PROJECT : Warehouse Actual Values

LOCATION : PT KBS Need as per


LUMINAIRE : 100 as per selection for
POSITION : Cilegon banten Design Installation
1 Room Width W m 24.00
2 Room Length L m 168.00
3 Room Area Af L*W 4032.00 4032.00
4 Total Height Ht m 6.00
5 Suspension length Hs m 0.00
6 Mounting Height Hm Ht - Hs 6.00 6.00
L*W
7 Room Index Kr = 3.500 3.500
Hm(L+W)
8 Reflectance
Celing Rc 0.70
Walls Rw 0.50
Floor Rf 0.20
9 Number of light sources per lantern. n 1 1
10 Utilization Factor.
From Table
Kr1 1 UF1 0.51 UF2 - UF1 * Kr - Kr1
Kr 3.500 UF # UF =UF1+ 1.110 1.110
Kr2 1.25 UF2 0.57 Kr2 -Kr 1
11 Reduction Factor k 0.7 0.7
12 Depreciation Factor f 1.25 1.25
13 Type of Lamp D
14 Luminous Flux per Lamp O 12000 12000
15 Illumination Level E 100 100
E*Af*f
16 Calculation of Number Luminair N= 54.054
O * n *UF*K

L*N
17 Number of Luminair Along NL= 19.5
W
NL(Rounted Figure.) 20 20
W*N
18 Number of Luminair Across NW= 2.8
L
NW (Rounted Figure.) 3 3
19 Total Number of Luminairs Nt= NL*NW 60 60

1 Af
20 Uniformity S/Hm= 1.37 1.37
Hm Nt
Nt*O*n*UF*k
21 Maintained Average Illuminance Aave = 111 111
Af*f
Note: Average Illuminance as per selection = 111