Method To Evaluate Fault Current in Electircal Network
Method To Evaluate Fault Current in Electircal Network
Method To Evaluate Fault Current in Electircal Network
2.5 MVA rated current on 433 volts side = 2500 X 10³ = 3478 Amps considering 6.25 % of Z
√3 415
Considering this fault current on LV side will be = 3478 X 100 = 49.942 kA (at Transformer terminals)
(6.25 + 0.714)
% impedance will be
100,000 X 2500 X 0.144 =0.209 %
1000 X (415)2
To reach location - 2, two nos of breakers & B/B inside main PCC panel have to be considered,
Data considered
Breaker impedance @ 0.15 mΩ/ Breaker
Total travel of Bus Bars =4+2 Mtrs
4mts of 5000mm2 and 2mts of 3200mm2
Page 1 of 3
Impedance of 2mtrs length = 36 X 2 =0.0225mΩ
3200
To reach location - 3, 100mtrs of 8 runs, 3.5 cores, and 400mm 2 cables have to be taken into consideration.
Since there are 8 runs in parallel effective impedance will be = 0.122 = 0.001525 Ω
8
However the fault current seen by MPDB breakers will be much less than this because of the breaker impedance.
Considering this the fault current seen MPDB incomer breaker will be,
Page 2 of 3
FAULT CURRENT AT LOCATION – 4
To reach location - 4, 2 nos of breakers are to be considered along with B/B inside the MPDB.
Data considered
Breaker impedance 0.17 mΩ/ Breaker
Total travel of Bus Bars = 6mts @3200mm2
Breaker Impedance = 0.17 x 2 = 0.34 mΩ
% impedance will be
100,000 X 2500 X 0.001015 = 1.473 %
(415)2
Fault current at location-4 will be 30.026 kA
0.1222 X 60 = 0.00146 Ω
1000 x 5
% impedance will be
100,000 X 2500 X 0.00146 = 2.119 %
(415)2
Fault current,
= 3478 X 100 = 347800 = 25.383 kA
11.583 + 2.119 13.702
Page 3 of 3