Utility Building : DDC 7@ Groung Floor

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT: REF.: REV.

DATE ENG
OUTPUT INPUT
List Title:
DO AO AI DI

TRIP, FAULT / NORMAL


RUN / STOP ‐ ON / OFF
START/STOP ‐ ON/OFF

Co2, TEMPERATURE &

OPEN / CLOSE STATUS

SMOKE / FIRE ALARM


DIRTY / CLEAN FILTER
SPEED COMMAND

PRESSURE STATUS
FEEDBACK SIGNAL

GENERAL STATUS

GENERAL ALARM
TEMPERATURE &

AUTO / MANUAL
TEMPERATURE
MODULATING

FLOW STATUS
OPEN / CLOSE
COMMAND

COMMAND

COMMAND

HUMIDITY
HUMIDITY

HUMIDITY
PRESSURE

STATUS

STATUS
STATUS

STATUS
Utility Building ‐ 

DDC‐7@ Groung floor

NO. DESCRIPTION QTY ENABLE 0‐10VDC N1KΩ 0‐10VDC STATUS (VFC) FIELD DEVICES NOTES

A Exhuast Fans 11
1 Exhaust Fan Motor 11

2 Air Flow Switch 11

B Temp. Sensor 1
1 Temp. Sensor Reading 1

C Water Leak Detector 3


1 Water Leak Detector 3

D FACP 1
1 FACP 1

2 Software Integration 1 Software Integration Through BACnet/IP

E DGP_CPM Chiller 1
1 DGP_CPM Chiller 1 Fully Integrated to BMS System through BACnet/MSTP Protocol

F MODULAR CONTROLLER 1
1 MDP Power Meters, RMU 16

G Transformers 8
1 Transformer General Alarm 8

2 Transformer General Status 8

3 Transformer Stage # 1 Temp. Alarm 8

4 Transformer Stage # 2 Temp. Alarm 8

1 Software Integration 8 Fully Integrated to BMS System through Mod‐Bus Protocol

MODULAR CONTROLLER
SPARE POINTS
TOTAL # OF I/O DATA POINTS
(20%)
POINTS SUMM
ARY
MODULE SUM
MARY
MOD
ULE T