Engine Data
Engine model…….…………………………………………………..………………...….…. 6CTA8.3-D(M)
Cylinders/Configuration……...………………………………….. ……………………...…. 6/Inline
Displacement………….....……………………………….……………...………..litres [in³] 8.3 [506]
Aspiration………………………………………………………………… ……………….…… Turbocharged/Aftercooled
Exhaust type……………………………………………………………… ………………...… Wet
Engine speed……………………………………………………… ………………...….rpm 1500
Alternator Data
Alternator model………………………………………………………..……………….…… Newage Stamford UCM274H
Protection………………………………………………………………… ……………….…… IP23
Connection……………………………………………………………… ………………...… 3 phase 4 wire
Rated Power Factor…………………………………………………………………….…… 0.8
Temperature Rise Class…………………………………………………
………………...… F
Insulation Class…………………………………………………………………………...…. H
Frequency………………………………………………………….……………..……….Hz 50
Fuel System
Fuel consumption @ 100% Prime Power…………………..………………...l/hr [gal/hr] 41.3 [10.91]
Exhaust System
Exhaust gas flow…………………………………………..……………………..l/sec [cfm] 420 [889.9]
Exhaust gas turbine outlet temperature…………………..………………………..ºC [ºF] 448 [838.4]
Heat rejection to exhaust……………………..……………………………...kW [Btu/min] 103 [5861.4]
Maximum exhaust gas back pressure…………………………………….mm Hg [in Hg] 76.0 [3.0]
Ventilation System
Combustion air flow…….………………………………………………………..l/sec [cfm] 163 [345]
Alternator cooling air flow………….……………………………. ……………..l/sec [cfm] 514 [1089]
Engine casing heat rejection…….………………………….. ……………...kW [Btu/min] 16 [911]
Alternator heat rejection………….………………………….. ……………...kW [Btu/min] 10 [569]
Cooling System
Heat exchanger sea water flow (@ 10 psi pump pressure) ………..…..l/min [gal/min] 136 [36]
Heat exchanger expansion tank pressure cap rating……….………………....kPa [psi] 103 [15]
Main Cooler
Main coolant flow to heat exchanger……………………………….……..l/min [gal/min] 170 [45]
Main coolant flow to keel cooler (@ 5 psi external friction head) ….…..l/min [gal/min] 170 [45]
Main coolant thermostat start open temperature…….. .........…................…….°C [°F] 82 [180]
Main coolant thermostat full open temperature………...........…................…….°C [°F] 95 [203]
Heat rejection to main cooling system………………. ..............................kW [Btu/min] 139 [7910]
Rating Conditions: Ratings are in accordance with ISO 3046 reference conditions; air pressure at 100 kPa (29.61 in Hg), air
temperature 25°C (77°F), and 30% relative humidity. The fuel consumption data is based on No. 2 diesel fuel weight at 0.85 kg/liter
(7.1 lb/U.S. gal).
Prime Power Rating is applicable for supplying continual electrical power at varied load, conforming to ISO 8525 guidelines. The
following are the Prime Rating parameters:
* Prime Power is available for an unlimited number of hours per year in a variable load application. Variable load should not exceed a
70% average of the Prime Power rating during any operating period of 250 hours.
* The total operating time at 100% Prime Power shall not exceed 500 hours per year.
* There is a 10% overload capability for a period of 1 hour within a 12 hour period of operation. Total operating time at 10% overload
shall not exceed 25 hours per year.
Note.
1. All data is at Prime Power rated conditions.
2. Heat rejection to coolant values are based on 50%water/50% ethylene glycol mix and do NOT include fouling factors. If sourcing
you own cooler, a service fouling factor should be applied according to the cooler manufacturer’s recommendation.
3. All data is subject to a +/- 3% tolerance.