AKE 200

The new Line Matching Unit


for Powerline Communication
Webinar 2021-01-27

Restricted | © Siemens 2021


Agenda Agenda

Introduction

• Overview

• Line Matching Unit AKE 200

• Coupling Variants

• Transmission Diagrams

• Configuration

• Certificates

• Features / Take Aways

AKE 200

Page 2 Restricted | © Siemens 2020


Page 2 Restricted | © Siemens 2021
PowerLink Coupling to HV-Line
Understand the PLC offer parts and functions

Substation A Substation B

LT

= direction of HF signal
CC

Cabinet LT*) = Line Trap: Inductor inserted on the power line to guide the radio Cabinet
signal and to reduce frequency disturbances.
VoIP Phone IP PABX

CC*) = Coupling Capacitor: HV capacitor used to couple/ decouple the radio


LMU
LMU signal onto the power line and to provide safety insulation between AKE200
RTU -104 AKE200 Control Center
HV and LV side.

Router LMU = Line Matching Unit: Impedance matching between HV line and radio Router
signal, incl. overvoltage protection.
HF HF
Distance Distance
Protection Coax Cable * LT, CC com from 3rd party (Trench, Arteche,…) Coax Cable
Protection
Relays Relays

Iimportant:
- We need Frequency Positions => Frequency planning
- Attenuation/Noise of HV-Line => Attenuation Calculation/ Measurement-

Page 3 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
History

Line Matching Unit AKE 100

AKE 100 • Capacitive coupling of HF signals to


HV lines
• Impedance adaptation to guarantee for
optimum coupling of communication
Agenda
• Protection of Communication
equipment against high energy pulses
on the HV lines caused by regular
switching activities or lightning.

Page 5 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Overview

• Line Matching Unit AKE 200 is the successor to the AKE 100,
functionally fully-compatible with AKE 100, and it serves as a one to
one replacement of AKE 100.

• AKE 200 comes in three different variants – A1, A3 and A4 – which


can be combined to cover phase-to-earth or phase-to-phase
communication over HV power lines.

• AKE 200 can be ordered pre-configured for easier installation (but


remains re-configurable) for coaxial or symmetrical data cable.

• Predecessor AKE 100 can only be ordered in exceptional case,


as product is in phase-out mode.
See: “Product Lifecycle – Letter No. 20/06 SI DG EA“

Page 6 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Features
• Line Matching Unit AKE 200 serves as
a robust and safe interface between
HV Power Lines and Powerlink PLC
components
• AKE 200 is a 1:1 replacement of AKE
100
• Priciple of operation has not changed.
• Schematic is valid for AKE 100 and
AKE 200
Agenda
• Technical Data of AKE 200 are identical
or better than AKE 100
• Preconfigured for 75 Ohm (Coax) or
150 Ohm (symmetrical) cable (easy
reconfiurable)
• Certificates: IEC 60481 (KEMA),
IEC 61664-1, IP54, etc.
• Operating temperature
-40°C … 50°C

Page 7 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Proven Technology in state of the art Design - inside View

AKE 200
• Impedance on equipment side:
75 Ohm or 150 Ohm
• adaptable to different coupling capacitors

available in different variants:


Agenda
• AKE 200 A3
(Phase to Earth Coupling)
• AKE 200 A4
(Phase to Phase Coupling)
(same as A3 + A1 Hybrid))
• AKE 200 A1
(hybrid)

Page 8 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Safety

Isolation Transformer
AKE 200
Overvoltage protection:
• Primary Surge Arrestor
• > 5kA; 8/20µs
• 8kA /200ms
Secondary Gas filled
Agenda • Secondary Gas filled Arrestors
Arresters additionally limit overvoltages on
PowerLink side
• Isolation Transformer
Primary Surge Arrester • Dielecrtic strenght: min 10kVeff
• Surge withstand: min 10kV,
1,2/50µs

Page 9 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Handling safety

AKE 200

Housing cover can only be


removed if earthing switch is
Agenda in Position and therefore
HV input of AKE 200 is
grounded!

Page 10 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Ordering Information

AKE 200 can be ordered preconfigured for


symmetrical (150 Ohm) or asymmetrical / coaxial (75 Ohm) cable

Productname Ordering Code MLFB


HF-hybrid transformer AKE200 A1 75R 7VR9670-0AK10
HF-hybrid transformer AKE200 A1 150R 7VR9670-0AK11
Coupling unit AKE200 A3 75R 7VR9670-0AK30
Coupling unit AKE200 A3 150R 7VR9670-0AK31
Coupling unit AKE200 A4 75R 7VR9670-0AK40
Coupling unit AKE200 A4 150R 7VR9670-0AK41

Page 11 Restricted | © Siemens 2021


Line Matching Unit - AKE 200
Coupling variants
Line Matching Unit – AKE 200
Coupling Configurations for Versions A1, A3 and A4

Phase to Earth Coupling Phase to Phase Coupling Phase to Phase Intersystem Coupling
AKE 200 A3 AKE 200 A3 and AKE 200 A4 AKE 200 A1 and AKE 200 A3

Higher costs but good transmission reliability Higher costs but highest transmission reliability
Minimum costs but low transmission reliability.
Transmission guarantee when one connected cable transmission guarantee even during short-circuit
No transmission guarantee when one connected
is broken fault and earth fault of connected cable
cable is broken

NOTE: In this context, “Distance < 30m” or “Distance > 30m” means the length difference between the cables
from the coupling capacitors to AKE200 A4 (Phase to Phase) or AKE200 A1 (Intersystem Coupling)
Page 13 Restricted | © Siemens 2021
Line Matching Unit – AKE 200
Phase to Earth Coupling - Variant A3

Page 14 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Phase to Phase Coupling – Variant A3/A4

Page 15 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Phase to Phase Intersystem Coupling - Variant A1/A3

Page 16 Restricted | © Siemens 2021


Line Matching Unit - AKE 200
Transmission Diagrams
Composite Loss, Return Loss,
Agenda Distortion and Intermodulation

IEC 60481 Requirements

• Return Loss < -12 dB (signal reflection)

• Composite Loss < - 2 dB (signal damping)

• Intermodulation < - 80 dB (signal distortion)

• AKE 200 exceeds the requirements of IEC 60481 and


the transmission parameters are even better than those
of AKE 100

AKE 200

Page 18 Restricted | © Siemens 2020


Page 18 Restricted | © Siemens 2021
Line Matching Unit – AKE 200
Composite and Return Loss - Matching Stage 1

IEC 60481
Return Loss Limit
-12dB

IEC 60481
Composite Loss
Limit -2dB

Page 19 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Composite and Return Loss - Matching Stage 2
In matching stage 2 it is
possible to transmit down to
a lower cutoff frequency
(aG < 2 dB) which is less than
for stage 1 given the same
capacitance of the coupling
capacitor and at the expense
of a lower return loss ( aR ≈ 7
dB). Matching stage 1 should
be used wherever possible

IEC Limit -2 dB

Page 20 Restricted | © Siemens 2021


Line Matching Unit - AKE 200
Configurations
Agenda AKE 200 Configuration

AKE can be configured to

• adapt to different HV coupling capacitors


(nominal values 2.2 nF, 4.4 nF and 8.8 nF)

• chose between matching stages 1 and 2

• 75 Ohm unsymmetrical or
150 Ohm symmetrical cable

AKE 200

Page 24 Restricted | © Siemens 2020


Page 24 Restricted | © Siemens 2021
Connection Diagramm AKE 100 A3 / AKE 200 A3
Matching Stage 1, 75 Ohm

Page 25 Restricted | © Siemens 2021


Connection Diagramm AKE 100 A3 / AKE 200 A3
Matching Stage 2, 75 Ohm

Page 26 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Circuit diagram (inside housing cover)

Page 33 Restricted | © Siemens 2021


Line Matching Unit - AKE 200
Certificates
Line Matching Unit – AKE 200
Test Certificates

AKE 200 exceed the requirements given by the line matching unit standard IEC 60481

Page 35 Restricted | © Siemens 2021


Line Matching Unit - AKE 200
Features
Line Matching Unit – AKE 200
Features / Take Aways

• Based on proven technology


• Fully functional replacement of AKE 100
• Identical or even enhanced transmission parameters than its
predecessor AKE 100
• Adapted and tested according current safety standards
• KEMA tested according highest EMV isolation requirements
(isolation >10 kV, surge 8 kA > 200 ms, …)
• Optimized for High Voltage PowerLine Communication with
Siemens Powerlink Technology

Page 37 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Technical Data

Page 38 Restricted | © Siemens 2021


Line Matching Unit – AKE 200
Documentation Links

Further documentation can be found in

SIOS:
https://support.industry.siemens.com/cs/products?mfn=ps&pnid=25509&lc=en-WW

or Sharepoint:
https://wse06.siemens.com/content/P0009272/SitePages/Smart%20Communication.aspx?FilterField1=Product&Filte
rValue1=AKE200%20-%20Coupling%20Unit&filter=on

Page 39 Restricted | © Siemens 2021


AKE 100
Product Phase-out and Cancellation Announcement

Page 40 Restricted | © Siemens 2020


Contact
Norbert Semela Jens Buerger Klaus Lehr
Product Manager Technical Sales Technical Sales
Phone Phone Phone
+43 664 80117 31481 +49 152 2295 1134 +49 174 1560867
E-mail E-mail E-mail
norbert.semela@siemens.com jens.buerger@siemens.com klaus.lehr@siemens.com

Siemens AG Siemens AG
Smart Infrastructure Smart Infrastructure
DG EA-P&R DE-AU D3 DG EA-S TES SCS
81739 Munich 81739 Munich
Germany Germany

siemens.com/powerlink-ip

Restricted | © Siemens 202


2021

You might also like