C-FIX 1.117.0.

0
Database version
2023.6.16.16.1
Date
03/08/2023

fischer fixings LLC

62 Orange Ave
10901 Suffern, NY
Phone: +1 845 504 5098
Fax: +1 845 625 2666
info@fischerfixingsusa.com
www.fischerfixingsusa.com

Design Specifications
Anchor
Anchor system fischer Injection system FIS EM plus
Injection resin FIS EM Plus 390 S
Fixing element Threaded rod FIS A M 20 x 245 8.8,
zinc plated steel, Property Class 8.8
Calculated anchorage 6.00 in, Anchoring depth hef for calculation 5.98 in
depth

Geometry / Loads / Scale units


in, lbf, inlbf

black: Value of design actions (including

partial safety factor for the load)

blue: Sustained Loads has to be Static

respected according ACI.

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 1
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Input data

Design method Design method ACI 318-14 Bonded


Load Combination Design Loads ACI 318-14 Chapter 5.3
Base material Normal weight concrete, 5000 psi, ACI 318
Concrete condition Non-cracked, dry hole
Temperature range 75 °F long term temperature, 104 °F short term temperature,
Temperature range A
Reinforcement Tension: Condition B. Shear: Condition B. Edge
reinforcement with stirrups
Drilling method Hammer drilling
Installation type Push-through installation
Annular gap Annular gap filled
Type of loading Permanent-Transient/Static
Base plate location Base plate flush installed on base material
Base plate geometry 28.00 in x 14.00 in x 0.50 in
Profile type None

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
lbf lbf lbf inlbf inlbf inlbf
1 5,712.0 0.0 3,917.0 19,586.0 1,551.0 28,560.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
2 4,896.0 3,358.0 2,890.0 1,330.0 99,388.0 107,455.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
3 3,672.0 2,518.0 2,890.0 997.0 95,191.0 101,335.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
4 4,956.0 3,178.0 0.0 2,560.0 15,888.0 24,780.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
5 4,796.0 3,698.0 0.0 940.0 18,488.0 23,980.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
6 3,732.0 2,338.0 0.0 2,227.0 11,691.0 18,660.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
7 3,572.0 2,858.0 0.0 1,273.0 14,291.0 17,860.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
8 4,896.0 3,358.0 860.0 1,330.0 16,268.0 32,090.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load
9 3,672.0 2,518.0 860.0 997.0 12,071.0 25,970.0 Permanent-Transient/Static
0.0 - - 0.0 0.0 - Sustained Load

1: U1+1.4DL
2: U2+1.2DL+Ws-x (Connection)
3: U3+0.9DL+Ws-x (Connection)
4: U2+1.2DL+Wp (Connection)
5: U2+1.2DL+Ws (Connection)
6: U3+0.9DL+Wp (Connection)
7: U3+0.9DL+Ws (Connection)
8: U2+1.2DL+Wp-x (Connection)
9: U3+0.9DL+Wp-x (Connection)

*⁾ The required partial safety factors for actions are included

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 2
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Resulting of the most decisive anchor forces.


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. lbf lbf lbf lbf
1 1,919.9 1,067.0 63.1 -1,065.1
2 1,581.2 593.0 63.1 -589.7
3 226.7 1,313.7 63.1 1,312.2
4 0.0 1,788.8 63.1 1,787.6
5 1,895.7 1,318.1 776.4 -1,065.1
6 1,557.1 974.9 776.4 -589.7
7 202.5 1,524.7 776.4 1,312.2
8 0.0 1,948.9 776.4 1,787.6

max. concrete compressive strain : 0.03 ‰


max. concrete compressive stress : 112 psi
Resulting tensile actions : 7,383.1 lbf , X/Y position ( -9.14 / 0.03 )
Resulting compression actions : 2,487.1 lbf , X/Y position ( 12.84 / -0.45 )

Resistance of the most decisive tensile loads.


Proof Action Capacity Utilisation βN
lbf lbf %
Steel failure 1,919.9 28,611.4 6.7
Concrete cone failure 7,383.1 18,397.3 40.1
Bond failure 7,383.1 14,800.6 49.9
Sustained load failure 0.0 11,721.3 0.0

Steel failure Table 17.3.1.1

Values taken from ICC ES Report.

Nsa ϕs ϕ Nsa Nua βN,s


lbf lbf lbf %
44,017.6 0.65 28,611.4 1,919.9 6.7

βN,s
Anchor no. % Group N° Decisive Beta
1 6.7 1 βN,s;1
2 5.5 2 βN,s;2
3 0.8 3 βN,s;3
4 0.0 4 βN,s;4
5 6.6 5 βN,s;5
6 5.4 6 βN,s;6
7 0.7 7 βN,s;7
8 0.0 8 βN,s;8

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 3
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Concrete cone failure Table 17.3.1.1

Eq.
(17.4.2.1a/1b)

Eq.
(17.4.2.1c)

Eq.
(17.4.2.2a)

Eq.
(17.4.5.1d)

Eq. (17.4.5.3)

Eq.
(17.4.2.5a/5b)

Eq. (17.4.2.6)

Ncbg ϕc ϕ Ncbg Nuag βN,cb


lbf lbf lbf %
28,303.5 0.65 18,397.3 7,383.1 40.1

βN,cb
Anchor no. % Group N° Decisive Beta
1, 2, 3, 5, 6, 7 40.1 1 βN,cb;1

Bond failure Table 17.3.1.1

Eq. (17.4.5.1a/1b)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 4
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Eq. (17.4.5.1c)

Eq. (17.4.5.1d)

Eq. (17.4.5.2)

Eq. (17.4.5.3)

Eq. (17.4.5.4a/4b)

Eq. (17.4.5.5a/5b)

Nag ϕb κb λa ϕ Nag Nuag βN,b


lbf lbf lbf %
26,910.2 0.55 1.00 1.00 14,800.6 7,383.1 49.9

βN,b
Anchor no. % Group N° Decisive Beta
1, 2, 3, 5, 6, 7 49.9 1 βN,b;1

Resistance of the most decisive shear loads.


Proof Action Capacity Utilisation βV
lbf lbf %
Steel failure 1,948.9 15,849.0 12.3
Concrete pry-out failure 1,524.7 6,073.0 25.1
Concrete edge failure 6,200.9 8,335.8 74.4

Steel failure Table 17.3.1.1

Values taken from ICC ES Report.

Vsa ϕs ϕGrout ϕ Vsa Vua βV,s


lbf lbf lbf %
26,415.1 0.60 1 15,849.0 1,948.9 12.3

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 5
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

βV,s
Anchor no. % Group N° Decisive Beta
1 6.7 1 βV,s;1
2 3.7 2 βV,s;2
3 8.3 3 βV,s;3
4 11.3 4 βV,s;4
5 8.3 5 βV,s;5
6 6.2 6 βV,s;6
7 9.6 7 βV,s;7
8 12.3 8 βV,s;8

Concrete pry-out failure Table 17.3.1.1

Eq. (17.5.3.1a/b)

Eq. (17.4.5.1a/1b)

Eq. (17.4.5.1c)

Eq. (17.4.5.1d)

Eq. (17.4.5.2)

Eq. (17.4.5.3)

Eq. (17.4.5.4a/4b)

Eq. (17.4.5.5a/5b)

Vcp ϕc ϕ Vcp Vua βV,cp


lbf lbf lbf %
8,675.7 0.70 6,073.0 1,524.7 25.1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 6
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

βV,cp
Anchor no. % Group N° Decisive Beta
1 13.0 1 βV,cp;1
2 9.8 2 βV,cp;2
3 21.6 3 βV,cp;3
4 21.9 4 βV,cp;4
7 25.1 5 βV,cp;5
6 16.1 6 βV,cp;6
5 16.1 7 βV,cp;7
8 23.8 8 βV,cp;8

Concrete edge failure Table 17.3.1.1

Eq.
(17.5.2.1a/1b)

Eq. (17.5.2.1)

Eq.
(17.5.2.1c)

Eq.
(17.5.2.2a)

Eq.
(17.5.2.2b)

Eq. (17.5.2.2)

Eq. (17.5.2.5)

Eq.
(17.5.2.6a/6b)

Eq. (17.5.2.7)

Eq. (17.5.2.8)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 7
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Vcbg ϕc λa ϕ Vcbg Vuag βV,c


lbf lbf lbf %
11,908.3 0.70 1.00 8,335.8 6,200.9 74.4

βV,c
Anchor no. % Group N° Decisive Beta
1, 2, 3, 4 14.1 1 βV,c;1
5, 6 41.9 2 βV,c;2
7, 8 8.9 3 βV,c;3
1, 2 0.7 4 βV,c;4
3, 4 74.4 5 βV,c;5
5, 6, 7, 8 25.8 6 βV,c;6

Most decisive result from tension and shear loads.

Tension loads Utilisation βN Shear Loads Utilisation βV


% %
Steel failure * 6.7 Steel failure * 12.3
Concrete cone failure 40.1 Concrete pry-out failure 25.1
Combined pull-out and concrete cone failure 49.9 Concrete edge failure 74.4
Sustained load failure 0.0

* Most unfavourable anchor

Resistance of the most decisive combined loads.

Proof successful
Eq. (17.6.3)

Non decisive load cases.


# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading βN βV β
lbf lbf lbf inlbf inlbf inlbf % % %
1 5,712. 0.0 3,917. 19,586 1,551. 28,560 Permanent-Transient/Static 34.71 37.93 37.02
0 0 .0 0 .0
0.0 - - 0.0 0.0 - Sustained Load
3 3,672. 2,518. 2,890. 997.0 95,191 101,33 Permanent-Transient/Static 43.93 71.09 82.01
0 0 0 .0 5.0
0.0 - - 0.0 0.0 - Sustained Load
4 4,956. 3,178. 0.0 2,560. 15,888 24,780 Permanent-Transient/Static 28.37 14.35 16.18
0 0 0 .0 .0
0.0 - - 0.0 0.0 - Sustained Load
5 4,796. 3,698. 0.0 940.0 18,488 23,980 Permanent-Transient/Static 27.89 14.24 15.79
0 0 .0 .0
0.0 - - 0.0 0.0 - Sustained Load
6 3,732. 2,338. 0.0 2,227. 11,691 18,660 Permanent-Transient/Static 21.39 10.77 10.09
0 0 0 .0 .0
The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 8
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

0.0 - - 0.0 0.0 - Sustained Load


7 3,572. 2,858. 0.0 1,273. 14,291 17,860 Permanent-Transient/Static 21.23 10.67 9.96
0 0 0 .0 .0
0.0 - - 0.0 0.0 - Sustained Load
8 4,896. 3,358. 860.0 1,330. 16,268 32,090 Permanent-Transient/Static 27.69 22.46 20.06
0 0 0 .0 .0
0.0 - - 0.0 0.0 - Sustained Load
9 3,672. 2,518. 860.0 997.0 12,071 25,970 Permanent-Transient/Static 20.72 19.07 13.58
0 0 .0 .0
0.0 - - 0.0 0.0 - Sustained Load

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 1 in

Profile type None

Technical Remarks
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and the
serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the actions
introduced by the anchors. For these verifications the additional provisions given in the current design method shall be taken into
account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must be sufficiently
stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the stiffness of the
plate. The proof of the necessary stiffness is not carried out by C-Fix.

The anchors must be installed in accordance with the manufacture's installation instructions. Please check the latest ICC-ES
Evaluation Report

Supplemental reinforcement: Condition A applies where supplementary reinforcement is present except for pullout and pryout
strength.
Condition B applies where supplemental reinforcement is not present and for pull out or pry out strength.

Adhesive anchors installed in horizontal or upwardly inclined orientations to resist sustained tension loads shall be continuously
inspected during installation by an inspector specially approved for this purpose by the building official. Please observe the
relevant standard.

Technical remarks for the calculation of multiple load cases


The calcualtion was done based on the input of several load cases. The software is determining the decisive load case for the
fixing itself. This can be varify to the general decisive load case in the structure. Every result has to be checked by the design
engineer and varified with the calculation of the structure.

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 9
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Installation data
Anchor
Anchor system fischer Injection system FIS EM
plus
Injection resin FIS EM Plus 390 S (other cartridge Art.-No. 544174
sizes available)
Fixing element Threaded rod FIS A M 20 x 245 8.8, Art.-No. 519404
zinc plated steel, Property Class 8.8

Accessories Dispenser FIS DM S Art.-No. 511118


SDS Plus-V II 24/200/250 Art.-No. 531853
or alternatively
FHD Max 24/400/620 Art.-No. 546604
Hammer drilling with or without
suction
Alternative cartdriges FIS EM Plus 585 S Art.-No. 544157
FIS EM Plus 1500 S Art.-No. 544173
The shown cartdriges are
alternative to the highlighted
one above with the same approval
number.

Installation details
Thread diameter M 20
Drill hole diameter d0 = 24 mm
Drill hole depth -
Calculated anchorage hef = 6.00 in
depth
Drilling method Hammer drilling
Drill hole cleaning
Installation type Push-through installation
Annular gap Annular gap filled
Maximum torque Tinst,max = 1,062.1 inlbf
Socket size 30 mm
Base plate thickness t = 0.50 in
Total fixing thickness tfix = 0.50 in
Tfix,max
Volume of resin per drill 40 ml/20 scale divisions
hole

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 10
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
03/08/2023

Base plate details


Base plate material Not available
Base plate thickness t = 0.50 in
Clearance hole in base df=0.94 in
plate

Attachment
Profile type None

Anchor coordinates

x y
Anchor no. in in
1 -12 3
2 -8 3
3 8 3
4 12 3
5 -12 -3
6 -8 -3
7 8 -3
8 12 -3

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the
license agreement of the Software.

Page 11