For an end user to utilize the O3 App the facility is required to utilize enteliWEB.

Select one:
True
False

Question 2

Question text

What is the correct power required by the O3 controller?

Select one:
a. 120VAC
b. 24VAC
c. 0-10VDC
d. 24VDC

Question 3

Question text

Select the devices that are members of the Application Controllers series. (select
three)
Select one or more:
DAC-1180
DVC-V322
eBCON
eZFC

Question 4

Question text

Which devices include a real time clock? (select two)


Select one or more:
DAC-1180
DFM-404
DSC-1616E
eBMGR

Question 5

Question text

Select the correct a O3 hardware for a zone that is serviced by a fan coil unit
equipped with a cooling coil, perimeter heat and a 3 speed fan. In addition there is
an environmental blind/shading system to take advantage of natural light. The
specification also requires automatic occupant detection and a no-touch interface
for the user space.

Select the correct item from the drop down list to mach the requirement. (Feel free
to search the internet to find information on product you are not familiar with.)
DIN-CPU

Controller Answer
Delta Electronics DRC-24V60W1A

Supply Power Answer
O3-DIN-SRC

HVAC Answer
O3-Hub

Zone Sensor Answer
O3-Hub

Shade Control Answer

Topic 2:

Question 1

Question text
This power connection requires which type of power supply?

Select the best answer.

Select one:
a. A dedicated 24VAC power supply.
b. 120VAC
c. 24VAC
d. 24VDC

Question 2

Question text

The controller ground lug can be connected to the power circuit neutral.

Select one:
True
False

Question 3

Question text

Drag the correct power input terminals to the power supply output connections.
Question 4

Question text

Delta products that require DC power are not polarity sensitive.


Select one:
True
False

Question 5

Question text

Match the correct wave form description for each diagram.

NOTE; You may need to expand your browser.

Answer 1
Sine Wave

Answer 2
Full Wave
Answer 3
Direct Current

Half Wave
Answer 4

Topic 3

Which temperature sensor has a negative temperature coefficient (i.e. the sensor
value is inverse to changes in temperature)?

Select one:
a. Resistive Temperature Device (RTD)
b. Thermistor

Question 2

Question text
You finished wiring in a new 4-20mA sensor for a Duct Static Pressure (DSP)
Sensor that is rated for a range of 0 - 1 inch Water Column, and configured the
Analog Input on an eBCON as per the following:

But the input readings displayed in enteliWEB seem wrong or unexpected.

What is the best solution?  Pick ONE answer.

Select one:
a. Blame the electrician.
b. Create a new AIC object that corrects the signal.
c. Call Delta tech support. Or better still, go on the tech forums and complain a
lot.
d. Change the input jumper from the factory setting of 10V to 4-20mA

Question 3

Question text

The two main causes of noise on a 0-5V signal. (Select the correct answer from the
drop down list.)

Improper grounding

A. Answer
Electromagnetic fields. (ie. Old florescent lights)

B. Answer

Question 4

Question text

Select the controller expansion module[s] that offer universal inputs. (Uniputs)

Select one or more:


a. eBM-440I
b. 03-DIN-8x4xP
c. 03-DIN-8xP
d. 03-DIN-CPU

Question 5

Question text

Drag and drop the names of the 6 main signal types from the pallet at the bottom,
to the correct end device shown in the image, below.  
6- Dry Contact
2- 10K T3 Temp Sensor
5- 5 VDC
5-10V DC
3,5 - 4-20ma
6-RTD temp sensor
Topic 4

Question 1

Question text

What is the maximum allowable VA draw of a eBM-404?

Select one:
a. 27VA
b. 120VA
c. 5VA
d. 24VAC

Question 2

Question text
What is the maximum switching amperage of a SSR or FET output on a Delta
controller?

Select one:
a. 0.5 Amps
b. 0.25 Amps
c. 5.0 Amps
d. 1.0 Amp

Question 3

Question text

Consider the binary output wiring and jumper selections in the illustration below.

Select one answer for each question.

Is the power source for the outputs internal or external?

Which jumper selection is used with this power source?

HINT:  The installation guide can used to find more information on jumper pin
settings.
Select one or more:
 internal
 Jumper Selection B
external
Jumper Selection A

Question 4

Question text

Which devices work correctly when connected to an analog output? (select two)

Select one or more:


device rated for 2 to 10 Volts at 20 mA
device rated for 0 to 10 Volts at 20 mA
device rated for 0 to 10 Volts at 50 mA
device rated for 0 to 20 Volts at 10 mA

Question 5

Question text
'Universal' (or analog) outputs are capable of supplying up to _____ mA at 10
VDC

Select one:
a. 10mA
b. 1A
c. 500mA
d. 20mA
e. 100mA

Topic 6

Question 1

Question text

MS/TP is an acronym for:

Select one:
a. Multiple Spanning Tree Protocol
b. Main Slave Trunk Protocol
c. Master Slave Token Passing
d. Master System Token Protocol

Question 2

Question text

Identify the DNA hierarchy levels. (select three)


Select one or more:
Subnet
System
Area
BACnet IP

Question 3

Question text

The Service port on a controller: (Select Two):

 
Select one or more:
Typically allows access to the entire network
converts the controller’s RS-232 to a laptop’s RS-485 port
Allows access to other workstations
Allows access to the connected controller

Question 4

Question text

How many controllers can an Ethernet network support?

Select one:
no more than 99
no more than 64
more than 99
no more than 32

Question 5

Question text

Consider a BACnet network with three DAC-633 controllers connected


sequentially in a daisy-chain fashion.

Which address assignments are accurate for these DACs? (select three)

Select one or more:


43009, 43010, 43011
43100, 43201, 43302
10101, 10102, 10103
20510, 20511, 20512

Question 6

Not yet answered


Marked out of 1.0
Flag question

Question text

When using DNA, what is the BACnet Device Address for a 'System' level
controller that has the following DIP switch settings? NOTE: In this example, there
is NO Area level controller present.

Select one:
a. It's not possible to determine the address without a System level controller
present.
b. 9
c. 90000
d. 90
e. 900
f. 81

Question 7

Question text

Which protocols are used by Delta products on RS-485 networks? (select two)
Select one or more:
LINKnet
BACnet IP
Point-to-Point
MS/TP

Question 8

Question text

True or False: By convention, subnet controllers are normally connected to NET2


of a System controller

Select one:
True
False

Question 9

Question text

Consider this network layout.

Controller #6 is set to address 31309 and controller #9 is set to address 51309.

Identify other correctly addressed controllers. (select two)

Select one or more:


Controller #5 is addressed as 31308
Controller #2 is addressed as 510000
Controller #10 is addressed as 51310
Controller #1 is addressed as 310000
Question 10

Question text

MS/TP ports are labeled as: (select two)


Select one or more:
Ethernet
Net 1
Serial
Net 2

Topic 7

Question 1

Question text

Identify two network wiring errors.

Select one or more:


shield doesn't land at the controllers
network polarity at Controller B
terminator not grounded
wiring at Controller A

Question 2

Question text

What Physical Network topology is supported for BACnet MS/TP over RS-485?
Select one:
a. "T"
b. Rose Link
c. “Y”
d. Daisy Chain
e. Star

Question 3

Question text

An RS-485 network configuration:

Select one:
allows bus but not star configuration
allows star but not bus configuration
must be wired in daisy-chain fashion
allows both bus and star configurations

Question 4

Question text

What type of wire is commonly used for MS/TP networks?

Select one:
fiber optic
Lamp Cord (rated for higher quality lamps only)
22 AWG shielded twisted pair
Cat 5 (or better)

Question 5

Question text

The Delta Wiring and Installation Guidelines document describes the


recommended method for grounding the RS-485 network cable shield.

Which statement summarizes this method?


Select one:
use TRM-768 at both ends of the network and terminate shield to TRM at both
ends
earth ground the shield at both ends of the network
earth ground the shield at one end of the network and leave floating at other end
leave the shield floating at both ends of the network

Topic 8

Question 1

Question text

When testing for stray voltages between an I/O wire and the controller's terminals,
we're looking for more than how many volts?

Select one:
a. 208 V
b. 5 V
c. 0.5 - 1V
d. 24 V
e. 460 V

Question 2

Question text

The padlock icon that can display for an AI, BI, AO, BO object means what when
it is displayed?

Select one:
a. The input/output object is locked out and can't be manipulated
b. The input/output object's software value is disconnected from the actual
hardware signal
c. The input/output object is faulted because there's no physical I/O wiring point
d. The input/output object has been checked and is known to work properly
e. The input/output object is not commissioned

Question 3
Question text

What tool is nearly always required for doing end-to-end commissioning?

Select one:
a. fire extinguisher
b. helicopter
c. CON-768BT
d. two-way radios
e. temperature calibration probe
Topic 9

Question 1

Question text

On an MS/TP network, the ratio of Invalid Received to Total Received should be


better than:

Select one:
a. 1 : 10000000
b. 1 : 1
c. 1 : 1000
d. 1 : 100
e. 1 : 100000

Question 2

Question text

What is the tolerable range of voltage for Delta controllers?

Select one:
a. 24 - 120 VAC
b. 22 - 26 VDC
c. 12 - 48 VAC
d. 18 - 30 VAC
e. 20 - 28 VAC

Question 3

Question text
The batteries on some Delta controllers need to be changed every X years:

Select one:
a. 10 years
b. 5 years
c. 2 years
d. 20 years
e. They last forever

Question 4

Question text

Why is a CON768-BT a required tool?

Select one:
a. enteliWEB only communicates to controllers using a CON768-BT
b. It's the only way to upgrade the firmware on a controller
c. It's the only local access method for many controllers
d. It's is a faster way to talk to a controller
e. It's the only way to locally talk to an eBCON

Question 5

Question text

The static memory free in a controller should not be allowed to drop below what
amount?

Select one:
a. 10%
b. 2%
c. 10 kB
d. 10 MB
e. 20%