Pesquisa de Tecnologia para Sistema de Controle Flexível de Impedância de Aterramento de Ponto Neutro para Redes de Distribuição
Pesquisa de Tecnologia para Sistema de Controle Flexível de Impedância de Aterramento de Ponto Neutro para Redes de Distribuição
Yi Wentao
Li Sukang
power dispatching center
power dispatching center
Nanchang Power Supply Company
Nanchang Power Supply Company
Nanchang, Jiangxi, China Nanchang, Jiangxi, China
yafeifei@163.com
Abstract—As the power network appeared fault, the residual It only can compensate a partial capacitive current by
fault-current can be controlled under the allowed range by using using traditional Petersen-coil. A very small residual current
the traditional Petersen-coil to compensate the most part of can also threaten coal mine safety. To further enhance
capacitive current. Although the small residual fault-current can security operation index and further reduce the residual
also cause gas explosion in mining power supply system with
current, a novel control technology for the neutral-point
high reliability. A novel control technology of neutral-point
ground impedance is presented in the thesis by controlling the ground impedance is now proposed. MATLAB simulation
duty cycle of power electronics IGBT, The ground impedance have been carried out to verify the validity of the method.
control systems are with reactor continue changing, excellent
dynamic responding, high control precision and the residual II. NOVEL EQUIVALENT IMPEDANCE CONTROL
fault-current approaching zero, it can reduce the accident TECHNOLOGY BASED ON IBGT
probability. Theoretical derivation and MATLAB simulation A. IGBT Control Circuit Design
results show that the proposed method is with high precision,
high speed and noiselessness. It can improve distribution
automation, accelerate grounding fault arc self-extinguishing,
and enhance power quality.
I. INTRODUCTION
With the power systems expansion, mining power supply
system as a special branch, it has developed rapidly. At Figure 1. Equivalent impedance control circuit based on IBGT
present, most chinese mining power systems are of 6kV power
apply, and few newly established mining power systems adopt The proposed equivalent impedance control circuit based
10kV[1]. They have been operated with neutral point on IBGT is shown in Figure 1. In the figure,VT1,VT2 are the
non-direct grounded. The single-phase earth fault is a main two inverse parallel IGBT,R and L are the load of control
factor that influence the mining power systems security. circuit[3,6], so the impedance angle is:
According to data statistics, The single-phase earth faults are
about 60 percent of whole electric faults[2]. Under the ϕ = arctan(ωL / R ) (1)
scurviness condition in coal mine that contains flammable and
explosive gas, when the single-phase earth fault happened, it Where ω is angular frequency. The load current is sine wave
can cause explosion by voltaic sparkle and insulation in steady-state by the ways of short circuit IBGT, and the
breakdown by grounding over voltage. In recent years, it has current angle lagging behind supply voltage(u1) is φ. Setting α,
occurred gas explosion accident frequently in mining power Δ are the firing angle and the duty cycle of IGBT respectively.
supply systems caused by electric fault. Bringing greatly Therefore, it can adjust output voltage(u2) by controlling duty
influence to the coal industry. In order to ensure safety, cycle(Δ) of IGBT(VT1,VT2) in the positive half cycle and
according to the coal safety standard 457, the residual current negative half cycle of supply voltage(u1) respectively. When
caused by single-phase earth fault is needed to be limited in α=0 in the positive half cycle, setting ti's the voltage cross-zero
about 20 amperes in the mining power systems. point. So the phase shift range of α is between φ and π (φ≤α
2U 1 ⎡ α −ωt
⎤ From the three equations (5)-(7), one can derive the following
i0 = ⎢ sin (ωt − ϕ ) − sin (α − ϕ )e tan ϕ
⎥ three equations:
Z ⎣⎢ ⎦⎥
U1
I VT = θ − sin θ (8)
α ≤ ωt ≤ α + θ (3) 2π Z
θ
Δ= (11)
2π
From the two equations (10)-(11),it can be derived:
U1 πZ
Z' = = (12)
I0 2πΔ − sin 2πΔ
1
Where, 0<Δ< ,therefore, the neutral point grounding
Figure 2. The curve of α andθ 2
equivalent impedance that we needed can be obtained by
Froming the curves above,it can be found that when α≤φ,θ controlling duty cycle(Δ) of IGBT based on PWM signal. The
=180 ,when α>φ, θ<180 . Setting I VT , I 0 are current rms
。 。 shift range of impedance is: Z ≤ Z' ≤ ∞.
value of IGBT and current rms value of load respectively. The B. Selecting the Trigger Signal of IGBT
following equations can be obtained:
A couple of trigger signals of IGBT in Figure 1 must be
isolated, otherwise, it's able to cause IBGT short-circuit by
⎧ α−ωt 2 ⎫
1 α+θ ⎪ 2U1 ⎡ ⎤⎪ connecting the two cathodes of VT1 and VT2. Selecting trigger
( ) ( ) ⎥ ⎬d(ωt )
2π ∫α ⎪ Z ⎣⎢
tanϕ
IVT = ⎨ ⎢sin ωt −ϕ − sin α −ϕ e signals of IGBT with high precision are the key of flexible
⎩ ⎦⎥ ⎪⎭ controlling equivalent impedance values[7-10].
It's usually adopts high frequency carrier signals in
U1 sinθ cos(2α +ϕ +θ ) experiment, the high frequency carrier signals are series of
= θ− narrow pulse. The turn-on time of VT1 is : α < ωt < π ,and
2π Z cosϕ the turn-on time of VT2 is : α + π < ωt < 2π ,the
frequency of narrow pulse is between 20000Hz and 30000Hz.
(5)
1217
III. MATLAB SIMULATION
Carrier Frequency of
Duty cycle(Δ) Voltage peak Load inductance Voltage Frequency
PWM
25% 100V 0.01H 23kHz 50Hz
The pulse signal 1 is superposition with controlling signal Figure 5. The controlling signal “1b”
“1a” and controlling signal “1b”, “1a” and “1b” is shown in
Figure 4, Figure 5. The pulse signal 2 is superposition with
controlling signal “2a” and controlling signal “2b”, “2a” and
“2b” is shown in Figure 6, Figure 7. The load current
waveform can be obtained by controlling pulse signal 1 and
pulse signal 2 that triggering flow IGBT1 and IBGT2
respectively. The load current waveform is shown in Figure 8.
1218
the three-phase capacitance to earth and calculates the
capacitive current that converts two control signals by PI
regulator and control signal conversion circuit. The control
signals contain PWM trigger signal of IGBT and tuning signal
of Petersen-coil( l ) that are transmitted to IGBT control
module and Petersen-coil tuning circuit respectively. When
the single phase grounding fault occurring, the measurement
device stop measuring, switch(K) is closed instantly,
Petersen-coil and adjustable reactor that are well controlled
start operating in power network. Consequently, the
capacitive current can be compensated with high precision. It
Figure 8. The load current waveform can limit the residual fault-current approaching zero and
improve personnel safety especially in mining power supply
From the equation(9), (11) and TABLEⅠ, load current system. When the grounding fault disappearing, switch(K)
rms value can be calculated as: break off automatically, the Petersen-coil and adjustable
reactor exit operating. At the same time,the cutoff signal is
sent to IGBT control module by measurement device which
U1 100 π
I0 = 2πΔ − sin 2πΔ = − 1 = 9.594( A) continue to work.
πZ π 2π 2
(13)
1219
being compensated by Petersen-coil is shown in Figure 11, the high control precision and the residual fault-current
waveform of fault current that is compensated by Petersen-coil approaching zero. It fits to apply in mining power supply
is shown in Figure 12. system with high reliability.
REFERENCES
[1] ZOU.Shiming, ZHANG. Genxian, and LIU. Shidong,“The Technol
ogy of Current Leakage for Industrial and Mining,” BeiJing:Coal I
ndustry Publishing House,2004,pp.160–189.
[2] YU.Qun, LIU.Xingbang, and CAO.Na, “The Protection of High V
oltage Current Leakage for Industrial and Mining Based on Curren
t Compensation,” Coal Mine Electromechanical, 2004,pp.31-33.
[3] CHENG.Lun,CHEN.Yu,“Novel Arc-suppression Coil Based on The
ory of Transformer with Controllable Load,” Automation of Electri
c Power Systems,vol. 30, pp.77–81,2006.
[4] CHEN.Jian,“Power Electronics-The Transformation and Controlling
Technology of Power Electronics,” BeiJing: High Education Publis
Figure 10. The fault-phase voltage waveform of pre and post fault hing House,2002.
[5] MO.Zhengkang,QIAN.Xinyu,andWANG.Nan,“Application Technolog
y of Power Electronics,”BeiJing:Machinery Industry Publishing Ho
use,2000.
[6] CHA.Shensen,ZHENG.Jianyong,SU.Lin,“Research on Current Balanc
ing of Parallel IGBT,”Electric Power Automation Equipement,vol.2
5, pp.32–34,2005.
[7] HE.Pengcheng,“New Type of Petersen Coil Based on Magnetic-Flu
x Controllable,”Hua Zhong University of Science & Technology,M
aster Degree Thesis,2004.
[8] LI.Hongda,ZHU.Dongbo,LIU.Ji,“The Continuously Adjustable Induct
ance Circuit Design Based on PWM,”Power System Technology,vo
l.30(Supplement), pp.268–270,2006.
[9] LIU.Ji,ZHU.Dongqin,“Stepless and Passive Inductance Change Usin
g IGBT,” Journal Ha Er Bin Univ.Sci.&Tech,vol.9, pp.50-53,2004.
[10] WU.Tao,“The Research and Design on IGBT,” Zhe Jiang Universi
Figure 11. The waveform of fault current that without being compensated ty,Master Degree Thesis,2005.
by Petersen-coil [11] ZENG.Xiangjun,YI.Wentao,LIU.Zhanglei,“Novel Technique of Capa
citive Current Resonance Measurement with Signal Injecting for D
istribution Networks,”Automation of Electric Power Systems,vol.32,
pp.77-80,2008.
1220