PROJECT: SOUQ WAQIF UNDERGROUND CARPARK

EQPT
S/N EQUIPMENT MONITOR CONTROL SOFTWARE
QTY
BUILDING MANAGEMENT SYSTEM
1 LIGHTING PANELS 92 
2 FIRE ALARM CONTROL PANEL 6 
3 STORM WATER PUMP SET 8  
4 IRRIGATION TANK MAKEUP PUMPS 6  
5 MAIN IRRIGATION PUMP SET 2  
6 COLD WATER BOOSTER PUMP SET 2  
7 SUBMERSIBLE PUMP SET 14 
8 STORM WATER TANK 4 
9 IRRIGATION WATER TANK 4 
10 POTABLE WATER TANK 1 
11 POTABLE WATER TANK (FOR FIRE PROTECTION) 1 
12 FIRE PROTECTION PUMPS 1 
13 FIRE PROTECTION MAIN/ZONE ALARM VALVE 9 
14 BUTTERFLY VALVE FOR WATER TANK 8 
15 EMCC/MCC 15 
16 ZONE ALARM VALVE 20 
17 MOTORIZED DAMPER 12 
18 SEF IN TUNNEL 3  
19 TOILET EXHAUST FANS 5  
20 ERU 3  
21 MV PANEL/EMV PANEL 4 
22 GENERATOR 2 
23 ATS 2  
24 PARKING MANAGEMENT SYSTEM 1  
25 GATE BARRIER 12 
26 FIRE SMOKE DAMPER 2 
27 PRE-ACTION VALVE 6 
28 POLISHED WATER TANK 1 
29 POLISHED WATER TANK PUMP 1  
30 TSE WATER TANK 1 1 
31 TSE WATER TANK 1 PUMP 1  
32 TSE WATER TANK 2 1 
33 TSE WATER TANK 2 PUMP 1  
34 REJECTED WATER TANK 1 
35 REJECTED WATER TANK SET (1D+1S) 1  
36 CHILLER 3  
37 CHW PRIMARY PUMP 4  
38 CHW SECONDARY PUMP 4  
39 CHEMICAL DOSING UNIT 2 
40 CONDENSED WATER PRIMARY PUMP 4  
41 COOLING TOWERS 9  
42 PRESSURIZATION UNIT 2 
43 AIR CURTAIN 12  
44 FAN COIL UNIT 29  
45 FRESH AIR HANDLING UNIT 34  
46 RACP 34  
47 LV PANEL 1 
48 MAKEUP WATER PUMPS 4  
49 MAKEUP WATER TANK 2 
50 WEATHER STATION 1 
SOFTWARE INTEGRATION
1 DIGITAL POWER METER FOR MCC 14 
2 DIGITAL POWER METER FOR MV PANEL 4 
3 CAR PARK CO MONITORING SYSTEM 1 
CARPARK CO MONITORING SYSTEM

S/N EQUIPMENT QTY MONITOR CONTROL SOFTWARE

1 CARPARK EXHAUST FANS 34 


2 CARPARK SUPPLY FANS 24 
3 INDUCTION FANS 135 
4 CO LEVEL SENSOR 133 
BILL OF QUANTITY: BUILDING MANAGEMENT SYSTEM

S/N DESCRIPTION QTY COO


BUILDING MANAGEMENT SYSTEM
FIELD INSTRUMENTS
1 Filter Air DP Switch 20Pa to 300 Pa 97 Germany
2 Mounting Kit for ADPS 97 Germany
3 24Vac/24Vdc 1A Power Supply regulator 1 UK
4 Relay Module, Contact: 12A 250Vac for FCU 29 UK
5 Water Pressure sensor, 0-15psi 16 U.S.A.
6 Water Pressure sensor, 0-200psi 19 U.S.A.
7 Water Diff. Pressure sensor, 0-100psi, DIN Conn, 0-10 Vdc 1 U.S.A.
8 Water flow switch weather proof 1"- 8" pipe size 15 U.S.A.
9 Water differential pressure switch 67 U.S.A.
10 Duct air temperature sensor 10kohm Type III 6 U.S.A.
11 4" Imm Type temperature sensor, 10kohm TypIII 121 U.S.A.
12 4" Thermowell 121 U.S.A.
13 Duct Air Temp. & Humidity sensor w/10K ohm type III, 0-10 vdc 102 U.S.A.
14 Damper actuator on/off type 10 N.M , 230 Vac with aux contact 6 Switzerland
15 Float switch -Tank Filling/Emptying, 5m cable with counterweight 46 Italy
16 DDC & IO MODULES
17 BACnet MSTP DDC Controller (4UI,4DO,2UO) Lot Canada
18 BACnet MSTP DDC Controller (6UI,5DO,3UO) Lot Canada
19 BACnet MSTP DDC Controller (10UI, 8UO) Lot Canada
20 FCU BACnet MSTP DDC Controller 29 Canada
21 FCU Room Thermostat with backlit display and graphical menus. 29 Canada
22 BACnet MSTP IO Modules (8UI, 2DI, 2UO, 2AO, 6DO) Lot Canada
23 BACnet MSTP IO Modules (8UI) Lot Canada
24 UPPER MANAGERMENT & AUTOMATION SERVER
25 EC-NetAX Supervisor / BMS Software Lot Canada
26 Eclypse-APEX IP server Lot Canada
27 Communication module with 2 RS-485 Ports Lot Canada
28 LOCAL MATERIALS
29 Operator workstation and Accessories 1 Local
30 Epson LX-350 heavy duty alarm printer 1 Local
31 HP office jet color printer 1 Local
32 Automation Server Metal Enclosure IP55 - c/w assembly 1 Local
33 DDC Panel Metal Enclosure IP55 - c/w Assy type 1 40 Local
34 DDC Panel Metal Enclosure IP55 - c/w Assy type 2 6 Local
35 DDC Panel Metal Enclosure IP55 - c/w Assy type 3 3 Local
36 30VA, 240/24Vac transformer + PVC box type for FCU DDC 29 Local
BILL OF QUANTITY: MOTORIZED VALVE + ACTUATOR
S/N DESCRIPTION QTY COO
FCU VALVE & ACTUATOR
1 1" 2 Way Motorized Valve 27 Italy
2 1.1/4" 2 Way Motorized Valve 2 Italy
3 modulating actuator 24 Vac w/ feedback 29 Italy
4 FAHU VALVE & ACTUATOR
5 2.1/2" 2 Way Motorized Valve 10 Italy
6 3" 2 Way Motorized Valve 9 Italy
7 4" 2 Way Motorized Valve 3 Italy
8 5" 2 Way Motorized Valve 12 Italy
9 modulating actuator 24 Vac w/ feedback 34 Italy
10 BUTTERFLY VALVE + ACTUATOR (for CHILLERS)
11 8" Butterfly Valve 12 Italy
12 Rotary valve actuator on/off/3pos. 230Vac 30Nm 12 Italy
13 mounting of MDL actuator on VFA butterfly valves 12 Italy
14 Auxiliary micro-switches for MDL actuators 12 Italy
15 BUTTERFLY VALVE + ACTUATOR (for COOLING TOWER)
16 8" Butterfly Valve 18 Italy
17 Rotary valve actuator on/off/3pos. 230Vac 30Nm 18 Italy
18 mounting of MDL actuator on VFA butterfly valves 18 Italy
19 Auxiliary micro-switches for MDL actuators 18 Italy
20 BUTTERFLY VALVE + ACTUATOR (for WATER TANKS)
21 1.1/4" Butterfly Valve 1 Italy
22 2.1/2" Butterfly Valve 1 Italy
23 4" Butterfly Valve 6 Italy
24 Rotary valve actuator on/off/3pos. 230Vac 30Nm 8 Italy
25 mounting of MDL actuator on VFA butterfly valves 8 Italy

BILL OF QUANTITY: BMS INSTALLATION, CABLE PULLING, TERMINATION


S/N DESCRIPTION QTY COO
BMS INSTALLATION, CABLE PULLING & TERMINATION
1 Cable Pulling Lot Local
2 Cable Termination Lot Local
3 Field Device Installation 520 Local
4 DDCP Installation 50 Local

BILL OF QUANTITY: BMS CABLES (PVC Sheath, NON-Low Smoke Zero Halogen)
S/N DESCRIPTION ROLLS COO
BMS CABLES (60 METERS/POINT)
1 2C, 18AWG Shielded cable (305m/roll) 350 Italy

2 2C, 22AWG Shielded twisted pair cable (305m/roll) 21 Italy

3 CAT6 cable (305m/roll) 1 Local

4 1.5 mmsq. Power cable 5 Local


BILL OF QUANTITY: CAR PARK CO MONITORING SYSTEM
S/N DESCRIPTION QTY COO
FIELD INSTRUMENTS
1 Carbon Monoxide Detector 4-20mA 133 Canada
2 24Vac/24Vdc 1A Power Supply regulator 9 UK
3 DDC & IO MODULES
4 BACnet MSTP DDC Controller (6UI,5DO,3UO) Lot Canada
5 BACnet MSTP DDC Controller (10UI, 8UO) Lot Canada
6 BACnet MSTP IO Modules (8UI, 2DI, 2UO, 2AO, 6DO) Lot Canada
7 LOCAL MATERIALS
8 CO Panel Metal Enclosure IP55 - c/w Assy type 1 3 Local

BILL OF QUANTITY: CO SYSTEM INSTALLATION, CABLE PULLING, TERMINATION


S/N DESCRIPTION QTY COO
CO SYSTEM INSTALLATION, CABLE PULLING & TERMINATION
1 Cable Pulling Lot Local
2 Cable Termination Lot Local
3 Field Device Installation 133 Local
4 DDCP Installation 3 Local

BILL OF QUANTITY: CO SYSTEM CABLES (PVC Sheath, NON-Low Smoke Zero Halogen)
S/N DESCRIPTION ROLLS COO
CO SYSTEM CABLES (60 METERS/POINT)
1 2C, 18AWG Shielded cable (305m/roll) 55 Italy
2 2C, 22AWG Shielded twisted pair cable (305m/roll) 1 Italy