Caja de Sintonía AKE 200 de SIEMENS
Caja de Sintonía AKE 200 de SIEMENS
Introduction
• Overview
• Coupling Variants
• Transmission Diagrams
• Configuration
• Certificates
AKE 200
Substation A Substation B
LT
= direction of HF signal
CC
Cabinet LT*) = Line Trap: Inductor inserted on the power line to guide the radio Cabinet
signal and to reduce frequency disturbances.
VoIP Phone IP PABX
Router LMU = Line Matching Unit: Impedance matching between HV line and radio Router
signal, incl. overvoltage protection.
HF HF
Distance Distance
Protection Coax Cable * LT, CC com from 3rd party (Trench, Arteche,…) Coax Cable
Protection
Relays Relays
Iimportant:
- We need Frequency Positions => Frequency planning
- Attenuation/Noise of HV-Line => Attenuation Calculation/ Measurement-
• Line Matching Unit AKE 200 is the successor to the AKE 100,
functionally fully-compatible with AKE 100, and it serves as a one to
one replacement of AKE 100.
AKE 200
• Impedance on equipment side:
75 Ohm or 150 Ohm
• adaptable to different coupling capacitors
Isolation Transformer
AKE 200
Overvoltage protection:
• Primary Surge Arrestor
• > 5kA; 8/20µs
• 8kA /200ms
Secondary Gas filled
Agenda • Secondary Gas filled Arrestors
Arresters additionally limit overvoltages on
PowerLink side
• Isolation Transformer
Primary Surge Arrester • Dielecrtic strenght: min 10kVeff
• Surge withstand: min 10kV,
1,2/50µs
AKE 200
Phase to Earth Coupling Phase to Phase Coupling Phase to Phase Intersystem Coupling
AKE 200 A3 AKE 200 A3 and AKE 200 A4 AKE 200 A1 and AKE 200 A3
Higher costs but good transmission reliability Higher costs but highest transmission reliability
Minimum costs but low transmission reliability.
Transmission guarantee when one connected cable transmission guarantee even during short-circuit
No transmission guarantee when one connected
is broken fault and earth fault of connected cable
cable is broken
NOTE: In this context, “Distance < 30m” or “Distance > 30m” means the length difference between the cables
from the coupling capacitors to AKE200 A4 (Phase to Phase) or AKE200 A1 (Intersystem Coupling)
Page 13 Restricted | © Siemens 2021
Line Matching Unit – AKE 200
Phase to Earth Coupling - Variant A3
AKE 200
IEC 60481
Return Loss Limit
-12dB
IEC 60481
Composite Loss
Limit -2dB
IEC Limit -2 dB
• 75 Ohm unsymmetrical or
150 Ohm symmetrical cable
AKE 200
AKE 200 exceed the requirements given by the line matching unit standard IEC 60481
SIOS:
https://support.industry.siemens.com/cs/products?mfn=ps&pnid=25509&lc=en-WW
or Sharepoint:
https://wse06.siemens.com/content/P0009272/SitePages/Smart%20Communication.aspx?FilterField1=Product&Filte
rValue1=AKE200%20-%20Coupling%20Unit&filter=on