Sound Research Test Certificate No: 7753a

Laboratories
Holbrook House, Little Waldingfield Contract: C/22485
Sudbury, Suffolk CO10 0TH
Page 1 of 1
Tel: +44(0)1787 247595
Date: 06 June 2013
e-mail: srl@srltsl.com

Confidential

See SRL Report C/22485/T07 for full details


Laboratory Measurement of the Flanking Transmission of Airborne Sound between Adjoining Rooms
of a Suspended Ceiling to BS EN ISO 10848-2:2006

Test Numbers: 39 & 40 Air Temperature: 14.1 °C


Manufacturer: Armstrong Air Humidity: 56 %
Client: Armstrong Test Date: 18/04/2013
Sample mounted by: Armstrong
Product identification: Plain & Bioguard Plain 600x600x15mm

70

Dn,f
Suspended Ceiling
Freq Normalised Flanking BS EN ISO 717-1
Level Difference - dB reference curve

f 1/3 Oct 1/1 Oct 60


Hz Dn,f
50+ 9.9
Suspended Ceiling Normalised Flanking Level Difference, Dn,f dB

63+ 11.8 10.8


80+ 10.9 50
100 10.0
125 20.7 14.2
160 24.1
200 26.7
250 27.1 27.3 40
315 28.2
400 28.2
500 30.4 30.1
630 32.8 30
800 34.3
1000 36.9 36.3
1250 39.1
1600 40.9
2000 42.5 42.1 20
2500 43.4
3150 44.0
4000+ 44.3 42.4
5000+ 40.2 10
6300+ 42.0
8000+ 45.8 44.4
10000+ 47.2
Average
100-3150 31.8 0
100 160 250 400 630 1000 1600 2500
125 200 315 500 800 1250 2000 3150
Frequency, Hz
v1.4
Rating according to BS EN ISO 717-1:1997 Notes : * shows measurement corrected for background
Dn,f,w (C;Ctr)= 35 (-2;-7) + shows frequency beyond standard and not UKAS accredited

............................................ ..................................
Allen Smalls Tom Gardner
Quality Manager Head of Testing