NEW SOLUTIONS

re ventilation
systems

FIRE DAMPERS
SMOKE EXHAUST FANS
JET FAN SYSTEMS
OVERPRESSURE SYSTEMS
CONTROL SYSTEMS
fire protection devices

examples of application

mcr WIP mcr PL 1 mcr FS mcr MONSUN mcr PASAT mcr FID S mcr FID C

mcr PL 1 mcr MONSUN C mcr DOR mcr OMEGA mcr ZIPP mcr FID PRO
fire dampers and smoke exhaust dampers

mcr FID PRO mcr FID S mcr FID C


single-blade cut-off fire single-blade cut-off fire damper and single-blade cut-off damper
damper and damper damper for fire ventilation systems CE - according to EN 15650:2010
for fire ventilation systems CE - according to EN 15650:2010
CE - according to EN 15650:2010 CE - according to EN 12101-8:2011

Fire resistance Fire resistance Fire resistance


EI 120 (ve ho i<–>o)S EI 120 (ve ho i<–>o)S EI 120 (ve ho i<–>o)S/ E 120 (ve ho i<–>o)S
EI 120 (Vew-i<–>o)S1000C 300AAmulti

Versions Versions Versions


S – cut-off fire damper S – cut-off fire damper S – cut-off fire damper
V – for fire ventilation systems (smoke exhaust)

Purpose Purpose Purpose


The damper has been designed for use in The damper has been designed for separating The damper has been designed for use in
general ventilation systems (intake and fire-hazardous zones from safe parts of the general ventilation systems (intake and
exhaust types), at passages through space building (S version) and assuring appropriate exhaust types), at passages through space
dividing elements – walls and floors. evacuation conditions through fire ventilation dividing elements – walls and floors.
(V version) – intake and exhaust damper.

Control – release Control – release Control – release


Thermal fuse mechanism – activated by a return Thermal fuse mechanism – activated by a return Thermal fuse mechanism – activated by a return
spring with fusible link rated at e.g. 72°C, spring with fusible link rated at e.g. 72°C, spring with fusible link rated at e.g. 72°C,
manual re-arming by means of a lever as an manual re-arming by means of a lever as an manual re-arming by means of a lever as an
option. option. option.
Electrical actuator – activated by Electrical actuator – activated by Electrical actuator – activated by
a thermocouple rated at e.g. 72°C or remotely, a thermocouple rated at e.g. 72°C or remotely, a thermocouple rated at e.g. 72°C or remotely,
by supply power decay (power break), by supply power decay (power break), by supply power decay (power break),
remote reset by supplying power remote reset by supplying power remote reset by supplying power
(Vn= 24V AC/DC or 230V AC). (Vn= 24V AC/DC or 230V AC). (Vn= 24V AC/DC or 230V AC).
Electrical actuator – activated remotely, by KW1 mechanism – activated by a return
supplying power (pulse), remote reset by spring with fusible link rated at e.g. 72°C or
resupply of power remotely by an electromagnet (pulse or power
(Vn= 24V AC/DC or 230V AC). break), reset by means of a lever or additional
actuator (Vn= 24V DC or 230V AC).

Dimensions (to the accuracy of 1 mm): Dimensions (to the accuracy of 1 mm): Dimensions (to the accuracy of 1 mm):
– round damper: diameter 100-200 mm, – rectangular damper with insulating – rectangular damper:
– sleeve, nipple or flange type of execution. separator, in a casing: width 200–800 mm; height 200–400 mm;
width 200–1500 mm; height 200–1500 mm; casing length 296 mm
casing length 296 mm,
– round damper with insulating separator,
in a casing: diameter 125-630 mm;
casing length 296 mm.
fire dampers and smoke exhaust dampers

mcr WIP mcr DOR mcr FS


louver damper, cut-off type and door-type smoke exhaust and louver transfer damper
for fire ventilation systems air-intake damper CE - according to EN 15650:2010

Fire resistance Fire resistance Fire resistance


EIS 60, EIS 60 AA, E 120, ES 120 – depending EIS 120 AA E 120
on method of manufacturing, as well as
method and place of installation

Versions Versions Versions


S – cut-off fire damper V – for fire ventilation systems (smoke exhaust) 101 – curtain partially in air stream
V – for fire ventilation systems (smoke exhaust) D1 – single-leaf damper 201 – curtain outside of air stream
M – double-function for combined systems D2 – double-leaf damper 301 – curtain outside of air stream
T – transfer damper (round damper)

Range of application Range of application Range of application


The damper has been designed for separating The damper has been designed for use in fire The damper is intended for unducted
fire-hazardous zones from safe parts of the ventilation ducts as outlet damper (smoke mounting, in partitions – as a transfer
building (S version) and assuring appropriate exhaust) and as inlet damper for evacuation damper for transmission of air between
evacuation conditions through fire ventilation needs (intake of fresh air). rooms.
(V version) – intake and exhaust damper.
It can be also used in so-called combined
systems (M version), as a transfer damper
(T version) and at the end of ventilation ducts.

Control – release Control – release Control – release


Thermal fuse mechanism – activated by a return EM 24 D mechanism – remotely activated by Spring mechanism – activated by a return
spring with fusible link rated at e.g. 72°C, an electromagnet (pulse supply Vn= 24V AC/DC), spring with fusible link rated at e.g. 72°C,
manual re-arming by means of a lever as an manual reset. manual reset.
option. By implementing an intermediary module MP Electromagnetic release – activated by
Electrical actuator – activated by a 230/24 damper can be released by 230 AC/DC a thermo element (e.g. 72°C) or remotely,
thermocouple rated at e.g. 72°C or remotely, voltage. by lack of supplying power
by supply power decay (power break), remote (power break Vn= 24V AC/DC or 230V AC),
reset by supplying power manual reset.
(Vn= 24V AC/DC or 230V AC).
Electrical actuator – activated remotely, by
supplying power (pulse), remote reset by
resupply of power
(Vn= 24V AC/DC or 230V AC).
KW1 mechanism – activated by a return
spring with fusible link rated at e.g. 72°C or
remotely by an electromagnet (pulse or power
break), reset by means of a lever or additional
actuator (Vn= 24V DC or 230V AC).
fire protection devices

mcr MONSUN smoke mcrexhaust


PASAT mcr ZIPP
axial smoke exhaust fan roof fan cut-off fire valve
CE - according to EN 12101-3 CE – according to EN 12101-3 CE – according to EN 1366-2
(coming soon)

Fire resistance* Fire resistance Fire resistance


F400 – 400°C for 120 min. F400 – 400°C for 120 min. EIS 120
F300 – 300°C for 60 min.
F200 – 200°C for 120 min.

Versions Versions Versions


Long casings (LC). Single or double speed motors. - vertically mounted
Single or double speed motors. - horizontally mounted

Purpose Purpose Purpose


The fan has been designed to remove smoke The fan has been designed to remove smoke The valve has been designed for assembly
and hot air from enclosed interiors during and hot air from enclosed interiors during at the end of ventilation ducts and is used
fire. It facilitates evacuation of people and fire. It facilitates evacuation of people, for separating fire-hazardous zones from safe
protects the building structure and its fittings it also prevents the fire spreading to the parts of the building as well as for transferring
against high temperature, it also prevents neighbouring fire compartments. The fan may air through building partitions.
the fire spreading to the neighbouring fire be used in comfort ventilation systems.
compartments. The fan may be used in
comfort and industrial ventilation systems as
an exhaust or venting fan.

Technical data Technical data Technical data


Available in 10 sizes: Available in 6 sizes: Available in 4 sizes:
from D 355 mm to D 1 000 mm. from D315 mm to D710 mm. D100 mm, D125 mm, D160 mm, D200 mm.
Standard air output up to 100 000 m3/h. Standard air output up to 52 000 m3/h.
Compression of up to 1 800 Pa. Compression of up to 2 000 Pa.

Accessories Accessories Control – release


- mounting feet for horizontal installation SW - back draft dampers for duct connection Thermal fuse mechanism – activated by a return
- protective wire fan guard on rotor or motor KS & KS-V spring with fusible link rated at e.g. 72°C,
side SO - round flexible connectors KD manual re-arming by means of a lever as an
- vibration compensators – flexible connectors - roof bases for flat or slope roofs PD option.
KD, F400 class - noise reduction roof bases with silencer PD-T EMz mechanism – activated by a return spring
- counterflanges for duct installation PK - service circuit breakers WS with fusible link rated at e.g. 72°C or remotely
- back draft dampers KS and KS-V by an electromagnet (pulse and power break
- shock absorbers AM (F400) and BM Vn= 24V DC or 230V AC), manual reset.
- control automatics OM
- silencers TH
- service circuit breakers WS
- vertical mounted brackets PP
- air deflectors KP
- suction nozzles with grill DS
- outlet stub with grill WO

*/ fans without a fire resitance rating (BO type)


are available on an individual basis.
smoke protection devices

overpressure smoke prevention system for vertical escape routes mcr EXi

To provide more safety to building users, an overpressure smo-


ke prevention system for vertical escape routes mcr EXi is in-
stalled in staircases. The system consists of suitably designed sets
of equipment which co-operate in inducing overpressure to pre-
vent smoke from getting to the protected zone. The system opera-
tion is controlled by certified mcr Omega control unit.
The overpressure system mcr EXi is actuated by emergency smoke
exhaust button or by external triggering devices (e.g. by signal
from FACV – fire alarm control unit).
As the signal of fire signalling system occurs in the building, the
properly adjusted intake units get activated: GZN (upper intake
system) and/or DZN (lower intake system), located in certain
places of the staircase. Within a few seconds, the staircase is filled
with air and differential pressure between the staircase and the
corridor develops. The overpressure in the staircase is of 20-80 Pa,
which guarantees the force necessary to open evacuation door is
not higher than 100 N. As the door is open, excessive air in the
staircase prevents smoke from getting to the escape route. The air
reaches required flow rate if exhaust is provided from each floor at
which ventilator is installed. Recommended area of the hole should
equal at least 0.3 m2 (air may be exhausted e.g. through the win-
dow smoke exhaust system mcr-OSO or through dedicated pres-
sure relief-smoke exhaust channels with fire dampers mcr FID or
mcr WIP).
Pressure is controlled automatically by the system of correctly ar-
ranged pressure relief units such as GZU (upper pressure relief
unit) and/or DZU (lower pressure relief unit).

smoke detector

8 7 9
smoke exhaust
alarm button
8
1 RS485/RS232

system of graphic supervision


fire alarm

graphic supervision station


3
communication with the

FACU

alarm monitoring correctness of


station

2 fire algorithm

power supply: 400V/230V AC


fire alarm
signalling

implementation

system failure

fire alarm

2 mcr OMEGA

CONTROL UNIT
7
3
power supply and control

power supply
and control
power supply

2
monitoring

monitoring

1 3

2 Pressure relief sets/*


- wall type
Inlet-air sets/*
8 - wall type
- roof type

5 4 - roof type

6 Elements
for adjustment and measurement /*

Overpressure system: Arrangement and quantity of each system element depend on the
1. inspection and measurement elements requirements, construction and location of the protected staircase,
2. smoke sensors lobby, lift shaft, etc.
3. alarm buttons
4. supervision station
5. FACU (fire alarm control unit)
6. mcr Omega control unit
7. pressure relief sets/* (roof or wall type)
8. intake-air sets/* (roof or wall type)
9. exhaust air/* (roof or wall type)
*/ location and quantity depending on air demand of the system
smoke protection devices

complex jet fan system for garages mcr j-FLO


Jet fan systems are used for smoke exhausting from underground
garages as a solution alternative to conventional duct systems.
Operation of the jet fan systems is based on a piston effect in
which the smoke and fire gases are suitably forced through the
whole garage section from the inlet hole to the outlet hole (smoke
exhaust).
The jet fan systems may be used also for comfort ventilation of
garages, as well as co-operate with the CO and LPG detection
systems and dilute and remove gases harmful to people’s health.
The mcr j-FLO complex jet fan system for garages consists of:
• main inlet and outlet fans (e.g. mcr Monsun, mcr Pasat,
mcr Monsun S & mcr Monsun R) of fire resistance F200, F300,
F400 (single-direction or reversible),
• jet fans mcr Bora of fire resistance F200, F300, F400 (single-
direction or reversible),
• mcr Omega control units which supply and control the system
components,
• cut-off dampers for fire ventilation systems (e.g. mcr FID S,
mcr WIP),
• power supply cables, cable suspensions and electro-installation
accessories,
• components of CO, LPG and smoke detection system.
Configuration and the number of individual components of
the system depend on the surface area, height, requirements,
construction and location of the garage to be protected.

communication with the BMS system


BMS system CO and LPG detection unit
power supply 230 V
I threshold
II threshold
III threshold

confirmation of triggering fire alarm


Fire alarm error CO CO CO warning sign
control unit
RS485/RS232

fire alarm
LPG LPG LPG warning sign

uninterrupted power supply


Control and power supply unit mcr Omega C2100 400 V
power supply 400 V
power supply 400 V

power supply and control


monitoring

power supply 400 V


power supply 400 V
power supply 400 V

monitoring

power supply 400 V


power supply and control

power supply 400 V

smoke exhaust air inlet


smoke exhaust outlet fans fire dampers jet fans fire dampers inlet fans

In the case of a fire/smoke, the mcr j-FLO complex jet fan system for garages:
- provides temperature which allows for safe evacuation of garage users (less than 60°C to the level 1.80m above the ground)
- provides visibility which allows for safe evacuation of garage users (less than 10m to the level 1.80m above the ground)
- facilitates operation of rescue teams by not allowing the temperature to increase above 100°C at the distance of more than 10m
from the fire source,
- contributes to the building structure protection by ensuring temperature below 200°C at the level over 2.50m from the ground
(in the space under the ceiling).
FIRE PROTECTION SYSTEMS

smoke and heat exhaust


systems and rooflights
fire ventilation systems
fire protection of building structures