PRECOMMISSIONING

- INSPECTION OF PANELS
- MOUNTING OF CANOPY THY
FANS , PANEL METERS ETC.,
- INTERPANEL WIRINGS
- EXTERNAL CABLING &
OPERATING INSTRUCTION
FOR TERMINATION
- EARTHING
STATIC ( PANEL
EXCITATION &
EQUIPMENT
ELECTRONIC )
- TIGHTNESS OF ALL TBs
- AVAILABILITY OF
CONTROL SUPPLY

REF: 18-06-2004 / PR1

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
PRECOMMISSIONING

- MEGGERING
- HEALTHYNESS OF
ELECT. COMPONENTS LIKE
COILS FUSES, RESISTORS AND
AUX.CONTACTS.
- LOCATION OF MODULES
OPERATING INSTRUCTION
- SECURING
FOR ELECTRONIC
MODULES PROPERLY
STATIC EXCITATION TO THE
EQUIPMENT
CONNECTORS.
- HEALTHYNESS OF
THY.DEVICES

REF: 18-06-2004 / PR2

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
PRECOMMISSIONING

• STATIC CHECKS ON
CONTROL AND POWER
ELEMENTS .
• SETTING OF MODULES AS
PER TEST REPORT
• MAKING GEN.CT CIRCUIT
OPERATING INSTRUCTION
THROUGH
FOR
• PANEL CHARGINGEQUIPMENT
STATIC EXCITATION
• DISTRIBUTION OF AC/DC
• PHASE SEQUENCE
• HEALTHYNESS OF POWER
SUPPLIES
• HEALTHYNESS OF
ELECTRONIC MODULES
REF: 18-06-2004 / PR3

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
PRECOMMISSIONING

• SIMULATION OF Ug , Ig & If .
CALIBRATION AND DISPLAY
ON TERMINAL
•PROTECTION AND
INTERLOCKS.
•CHANNEL HEALTHYNESS
OPERATING INSTRUCTION
•PROTECTION
FOR CHANGE-OVER
•ALARM AND SIGNALLING
STATIC EXCITATION EQUIPMENT
•LOCAL / REMOTE CONTROLS
/ INDICATIONS
• FIELD BREAKER OPN.
• PROTECTION TRIPPING

REF: 18-06-2004 / PR4

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
COMMISSIONING

• CHKG.PULSES RIGHT FROM


GENERATION TILL DEVICES
FOR PROPER SHAPE ,
SEQUENCE AND
DISTRIBUTION.
• PULSE BLOCKING AND
OPERATING INSTRUCTION
CHANNEL
FOR CHANGE-OVER
• LIGHT
STATIC LOAD TESTEQUIPMENT
EXCITATION
• DC WAVEFORM ON CRO
•WATER LOAD TEST
•PROPER SHARING OF THY
BRIDGES.
•mv DROP ACROSS THYs.
•REPEAT TESTS WITH EXN.TRA.
REF: 18-06-2004 / PRE5

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
COMMISSIONING

-SETTING OF GATE CONTROL


MDL.
•GEN.PROTECTION CHECKS
•SCC , OCC . RECORDING
•CHKG. PT FEEDBACKS FOR
MAGNITUDE AND SEQUENCE.
OPERATING INSTRUCTION
•CALIBRATION
FOR OF Ug IF
REQUIRED.
STATIC EXCITATION EQUIPMENT
•NORMALISING
•FIELD FLASHING TR. O/P
•RECORD RESIDUAL VOLTAGE
1-4%

REF: 18-06-2004 / C1

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA
COMMISSIONING

•STEP TEST ON AUTO AND


RECORDINGS OF DVR
RESPONSE.
•V/F LIMITER SETTING
•LOADING
•LIMITERS If , Ig ind., Ig cap.,
OPERATING INSTRUCTION
LOAD
FOR ANGLE
•PSS
STATIC EXCITATION EQUIPMENT

REF: 18-06-2004 / C3

BHARAT HEAVY ELECTRICALS LIMITED


ELECTRONICS DIVISION
MYSORE ROAD, BANGALORE-560 026
INDIA