Date of Report Date : August 8, 2023

Date of Sampling Client : August 10, 2023


Client Name : Technical Contracting Est.
Project Name : The Village Mall (SLIDER)
Sample Description : Chilled Water System

CHEMICAL WATER ANALYSIS REPORT

Item No. Sample Referances Control Limits Results

1 Sample Referances 9.5-11 9.1


2 Conductivity uS/Cm 5000 Max 2784
3 TDS, ppm 3000 Max 2234
4 Corrosion Inhibitor, ppm 1000 Min 865
5 Total Iron, ppm as Fe 2.0 Max 0.9
6 Total Suspended Solids, ppm 10 Max 6.7

Finding&Recommendation:

• All water parameters tested were found acceptable and within the limits.

Best Regards,

Reem Baissa
Lab Chemist
WATER TECHNOLOGIES
Office +966 12 660 6031Ext: 211
AI-Andalus District, Shahd Center, P.O. Box 11112 Jeddah 21453, Kingdom of Saudi Arabia
www.middle-east.veoliawatertechnologies.com