1 2 3 4 5 6 7 8 9 10

PLC CUM MCC PANEL


C

PANEL GENERAL ARRANGEMENT


Rev : 00 , Date : 04.06.2023
D

G CLIENT : 02 03 TITLE : SHEET NO 01/04


M/s.MAADEN 00 04.06.2023 FOR APPROVAL 01 TITLE SCALE NTS
ERAM ASACON COMPANY APPLICATION : WO.NO NO DATE REVISION NO DATE REVISION DRAWN BY : CHECKED BY : APPROVED BY : DWG. NO : REV
AUTO WEIGHING AND BATCHING SYSTEM 40 PROJECT: AUTO WEIGHING AND BATCHING SYSTEM SKV MIU SVY EAC-40-GA-01 00
1 2 3 4 5 6 7 8 9 10

PANEL SPECIFICATIONS DRAWING REFERENCE


CABLE DUCT
1. All Dimension in mm.
2. The Panel Shall Be Suitable for 415vac,3phase,50Hz ( Effectively Earthed). CD XX x XX
B
CABLE DUCT DEPTH
3. Panel Shall Have Single Front Operation. CABLE DUCT WIDTH
4. Removable Type 1.5mm Thick Gland Plate Shall be provided in Bottom of the Panel. CD - CABLE DUCT
5. Material : CRCA Sheet Steel. FD - FIELD DUCT
6. Sheet thickness (As per Rittal Standard):
Enclosure Frame : 9-fold Profiled.
C
Door : 2mm.
Side Cover : 1.5mm.
Mounting Plate : 3mm.
Surface Finish
Enclosure : Powder coated in RAL 7035(Minimum 60microns thickness coating).
Door shall be projected type with swing of 85-120.
7. Panel shall be free standing type as per requirement.
D
8. Maximum Operating Height Shall be 1800mm.and Minimum Operating Height Shall be 300mm.
9. Degree of Protection IP-55 (Before making Panel Cut-out).
10. Cable entry shall be from Bottom.
11. Panel internal wiring run through the PVC channels with cover.
12.
13. Seperate Key shall be provided for each panel.
E

G CLIENT : 02 03 TITLE : SHEET NO 02/04


M/s.MAADEN 00 04.06.2023 FOR APPROVAL 01 SPECIFICATION SCALE NTS
ERAM ASACON COMPANY APPLICATION : WO.NO NO DATE REVISION NO DATE REVISION DRAWN BY : CHECKED BY : APPROVED BY : DWG. NO : REV
AUTO WEIGHING AND BATCHING SYSTEM 40 PROJECT: AUTO WEIGHING AND BATCHING SYSTEM SKV MIU SVY EAC-40-GA-01 00
1 2 3 4 5 6 7 8 9 10

EXTERNAL SIDE VIEW EXTERNAL FRONT VIEW EXTERNAL SIDE VIEW


A
800
500 500

PLC CUM MCC PANEL


150

150
HOOTER

HOOTER WEIGHT INDICATOR

UPS 24V
HEALTHY HEALTHY ALARM ACK. EMG
IND. IND. ILL.PB PB

RED GREEN YELLOW RED

UPS POWER OFF/ON


2000

2000
2115

WIRING PLAN
POCKET

D
150

150

15 15
100

100

800
460

G CLIENT : 02 03 TITLE : SHEET NO 03/04


M/s.MAADEN 00 04.06.2023 FOR APPROVAL 01 EXTERNAL PANEL GENERAL ARRANGEMENT SCALE NTS
ERAM ASACON COMPANY APPLICATION : WO.NO NO DATE REVISION NO DATE REVISION DRAWN BY : CHECKED BY : APPROVED BY : DWG. NO : REV
AUTO WEIGHING AND BATCHING SYSTEM 40 PROJECT: AUTO WEIGHING AND BATCHING SYSTEM SKV MIU SVY EAC-40-GA-01 00
1 2 3 4 5 6 7 8 9 10

INTERNAL SIDE VIEW INTERNAL FRONT VIEW INTERNAL SIDE VIEW


800
500 500

CD 60 X 80 MM
180

4AI

CD 60 X 80 MM
Q03 Q04 Q05 Q06 Q07 Q08

F01 B01 B02


160

MCB
SMPS
SP01
G01

CD 60 X 80 MM
R207-A R208-A R209-A R210-A
160

RELAY
RELAY
CD 80 X 80 MM
FD 60 X 80 MM

CD 60 X 80 MM
R211-A R212-A
160

C RELAY
RELAY
2115

2115

REC01
CD 80 X 80 MM

X209
DO

DI X201

X210
DO

DI X202

X211
DO
DI X203

X212
DO
DI X204

TB'S DI
FD 80 X 80 MM

FD 80 X 80 MM

X213
X205
DO
TB'S
820

DI X206
X214
DO

D
DI X207

DI X208

AI X215

X32
WI-1
UPS X30
TB'S

PE 185 185 PE

FOUNDATION VIEW

40
460

424

379

670
735
800

G CLIENT : 02 03 TITLE : SHEET NO 04/04


M/s.MAADEN 00 04.06.2023 FOR APPROVAL 01 INTERNAL PANEL GENERAL ARRANGEMENT SCALE NTS
ERAM ASACON COMPANY APPLICATION : WO.NO NO DATE REVISION NO DATE REVISION DRAWN BY : CHECKED BY :APPROVED BY : DWG. NO : REV
AUTO WEIGHING AND BATCHING SYSTEM 40 PROJECT: AUTO WEIGHING AND BATCHING SYSTEM SKV MIU SVY EAC-40-GA-01 00

You might also like