00 - One Line-Diagram - Rev
00 - One Line-Diagram - Rev
DEVICE PDUS
WIRE LEGEND
QS DEVICES THAT SUPPLY PDU
Q QS CONTROL LINK (CONNECT WIRES 1, 2,
DIN RAIL POWER SUPPLY +75 3 AND 4)*
Q QS CONTROL LINK (CONNECT WIRES 1, 3
MYROOM DIN RAIL POWER SUPPLY +30 AND 4. DO NOT CONNECT WIRE 2)*
QS PLUG-IN POWER SUPPLY, QS J-BOX POWER
+8
NOTES ON WIRING SUPPLY P PANEL CONTROL LINK (CONNECT WIRES 1,
2, 3, 4 AND 5)*
ENERGI SAVR NODE WITH ECOSYSTEM, ENERGI
QS CONTROL LINK SAVR NODE WITH DALI, ENERGI SAVR NODE +30
THE QS CONTROL LINK HAS A FREE WIRING TOPOLOGY (DAISY CHAIN, T-TAP, ETC). THE SYSTEM WIRING WITH T-SERIES TUNABLE-WHITE PANEL CONTROL LINK (CONNECT WIRES 1,
P
ILLUSTRATED BY THIS DRAWING HAS BEEN LAID OUT TO ENSURE APPROPRIATE POWER TO EACH DEVICE. IF FOR ENERGI SAVR NODE FOR 0–10 V, ENERGI SAVR 2, 3 AND 4. DO NOT CONNECT WIRE #5)*
ANY REASON THE SYSTEM IS TO BE WIRED DIFFERENTLY THAN WHAT IS SHOWN, PLEASE CONFIRM ALL DEVICE NODE WITH SOFTSWITCH, ENERGI SAVR NODE
GRX-CESO-277PKG +14
GRX-CESO POWER REQUIREMENTS ARE MET (PLEASE REFER TO “QS LINK POWER REQUIREMENTS” FOR INDIVIDUAL DEVICE FOR 0–10 V (DIN RAIL), ENERGI SAVR NODE WITH
CCI 1 Floor 1\Sheet 1\ Devices - CCO P PANEL CONTROL LINK (CONNECT WIRES 1,
220V Daylight Package 003 POWER REQUIREMENTS). SOFTSWITCH (DIN RAIL)
3, 4 AND 5. DO NOT CONNECT WIRE #2)*
FOR QS CONTROL WIRE LENGTHS TOTALING LESS THAN 500 FT (153 M), USE LUTRON CABLE GRX-CBL-346S (4 1 A MYROOM DIN RAIL POWER MODULE
GRX-LC8 PP-DV
CONDUCTOR NON-PLENUM), OR GRX-PCBL-346S (4 CONDUCTOR PLENUM). OTHERWISE USE 2 #18 AWG (1.0 SQ MM) + SWITCHING, 1 A MYROOM DIN RAIL POWER +4 QS SIVOIA SHADE CONTROL LINK*
S
Feed** MODULE PHASE ADAPTIVE
2 #22 AWG (0.5 SQ MM) TWISTED AND SHIELDED OR EQUIVALENT (BELDEN #9461). FOR QS CONTROL WIRE LENGTHS
TOTALING UP TO 2,000 FT, USE GRX-CBL-46L (5 CONDUCTOR NON-PLENUM) OR GRX-PCBL-46L (5 CONDUCTOR ENERGI SAVR NODE WITH DALI (DIN RAIL),
+3 T BELDEN CABLE 1387LA(OR EQUIVALENT)
ENERGI SAVR NODE WITH ECOSYSTEM (DIN RAIL)
PLENUM). TOTAL QS CONTROL WIRE LENGTH MUST NOT EXCEED 2,000 FT (600 M).
ENERGI SAVR NODE PHASE ADAPTIVE (DIN RAIL),
Link 1 : QS QS MOTOR GROUP CONTROLLER (DIN RAIL), 0 NORMAL INPUT POWER 2 #12 AWG (4 SQ
Q (7 QS Devices) ECOSYSTEM BUS/LOOP* HOMEWORKS QS DIN RAIL POWER MODULES MM) + GROUND
THIS IS A TOPOLOGY-FREE AND POLARITY-FREE WIRING (DAISY-CHAIN, T-TAP, HOME-RUN ETC.). KEEP ALL THE
GRAFIK EYE QS (ALL MODELS EXCEPT GRAFIK NORMAL-EMERGENCY INPUT POWER 2
Q
Link 2 : QS DRIVERS/MODULES IN ONE ROOM ON THE SAME LOOP WHENEVER POSSIBLE. ECOSYSTEM LOOPS ARE SHOWN ON +3
EYE QS DALI WITH KNX), QS TIMECLOCK #12 AWG (4 SQ MM) + GROUND
THE LIGHTING PLANS. IF THERE IS A DISCREPANCY, AND IF ROOMS ARE WIRED ON A DIFFERENT LOOP THAN THE
LINK A : 0
ONE SHOWN, LUTRON NEEDS TO BE NOTIFIED AS THIS INFORMATION IS IMPORTANT FOR PROGRAMMING THE QP2 QUANTUM LIGHTING HUB LINKS B,C,D :
ALP6C-FT-4F1U-1N1C-L SYSTEM. +33 EACH 3 PHASE 4 WIRE INPUT POWER, 4 #12
Floor 1\Sheet 1\ Devices QSWE-10BRLN-AW-NST
Floor 1\Sheet 1\ Devices - Control Station 003 USE LUTRON CABLE C-CBL-216-GR1 (2 #16 CONDUCTOR NON-PLENUM) OR C-PCBL-216-CL-1 (2 #16 CONDUCTOR
3
Athena DIN Rail Panel 3 LINKS A,B : AWG (4 SQ MM) + GROUND
Athena DIN Rail Panel (1613mm H, International seeTouch QS Wallstation Non Insert 10 QP3 QUANTUM LIGHTING HUB
Button with Raise/Lower
PLENUM RATED). OTHERWISE USE 2 #16 AWG (1.5 SQ MM) BY OTHERS. +33 EACH
467mm W, 108mm D): 220 V-240 V,
feed-through. Scenes 1-9 + Off with Scene Raise/Lower LOOP LENGTH IS LIMITED BY THE WIRE GAUGE USED FOR E1 AND E2 AS FOLLOWS: LINKS
Includes 4 Switching modules, 1 DALI 1 gang backbox
TWO PROCESSOR LIGHTING HUB (QP5) 2 #12 AWG (4 SQ MM) + GROUND
A,B,C,D : +33
module, 1 Processor, 1 QSE-IO and 1
link power supply. EACH
SINGLE PROCESSOR LIGHTING HUB (QP5), 2-LINK LINKS A,B :
PROCESSOR (QP-2L) +33 EACH
3 #12 AWG (4 SQ MM) + GROUND
1-LINK PROCESSOR LIGHTING HUB (QP6), 1-LINK
LINKS A : +33
PROCESSOR LIGHTING HUB (QP5), 1-LINK 0-10 V SIGNAL: 2#18AWG (1.0 SQ MM)
EACH
PROCESSOR (QP-1L)
LCP 3 2#18 AWG (1.0 SQ MM)
QS DEVICES THAT CONSUME PDU
WIRE GAUGE MAX LOOP LENGTH QS WALLSTATION (SEETOUCH, ARCHITRAVE, 3#18 AWG (1.0 SQ MM)
SIGNATURE SERIES, QS PICO, KEYSWITCH,
#18 AWG (1.0 SQ MM) 550 FT (167M)
SINGLE COLUMN PALLADIOM), QS SLIDER, -1 ECOSYSTEM BUS/LOOP*
#16 AWG (1.5 SQ MM) 900 FT (274M) GRAFIK T SLIDER, QS INFRARED (IR) EYE,
#14 AWG (2.5 SQ MM) 1,400 FT (426 M) WALLBOX INPUT CLOSURE INTERFACE
#12 AWG (4 SQ MM) 2,200 FT (670M) QS NETWORK INTERFACE, QS DMX INTERFACE, DALI LOOP
ENERGI SAVR NODE PROGRAMMING INTERFACE, -2
QS WALLSTATION (DOUBLE COLUMN PALLADIOM)
T T-SERIES TUNABLE-WHITE LOOP
PREVENTATIVE VISIT TO PERFORM PREVENTATIVE MAINTENANCE, MINOR REPROGRAMMING, AND CONDUCT SYSTEM TRAINING. THE LUTRON SERVICE REPRESENTATIVE WILL REVIEW SERVICE
ALP3C-FT-3F1U-1N1C-L MAINTENANCE VISIT OPTIONS WITH THE END-USER PRIOR TO BEGINNING ANY WORK. THE END-USER WILL RECEIVE DOCUMENTATION THAT DESCRIBES THE WORK PERFORMED AND ANY
Floor 1\Sheet 1\ Devices QSWE-10BRLN-AW-NST (LSC-SCHD-MAINT) RECOMMENDATIONS FOR FUTURE SERVICE. QUANTITY DICTATES THE NUMBER OF DAYS PURCHASED.
Athena DIN Rail Panel 1 Floor 1\Sheet 1\ Devices - Control Station 001
Athena DIN Rail Panel (921mm H, International seeTouch QS Wallstation Non Insert 10 ADDITIONAL DAY OF ONSITE DAY OF SERVICE BY A LUTRON SERVICE REPRESENTATIVE.
467mm W, 108mm D): 220 V-240 V, Button with Raise/Lower SERVICE
feed-through. Scenes 1-9 + Off with Scene Raise/Lower
1 gang backbox
(LSC-DAY-ADDL-CS)
Includes 3 Switching modules, 1 DALI
module, 1 Processor, 1 QSE-IO and 1 REMOTE SUPPLEMENTAL A SUPPLEMENTAL REMOTE TRAINING FOR SITE PERSONNEL. THIS SERVICE IS AVAILABLE FOR LUTRON QUANTUM AND ATHENA SYSTEMS. THIS TRAINING IS NOT TO EXCEED 4
link power supply.
TRAINING HOURS. REMOTE NETWORK ACCESS IS REQUIRED FOR THIS VISIT AND THE SYSTEM MUST BE ABLE TO CONNECT TO THE INTERNET.
(LSC-TRAIN-RMTE)
REMOTE PROGRAMMING ONE 4-HOUR REMOTE PROGRAMMING ASSISTANCE SESSION TO MAKE PROGRAMMING ADJUSTMENTS PER THE DIRECTION OF A FACILITY MANAGER OR SPECIFIER. THIS SERVICE
ASSISTANCE IS AVAILABLE FOR LUTRON QUANTUM AND ATHENA SYSTEMS. REMOTE NETWORK ACCESS IS REQUIRED FOR THIS VISIT AND THE SYSTEM MUST BE ABLE TO CONNECT TO THE
(LSC-PRG-AST-RMTE) INTERNET.