Project : Banha 1st Taxes Building

- PANEL REF: DP-AC1 power system : FEEDER : (4X25+1X16)mm2 CU/XLPE/PVC


- PANEl TYPE : POWER CIRCUIT BREAKER TRIP (A) : 80 VOLTAGE DROP % :
- PANEL LOCATION : CIRCUIT BREAKER FRAME (A) : 80
- NO.OF WAYS : 24 CIRCUIT BREAKER S.C (KA) : 16
- MOUNTING : FLUSH MOUNTED CIRCUIT BREAKER TYPE : MCCB
- IP DEGREE : CIRCUIT BREAKER POLES : 3
-

- PHASE PHASE
circuit Number Connected Load R Y B LOAD DESCRIPTION C.B TRIP AMPS (A) CABLE /WIRE mm2 circuit Number Connected Load R Y B LOAD DESCRIPTION C.B TRIP AMPS (A) CABLE /WIRE mm2
FAN-01 125 125 FAN MCB (1P) - 26A (3X4) MM2 CU/PVC AC-13 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-02 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC SPARE SPARE SPARE MCB (1P) - 32A SPARE
FAN-03 125 125 FAN MCB (1P) - 26A (3X4) MM2 CU/PVC AC-15 1437.5 1438 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-04 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC AC-16 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-05 3575 3575 AIR CONDITIONER MCB (1P) - 32A (3X6) MM2 CU/PVC SPARE SPARE SPARE MCB (1P) - 32A SPARE
AC-06 1437.5 1438 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC AC-18 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-07 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC AC-19 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-08 3575 3575 AIR CONDITIONER MCB (1P) - 32A (3X6) MM2 CU/PVC SPARE SPARE SPARE MCB (1P) - 32A SPARE
AC-09 1437.5 1438 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC AC-21 4250 4250 AIR CONDITIONER MCB (1P) - 32A (3X6) MM2 CU/PVC
AC-10 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC AC-22 2200 2200 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC
AC-11 4250 4250 AIR CONDITIONER MCB (1P) - 32A (3X6) MM2 CU/PVC SPARE SPARE SPARE MCB (1P) - 32A SPARE
AC-12 1437.5 1438 AIR CONDITIONER MCB (1P) - 32A (3X10) MM2 CU/PVC SPARE SPARE SPARE MCB (1P) - 32A SPARE
- -
-

- R Y B BALANCE = 23.16%

TOTAL PHASE LOAD 15525.00 13600.00 12325.00


TOTAL CONNECTED LOAD (KVA) 41.5
FAN DEMAND FACTOR: 0.8
AIR CONDITIONER DEMAND FACTOR: 0.8
AIR CONDITIONER DEMAND FACTOR: 0.8

TOTAL DEMAND LOAD (KVA) 33.2


STEP 1 : MAI

PANEL NAME

DP-AC1
CIRCUIT ABBREVIATION

LTG1

LTG2

FAN1

FAN2

NS1

NS2

PS1

PS2

WH1

WH2

HD

AC1

AC2

AC3

EO1

EO2

PANEL1

PANEL2

MTR
STEP 1 : MAIN SETTINGS

PANEL TYPE "OPTIONAL"

POWER

STEP 2: CIRCUITS S
CIRCUIT DESCRIPTIION

LIGHTING

LIGHTING

FAN

FAN

NORMAL SOCKET

NORMAL SOCKET

POWER SOCKET

POWER SOCKET

WATER HEATER

WATER HEATER

HAND DRYER

AIR CONDITIONER

AIR CONDITIONER

AIR CONDITIONER

ELECTRIC OUTLET

ELECTRIC OUTLET

PANEL BOARD

PANEL BOARD

MOTOR
P 1 : MAIN SETTINGS
NUMBER OF CIRCUITS
"OPTIONAL" SPARE PERCENATGE %

24 5
STANDARD CIRCUIT NUMBERS.
CUSTOM CIRCUIT NUMBERS
(1R-3Y-5B)(2R-4Y-6B)
(1R-2Y-3B)(4R-5Y-6B)
VOLT-AMPERES
WATTS

STEP 2: CIRCUITS SETTINGS


CIRCUIT PHASE BRANCH C.B TRIP (A)

SINGLE PHASE MCB (1P) - 16A

SINGLE PHASE MCB (1P) - 16A

SINGLE PHASE MCB (1P) - 26A

THREE PHASE MCB (3P) - 20A

SINGLE PHASE MCB (1P) - 20A

SINGLE PHASE MCB (1P) - 20A

SINGLE PHASE MCB (1P) - 16A

THREE PHASE MCB (3P) - 20A

SINGLE PHASE MCB (1P) - 25A

SINGLE PHASE MCB (1P) - 16A

SINGLE PHASE MCB (1P) - 16A

SINGLE PHASE MCB (1P) - 32A

SINGLE PHASE MCB (1P) - 40A

THREE PHASE MCB (3P) - 20A

SINGLE PHASE MCB (1P) - 16A

THREE PHASE MCB (1P) - 16A

SINGLE PHASE MCB (1P) - 16A

THREE PHASE MCCB (3P) - 32A

THREE PHASE MCB (3P) - 20A


CLEAR IN
BALANCE PERCENTAGE %

10
IT NUMBERS.
T NUMBERS
R-4Y-6B)
R-5Y-6B)
ERES
S

GS
BREANCH CABLE C.S.A DEMAND FACTOR

(3X3) MM2 CU/PVC 1

(3X3) MM2 CU/PVC 1

(3X4) MM2 CU/PVC 0.8

(5X4) MM2 CU/PVC 0.8

(3X3) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(5X4) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(3X6) MM2 CU/PVC 0.8

(3X10) MM2 CU/PVC 0.8

(3X6) MM2 CU/PVC 0.8

(5X4) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(3X4) MM2 CU/PVC 0.8

(3X6) MM2 CU/PVC 0.8

(5X10) MM2 CU/PVC 0.8

(5X6) MM2 CU/PVC 0.8


0 0
CLEAR INPUT DATA
CIRCUIT PREFIX

FAN

FAN

PS

PS

WH

WH

HD

AC

AC

AC

EO

EO

PNL

PNL

MTR
SINGLE PHASE FAN1
SINGLE PHASE AC1
SINGLE PHASE AC2
FAN1 250
AC1 25550
AC2 15650
0
0
0
0
0
STEP 3 IS OK PROCEED TO STEP 4

STEP 3 : ASSIGN CIRCUIT TYPES


CIRCUITS POWER

1/DP-AC1 125

2/DP-AC1 125

3/DP-AC1 2200

4/DP-AC1 2200

5/DP-AC1 1437.5

6/DP-AC1 2200

7/DP-AC1 2200

8/DP-AC1 1437.5

9/DP-AC1 1437.5

10/DP-AC1 2200

11/DP-AC1 1437.5

12/DP-AC1 2200

13/DP-AC1 2,200

14/DP-AC1 2200

15/DP-AC1 2200

16/DP-AC1 4250

17/DP-AC1 4250

18/DP-AC1 3575

19/DP-AC1 3575
GROUP1
GROUP2
GROUP3
GROUP1
GROUP2
GROUP3
GROUP4
GROUP5
GROUP6
GROUP7
GROUP8

0.8 FAN
0.8 AIR CONDITIONER
0.8 AIR CONDITIONER
0
0
0
0
P4

T TYPES
LOAD NAME

FAN1

FAN1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC1

AC2

AC2

AC2

AC2
1 GROUP1
6 GROUP2
#VALUE! GROUP3
#VALUE!
#VALUE!
#VALUE!
#VALUE!
BALANCE PERCENTAG

10

10

PANEL WAYS = 24

STEP 4 : CHOOSE SPARE TYPES

Spare Remaining: 0
CIRCUIT NAME CIRCUIT COUNTER SPARE

FAN1 2 - (1) 5

AC1 13 - (4)

AC2 4 - (2)
REPEAT TIMES
5 1 SPARE1
2 SPARE2
3 SPARE3
4 SPARE4
5 SPARE5
6 SPARE6
7 SPARE7
8 SPARE8
9 SPARE9
10 SPARE10
11 SPARE11
12 SPARE12
13 SPARE13
14 SPARE14
15 SPARE15
16 SPARE16
17 SPARE17
18 SPARE18
19 SPARE19
20 SPARE20
21 SPARE21
22 SPARE22
23 SPARE23
24 SPARE24
25 SPARE25
26 SPARE26
27 SPARE27
28 SPARE28
29 SPARE29
30 SPARE30
31 SPARE31
32 SPARE32
33 SPARE33
34 SPARE34
35 SPARE35
36 SPARE36
37 SPARE37
38 SPARE38
39 SPARE39
40 SPARE40
41 SPARE41
42 SPARE42
43 SPARE43
44 SPARE44
45 SPARE45
46 SPARE46
47 SPARE47
48 SPARE48
49 SPARE49
50 SPARE50
0 0 0
24

CU

STEP 5 : Run Phase Analysis

RUN PHASE BALANCE


ANALYSIS
RUN PHASE BALANCE
ANALYSIS

NO. OF SPARES

1
GENERATE PANEL LOAD
SCHEDULE

BACK TO
HOME
10

15
16

GROUP1 GROUP1
GROUP1 GROUP2
GROUP1 GROUP3
GROUP1
GROUP1
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
GROUP2
0 0
E
E

1 NS1 25 - (5)

1
D
0

#N/A
BACK TO
HOME

#N/A
FAN1
AC1
AC2
0 0 0
SINGLE PHASE
0 0
NO. OF SPARES POWER

5 1

0
0 0
2

KVA

1
SPARE LEFT TOTAL

5 2

0 13

0 4

19
0 0
EMPTY

GROUP1

GROUP2

GROUP3

CU
0

0 0 0 0
0

0
0 0 0

0 0 0 0 0
LIGHTING

POWER

HEATER

A/C
0
0 0 0
A/C

POWER
0 0 0 00 0 0 0
0%

10%

20%

30%

40%

50%
0 0 0 0 0 0 0
0

24

19

FAN1 1/DP-AC1 125

FAN1 2/DP-AC1 125

AC1 3/DP-AC1 2200

AC1 4/DP-AC1 2200

AC1 5/DP-AC1 1437.5

AC1 6/DP-AC1 2200

AC1 7/DP-AC1 2200

AC1 8/DP-AC1 1437.5

AC1 9/DP-AC1 1437.5

AC1 10/DP-AC1 2200

AC1 11/DP-AC1 1437.5

AC1 12/DP-AC1 2200


AC1 13/DP-AC1 2200

AC1 14/DP-AC1 2200

AC1 15/DP-AC1 2200

AC2 16/DP-AC1 4250

AC2 17/DP-AC1 4250

AC2 18/DP-AC1 3575

AC2 19/DP-AC1 3575

SPARE1 SPARE1 1

SPARE2 SPARE2 1

SPARE3 SPARE3 1

SPARE4 SPARE4 1

SPARE5 SPARE5 1
0 0 0 0
24

SPARE COUNT TOTAL

5 24

true spare

GROUP1

GROUP1

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2

GROUP2
GROUP2

GROUP2

GROUP2

GROUP3

GROUP3

GROUP3

GROUP3

GROUP1

GROUP1

GROUP1

GROUP1

GROUP1

1
0 0 0 0
SPAREPERCENTAGE

5 2
0 0 0 0 0 0 0
phase per load type load type counter
THREE PHASE 0
SINGLE PHASE 2
4
0 0 0
total number of panel ways
19 20
24 STANDARD

24 CUSTOM

24 CUSTOM
0 0 0 0