing up download, perform a restore flow
its flow balance data, the flow balance data operation. The flow
balance data is overwritten in the balance data will not be
controller on application download. overwriten on subsequent
application downloads.
39235 I/A Transition MNB application fails to download Modify the MNB device’s
after a programming change with WorkPlace Tech application, so
service request denied error the 20th character of any object
name is not a space character.
This avoids a bug that is causing
service request denied errors.
40437 I/A Transition WebStation indicates invalid data Change the state from the current
when forcing a digital MNL I/O point. state to the state not desired and
back to the one that is to be
forced and save.
40614 I/A Transition When an S-Link point in an MNL Log onto the Automation Server
device is forced via a graphic while directly to force and view the
logged onto an ES, the word “Text” is point. The overridden state is
displayed in the graphic instead of displayed correctly when logged
the correct forced state of the point. onto the automation server.
40729 I/A Transition Launching EBO WorkPlace Tech Be sure to exit legacy WorkPlace
Editor with legacy WorkPlace Tech Tech Tool before attempting to
Tool open restarts PC. open an application in EBO
WorkPlace Tech Editor or
Monitor.
41112 I/A Transition Unable to Revert to WorkPlaceTech Manually enter the desired value
Application Value with MNB in WorkStation.
Controllers
41634 IP Controllers MPC: RPC: Download may fail on a Repeat uprev on failed
daisy chain network when a multi- controllers
stage uprev is required for
supplementary firmware file
download.
41689 IP Controllers If an image file containing the When using the bottom up deploy
Configuration Menu object is procedure, users should avoid
transferred to an IP Controller transferring image files containing
running version 1.xx firmware, the Configuration Menu object to IP
Configuration Menu will not be Controllers running 1.xx firmware
created and neither the eCommission versions
Tool nor the IP Controller will report
this incompatibility

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 11 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

40935 IP Controllers EBO: List of firmware packages is Select the Host Server in System
empty if Firmware folder is selected Tree and click Control Panel tab
in System Tree and then Firmware file
management link
35232 IP Controller MPX: In a multi-server environment, Import, assign and download
the list of available MPC firmware is firmware logged on either on top
not specific to any one server, this server OR directly on the child
can cause download failures server. Don’t mix and switch
between servers for different
operations.
Status log returned by import is
9886 Import/Export incorrect when multiple clients attempt -
simultaneous import/exports.
Uncheck unconfigured
22080 LonWorks/ Enabled but not configured NIC_IP in
NIC_IP_00X in L-Config and in WS
Xenta L-Config stops all interfaces in ES.
use Device discovery again.
Sometimes valid Lon Bindings are
Although the binding is indicated
25364 LonWorks/ indicated as faulty (Background
as faulty, it still can be saved.
Xenta Colour is red in Binding field) when
created.
26649 LonWorks/ Wrong data in the programming of the Contact Product Support Services
Xenta alias-tables. to get help to modify the XIF-file.
Selecting a MicroNet Schedule object
in WebStation causes an error to be Use the SFE graphic sub-object to
41632 MicroNet
displayed (Cannot read property of edit schedules in WebStation
'value' undefined).
EBO does not adjust the Application
Revision property value, when an
41689 Other -
image is created that includes a CAM
object
WorkStation - Do not see options
41043 such as Size, Move, Minimize,
Panels Alt + Space will display the menu
Maximize when the user clicks on the
title bar of the floating window
Full support for NaN, +infinity and -
infinity is not yet implemented. Use
NaN, +infinity or -infinity for
LonWorks network variables. For
It’s possible to set many numeric
26815 more information see WebHelp
Property grid properties to NaN, +infinity and -
topic “Not Active (NA) SNVT
infinity
Values For MNL LonWorks
Devices”. Use NaN for Value and
Priority array properties in I/A
Series MNB BACnet proxy objects.
Note: This is only an issue if the
41979 * Error compiling a WebService SOAP
Script script containing Web Services is
script program
edited and saved in 3.0.2.
DateTime value in program script
41384 editor debug window is not correct for
Script -
regional settings using the
Day/Month/Year format
35974 Search can take long time to finish if
Search -
properties are located in filed devices.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 12 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

To get the custom type name in


Custom types: Drag n drop instances
Search on the ES: see to that you
of custom types to search "Included
41166 Search have the custom type that you are
types" does not add the custom type
searching for in the library on the
name
ES.
When forcing an objects value in
41630 Sigma
Sigma via WebStation, the new value -
integration
is not displayed.
Trend log list does not auto refresh
41343 properly when user add records, edit
Trend Manually refresh after edit value.
records or clear the log with external
storage enabled on the server.
Changing visible log records in a Multi
Resize column and do other
41465 Trend Trend Log List will decrease the width
configuration change in the list and
(Multi list) size of all columns to the size of the
then click Save.
values width
There are two alternatives.
1. Run the backup prior to the
upgrade and deselect the backup
Upgrading the ES from 1.9.3.24 to
option when upgrading.
39059 Upgrade 2.0.2.59 with ES backup selected
2. Select the backup option when
resulted in a 'reboot' message.
upgrading but make sure the ES is
running before the upgrade
process is started.
Restore configuration in 1.9.3 and
37937 Upgrade ES upgrade failed from 1.9.3 to 2.0.1
run one more upgrade.
33408 Access the User group from the
Workspace Auto logoff field not displayed
Tree and the field is displayed
System tree is not visible in edit layout
26551 Add the Work Area before adding
Workspace mode for Workspaces until removed
the System tree
and added again
Graphic components not shown in Open graphic editor and add all
26908 WorkStation Graphic Editor after repair of WS components and categories
installation manually
Try to avoid very long lists of
objects, then filtering via ‘Quick
WorkStation crashed with
41687 WorkStation filter’, selecting multiple rows and
DataGridInternalException.
finally selection filtering via the
column header
Remember me disabled will not work
39211 WorkStation the first time if WorkStation already Log on one more time
have it set
Custom Type Library import: Warning
Recommend using the old normal
41028 when import 2.0 export files if the MPx
WorkStation instance import for 2.0 export files
contains objects with enumerated
properties
WorkStation: Objects in tree view
does not accept clicks if you had a Remove synchronization to parent
40861 WorkStation
content type for the Content type and delete the content type.
(Content type)
folder before adding it to a parent Enable synchronization again.
server.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 13 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

A List view with a Content Type


41650 WorkStation Requires a refresh to display the
Refresh the view once loaded.
(Content type) 'saved content type' with column sort
order changed from default

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 14 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

5. Important Engineering Information


There is no new important engineering information for this release, please refer to the EBO
3.0.1 release note section 6 for details of existing engineering information, however there is an
update to the graphic section 6.4 copied below for convenience with the additional text in italic.

6.4 Graphics Update


The JavaScript engine in the Graphics Editor and WorkStation was updated in release 1.8.
This has a number of advantages; bugs fixed, better performance, stronger compliance with
the JavaScript standard and better compatibility with the JavaScript engines that are used by
web browsers. The stronger compliance with the standard may result in compatibility issues
with JavaScript code written in older versions of EcoStruxure Building Operation. The old
version was sometimes more forgiving when running JavaScript’s that were not written
correctly.
To be able to open Graphis with unsecure content, you must turn on “Enable WebStation to
use unsafe string evaluated JavaScript methods like ‘eval’ ” in Security Settings.'

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 15 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

6. APPENDIX A – Supported upgrade Paths


6.1 Upgrade paths
Supported direct upgrade paths:

Upgrade releases
Installer From Version To Version
WorkStation, 1.7.2.xxxx 3.0.2
Enterprise Server,
Device administrator, 1.8.1.xxxx 3.0.2
Reports server 1.9.x.xxxx 3.0.2
Enterprise Central (EBO v2.0) 2.0.x.xxxx 3.0.2

6.2 Server upgrade options


The table below lists the supported server upgrade paths, the ES should be upgraded
before the AS/AS-P/AS-B:
From Version To Version Action on EBO server/database
1.7.2. xxxx 3.0.2.33 Full upgrade New firmware and database upgraded

1.8.1. xxxx 3.0.2.33 Full upgrade New firmware and database upgraded

1.9.x. xxxx 3.0.2.33 Full upgrade New firmware and database upgraded

2.0.x. xxxx 3.0.2.33 Full upgrade New firmware and database upgraded
3.0.1. xxxx 3.0.2.33 Hotfix upgrade New firmware, database not upgraded

Greenfield site* 3.0.2.33 Full Installer New firmware and new database
* For greenfield sites we recommend installing EBO 3.0.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 16 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

6.3 IP Controllers Shipped from the Factory


MP/RP controllers and IP-IO received from the factory may have a pre-release firmware
loaded, it is imperative that this firmware version is checked and upgraded to the latest
version for the EBO release being used as defined below.

Supported IP Controller Recommended build for


firmware releases new/replacement IP
controllers (MP, RP, IP-IO)
Release MP, IP-IO RP
SBO all Not supported Not supported Not supported
EBO
1.00.01/2/3/4 Not supported 2.00.02* (MP/IP-IO only)
2.0.1/2/3
1.00.01/2/3/4,
EBO 2.0.4** Not supported 2.00.02*
2.00.01* or later
EBO 3.0 2.00.01* or later 2.00.01 or later 2.00.02*

* Firmware 2.00.01 and later is deployed via the new universal firmware package.
** EBO 2.0.4 supports IP controllers with a mixture of 1.00.0x and 2.00.01/2 firmware.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 17 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

7. APPENDIX B – Installation
7.1 Installing v3.0.2 on a greenfield site
For installation of EcoStruxure Building Operation v3.0.2 WorkStation, Enterprise Server,
Enterprise Central or Report Server, please reference the Web Help at 3.0 for that topic.

7.2 Upgrading from an earlier release to v3.0.2


To ensure a smooth upgrade please refer to the v3.0.1 release note section 9.2 for details on
the process/procedures to upgrade a system that is running a release earlier than v3.0.

7.3 Upgrading from v3.0.1 to v3.0.2


Warning: Ensure a backup is available for all servers to be upgraded before proceeding.
7.3.1 Automation Server
Upgrade of the AS/AS-P/AS-B is performed using the Device Administrator (DA). Note: there
is a new DA for 3.0.2 that supports applying a new database, upgrading a database, applying
hotfix and getting backup set from device, eliminating the need for two different DA installers.

7.3.1.1 Device Administrator installation

Run the installer EBO.Device.Administrator v3.0.2.33 - EcoStruxure Building – Software.exe,


selecting the option to remove the existing version.

7.3.1.2 Upgrading an AS/AS-P/AS-B


Run the Device Administrator and select the AS/AS-P/AS-B to be upgraded and select the
upgrade button, you will be presented with the this menu.

Select Apply hotfix and you will be presented with the window as shown below.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 18 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

Select the OK button and you will be presented with a window to select the hotfix file.
Locate the hotfix file, i.e. AS-hotfix-3.0.2.33.exe. When the Open button is selected the AS
upgrade will begin immediately.
However if the file fails to load please check the PC has access to the internet as this is
required to validate the integrity of the file.

Note, the hotfix file is a self-extracting archive and will be extracted to the DA folder by DA.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 19 of 20 Company Confidential

© 2019 Schneider Electric, all rights reserved


[ Release Notes ] EcoStruxure™ Building Operation v3.0.2

When complete, logon to workstation and verify the running build is correct.

7.3.2 Enterprise Server


To apply the v3.0.2 maintenance release to an existing v3.0.1.xxxx Enterprise Server (ES) first
stop the ES service then run the installer EBO Enterprise Server Hotfix v3.0.2.33 -
EcoStruxure Building – Software.exe, note this is quick as the database is not upgraded.
Finally, check that the ES is running the new software build and verify the system is operating
as expected.

7.3.3 Enterprise Central


To apply the v3.0.2 maintenance release to an existing v3.0.x.xxxx Enterprise Central (EC)
first stop the EC service then run the installer EBO.Enterprise.Central Hotfix v3.0.2.33 -
EcoStruxure Building – Software.exe.
Finally, check that the EC is running the new software build and verify the system is operating
as expected.

7.3.4 WorkStation
To apply the v3.0.2 maintenance release to an existing v3.0.n.xxxx WorkStation, run the
installer EBO WorkStation Hotfix v3.0.2.33 - EcoStruxure Building - Software.exe.

7.3.5 License Administrator


To apply the v3.0.2 release to an existing v3.0.n.License Administrator installation, run the
installer EBO License.Administrator v3.0.2.33 - EcoStruxure Building - Software.exe (note;
there is no hotfix installer).

7.3.6 Reports Server


To apply the v3.0.2 release to an existing v3.0.n.xxxx Report Server installation, run the
installer EBO Reports Server v3.0.2.33 - EcoStruxure Building - Software.exe.

Schneider Electric
Andover North American R&D Center, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
www.schneider-electric.com
RN_EBO_v3.0.2 Rev B– July 2019 Page 20 of 20 Company Confidential