Project: 4-STY COMMERCIAL MIXED USE BUILDING Doc.

Title: STRUCTURAL ANALYSIS AND DESIGN


(SEISMIC LOAD ANALYSIS)
Location: CABAROAN.CITY OF SAN FERNANDO, LA UNION Proj. Ref.:
Date:
Owner : ALHUDA CENTER LA UNION Prepared by: ENGR. MICHELLE ROSE F. BERNARDO

SEISMIC LOAD ANALYSIS

PARAMETERS VALUE
Seismic Source Type A
Zone 4
Importance Factor 1
Rw in X Direction (RWX) 8.5
Rw in Z Direction (RWZ) 8.5
Soil Profile Type (STYP) 4
CT Value 0.0731
Total Building Height, h*, m 14.3
Closest Dist. To Seismic Source,km 14.7
Total Seismic Load, W, kN 6667.05
* excl roofing height, incl footing height

Seismic Zone Factor, Z 0.40


Near Source Factor, Na 1.00 ≥10 km
Near Source Factor, Nv 1.01 14.7 km
Seismic Coefficient,Ca 0.44
Seismic Coefficient,Cv 0.65

DESIGN BASE SHEAR

𝑇 = 𝐶𝑡(ℎ) / 0.538 sec


< 0.70 sec therefore Ft = 0

X-Direction Z-Direction

𝐶𝑣𝐼𝑊 208-8
𝑉= 945.05 kN 945.05 kN
𝑅𝑇

Need not exceed


208-9
2.5𝐶𝑎𝐼𝑊 862.79 kN 862.79 kN
𝑉=
𝑅
Shall not be less than
208-10
𝑉 = 0.11𝐶𝑎𝐼𝑊 322.69 kN 322.69 kN

For Zone 4, should not be less than


0.8𝑍𝑁𝑣𝐼𝑊 208-11
𝑉= 254.01 kN 254.01 kN
𝑅

PREVAILING BASE SHEAR 862.79 kN 862.79 kN


If Ft ≠ 0 If Ft ≠ 0
Ft = 0.07TV Ft = 0.07TV
32.47 = 32.47
<0.25V 215.70 <0.25V 215.70

CORELINE BUILDERS Page 1 of 1